SUPPLY OF CURRENT TRANSFORMER
189020059 - CURRENT TRANSFORMER OUTDOOR OIL FILLED HERMATICALLY SEALED POLYMER INSULATOR TYPE. FREQUENCY: 50 Hz, INSULATION LEVEL : 230/550 Kv, RATED VOLTAGE: 145 KV, SHORT CIRCUIT CURRENT : 40KA/1 sec, RATED CONTINUES CURRENT : 100 A, Rated Continues Thermal Current : 120%, 3 CORES:- CORE I - 100/1, 15VA, Class -1 , CORE II - 100/1 , 15VA, Class - 5P, ALF -20, CORE III - 100/1, Class- PS, Minimum Knee point Voltage Vk - 375V , Maximum Existing current at Vk - 100mA, Make : TELK,GE, HITACHI ENERGY, CG,TOSHIBA. NB : Terminal Connector suitable for ACSR Kundah Conductor ( 26.7mm) shall also be supplied along with CTs. as per GTP attached. Necessary drawings viz. outline diagram, GAD, Terminal connection Diagram (Rating & connection plate) along with standard QAP shall be attached along with the offer. Standard Acceptance tests as per relevant IS shall be included in the scope of supply.