The World Health Organization (WHO) Country Office in Ukraine invites you to submit your proposal for the following tender procedure: Invitation to Bid (ITB) 2026/EURO/UKR/0299 – Supply, Installation and Commissioning of Battery Energy Storage Systems (ESS) and Online UPS Systems for Healthcare Facilities in Ukraine (Mykolaiv and Kharkiv Oblasts). Please note that bidders may submit proposals for one, several, or all lots. Each lot has a corresponding Technical Proposal Annex containing detailed technical specifications and compliance requirements. Bidders shall complete and submit only the Annex(es) corresponding to the item(s)/lot(s) for which they are submitting a bid. The tender includes two categories of equipment: Battery Energy Storage Systems (ESS) and Online UPS Systems intended to provide backup power supply for various types of medical equipment. Bidders are encouraged to review the technical requirements for each lot and submit proposals for the lots that match their product portfolio and capabilities. The evaluation will be conducted separately for each hospital. WHO reserves the right to award one or more contracts on a per-hospital basis and may select different suppliers for different hospitals. Award decisions will be based on the evaluation of the received bids, including technical compliance, supplier capacity, and proposed delivery timelines. The list of documents required under this ITB is specified in Section 7: Returnable Forms and includes the following: Form A: Letter of Intent Form B: Self-Declaration Form Form C: Bidder Information Form Form D: Technical Bid Form with the corresponding Annex(es) Form E: Financial Proposal Form F: Confidentially Undertaking Form G: Manufacturer’s Authorization Form If you are interested in submitting a bid in response to this ITB: Please acknowledge receipt of this ITB by completing and returning the Letter of Intent, indicating your intention to submit a bid or not, no later than Wednesday, November 25, 2026 Please submit any requests for clarification no later than Wednesday, November 25, 2026 Please prepare your bid in accordance with the requirements and procedures outlined in this ITB and submit it no later than 17:00 Kyiv time Tuesday, December 1, 2026 All WHO vendors are required to comply with the United Nations Supplier Code of Conduct. We encourage all Proposers to join the United Nations Global Compact and support the Women’s Empowerment Principles (WEP). We look forward to receiving your competitive bid. Best regards, WHO Ukraine Procurement
323126
WHO ITB 2026/EURO/UKR/0299
Invitation to bid
Ukraine
INVITATION
+02:00
21 Nov 2026
19 Nov 2026
Form E. Financial Proposal Bidders are requested to complete columns 5–8 of this template. When completing the template, please note the following:
Supply, Installation and Commissioning of Battery Energy Storage Systems (ESS) and Online UPS Systems for Healthcare Facilities in Ukraine (Mykolaiv and Kharkiv Oblasts) 1. The proposal currency shall be either UAH or USD. Please indicate the selected currency in the corresponding column.
2. The offer shall include the full cost of the equipment, including all required accessories, installation, commissioning, training, and delivery to the designated site.
ITB: 2026/EURO/UKR/0299 3. For Ukrainian companies, the offered prices shall include VAT and all applicable taxes and charges. For international companies, the offered prices shall exclude VAT. Customs clearance formalities will be arranged by WHO upon delivery of the goods to Ukraine.
4. Conversion to/from currencies other than US Dollars will be made based on the official UN currency rates published at: https://treasury.un.org/operationalrates/OperationalRates.php.
5. The completed document shall be stamped (if applicable), signed, and submitted in PDF format.
Prepared by: (please indicate your company name)
No. Description (as per Technical Specifications) UoM Qty Currency Unit Price Total Price Offered Item / Specification
1 Supply, Installation and Commissioning of a 50 kW Battery Energy Storage System (ESS) with 50 kWh Battery Storage for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council set 3 0.00
2 Supply, Installation and Commissioning of a 40 kW Battery Energy Storage System (ESS) with 40 kWh Battery Storage for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council set 1 0.00
3 Supply, Installation and Commissioning of a 30 kW Battery Energy Storage System (ESS) with 30 kWh Battery Storage for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council set 1 0.00
4 Supply, Installation and Commissioning of an 80 kVA Online UPS System for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council (for the X-ray Calypso F) set 1 0.00
5 Supply, Installation and Commissioning of a 120 kVA Online UPS System for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council (for CT OPTIMA CT 520, General Electric, nominal power capacity: 90 kVA) set 1 0.00
6 Supply, Installation and Commissioning of an 80 kVA Online Uninterruptible Power Supply (UPS) System for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Clinical Hospital" of the Mykolaiv Oblast Council to Ensure Backup Power Supply for the Calypso F MTO ES (50 kW, 380 V) set 2 0.00
7 Supply, Installation and Commissioning of a 1 kVA Online Uninterruptible Power Supply (UPS) System for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Clinical Hospital" of the Mykolaiv Oblast Council to Ensure Backup Power Supply for the Huvitz HOCT-1F Eye Tomography System (220 V) set 1 0.00
8 Supply, Installation and Commissioning of a 4 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Clinical Hospital" of the Mykolaiv Oblast Council to Ensure Backup Power Supply for Equipment in the Dental, Pathology, and Ultrasound Departments set 3 0.00
9 Supply, Installation and Commissioning of a 12 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Clinical Hospital" of the Mykolaiv Oblast Council to Ensure Backup Power Supply for the KeenRAY DR50M, uDR 730i, and GMM (General Medical Merate) MAC D Mobile Radiographic Systems set 3 0.00
10 Supply, Installation and Commissioning of a 120 kVA Online Uninterruptible Power Supply (UPS) System for the Communal Non-Commercial Enterprise "City Hospital No. 3" of the Mykolaiv City Council to Ensure Backup Power Supply for the CT Revolution Maxima Computed Tomography System set 1 0.00
11 Supply, Installation and Commissioning of an 80 kVA Online UPS System for the Communal Non-Commercial Enterprise "City Hospital No. 3" of the Mykolaiv City Council (for the X-ray Calypso F) set 1 0.00
12 Supply, Installation and Commissioning of a 14 kW Battery Energy Storage System (ESS) (220 V) with 16 kWh Battery Storage for the Communal Non-Commercial Enterprise "City Hospital No. 3" of the Mykolaiv City Council to Ensure Backup Power Supply for the Symbol XL and Symbol 5R9 C-Arm Systems set 3 0.00
13 Supply, Installation and Commissioning of a 50 kW Battery Energy Storage System (ESS) (380 V) with 50 kWh Battery Storage for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Oncology Centre" of the Mykolaiv Oblast Council set 4 0.00
14 Supply, Installation and Commissioning of a 50 kW Battery Energy Storage System (ESS) (380 V) with 50 kWh Battery Storage for the Communal Non-Commercial Enterprise "City Hospital No. 4" of the Mykolaiv City Council (Branch: City Children's Hospital No. 2) set 1 0.00
15 Supply, Installation and Commissioning of a 120 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the SOMATOM go.Up Computed Tomography System manufactured by Siemens GmbH (Nominal Power Capacity: 80 kVA) set 1 0.00
16 Supply, Installation and Commissioning of a 120 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the X-Ray System set 2 0.00
17 Supply, Installation and Commissioning of a 6 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for Ultrasonic Equipment set 9 0.00
18 Supply, Installation and Commissioning of a 3 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for Intensive Care Unit (ICU) Equipment set 2 0.00
19 Supply, Installation and Commissioning of a 6 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for Laboratory Equipment set 9 0.00
20 Supply, Installation and Commissioning of a 20 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the C-Arm Imaging System set 1 0.00
21 Supply, Installation and Commissioning of a 30 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the Mammography System set 1 0.00
22 Supply, Installation and Commissioning of a 30 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the Fluorography System set 1 0.00
23 Supply, Installation and Commissioning of a 6 kVA Online Uninterruptible Power Supply (UPS) System (220V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the Dental Computed Tomography (CT) System set 1 0.00
24 Supply, Installation and Commissioning of a 140 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Municipal Non-Commercial Enterprise "Chuhuiv Central Hospital named after M.I. Kononenko" to Ensure Backup Power Supply for the Helios DRF Digital X-Ray System (Nominal Capacity: 90 kW) set 1 0.00
25 Supply, Installation and Commissioning of a 100 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Municipal Non-Commercial Enterprise "Chuhuiv Central Hospital named after M.I. Kononenko" to Ensure Backup Power Supply for the Polistat-M X-Ray System set 1 0.00
26 Supply, Installation and Commissioning of a 100 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Municipal Non-Commercial Enterprise "Chuhuiv Central Hospital named after M.I. Kononenko" to Ensure Backup Power Supply for the Hitachi Supria 32 X-Ray System set 1 0.00
27 Supply, Installation and Commissioning of a 3 kVA Online Uninterruptible Power Supply (UPS) System (220V) for the Municipal Non-Commercial Enterprise "Chuhuiv Central Hospital named after M.I. Kononenko" to Ensure Reliable Backup Power Supply for Critical Medical Equipment set 30 0.00
PLEASE SPECIFY:
Proposed Completion Time
Please confirm your acceptance of the standard payment terms: payment within 30 days after successful delivery, installation, commissioning, training, and acceptance of the equipment.
Annex 1. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 50 kW Battery Energy Storage System (ESS) with 50 kWh Battery Storage for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to critical medical equipment, including a hybrid inverter, MPPT solar charge controller, battery energy storage system, and battery charge/discharge monitoring functions.
Technical Specifications
Rated AC output power (inverter) Min 50 kW
Inverter type Hybrid
Output waveform Pure sine wave
Output voltage/frequency 380 V AC, 50 Hz
Input voltage 380 V
Battery type / voltage / minimum capacity LiFePO₄ / 48 V / min 50 kWh
Maximum battery charging time from DoD 20% Not more than 2 hours
System scalability Yes. The system shall support parallel operation of at least four units for capacity expansion and redundancy.
Control functions / modes Modes: “Grid + PV”, “Battery + PV/Grid”, automatic switching, power priority. Ability to limit battery charging currents.
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; MPPT overcurrent/overvoltage; battery overcharge and over-discharge protection via BMS.
Efficiency 93–97 %
Automatic transfer switching ≤ 10 ms
Interfaces RS485, CAN, USB, Wi-Fi / Ethernet. Mobile app for remote monitoring and configuration.
Operating temperature –10 °C to +55 °C
Humidity Up to 95 % non-condensing
Enclosure protection degree Not lower than IP21
Noise level Not more than 55 dB
Mounting type Wall-mounted or floor-standing
Additional Requirements
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The ESS shall ensure uninterrupted operation under unstable grid conditions and provide automatic transfer switching without interruption to the connected equipment (UPS function). A battery rack and BMS shall be included, where applicable. A Wi‑Fi module shall be supplied if required for commissioning.
The supply set shall include a Ukrainian-language user manual and a detailed electrical installation diagram.
The Supplier shall provide brief training to hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of conformity (UA certificate) for the hybrid inverter and battery or for the complete system
EMC safety certificates IEC / EN 61000-6-1 / 2 / 3 / 4 (If applicable)
Power converter safety IEC / EN 62109-1, IEC / EN 62109-2
Lithium-ion / lithium battery safety for stationary / energy storage systems IEC 62619
Safety testing for transport of lithium batteries / accumulators / ESS UN 38.3; IEC 61439‑1 / IEC 61439‑2
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP, Pervomaisk City, Mykolaiv Oblast, Ukraine
Annex 2. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 40 kW Battery Energy Storage System (ESS) with 40 kWh Battery Storage for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to critical medical equipment, including a hybrid inverter, an MPPT solar charge controller, battery energy storage system, and battery charge/discharge monitoring functions.
Technical Specifications
Rated AC output power (inverter) Min 40 kW
Inverter type Hybrid
Output waveform Pure sine wave
Output voltage/frequency 380 V AC, 50 Hz
Input voltage 380 V
Battery type / voltage / minimum capacity LiFePO₄ / 48 V / min 40 kWh
Maximum battery charging time from DoD 20% Not more than 2 hours
System scalability Yes. The system shall support parallel operation of at least four units for capacity expansion and redundancy.
Control functions / modes Modes: “Grid + PV”, “Battery + PV/Grid”, automatic switching, power priority. Ability to limit battery charging currents.
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; MPPT overcurrent/overvoltage; battery overcharge and over-discharge protection via BMS.
Efficiency 93–97 %
Automatic transfer switching ≤ 10 ms
Interfaces RS485, CAN, USB, Wi-Fi / Ethernet. Mobile app for remote monitoring and configuration.
Operating temperature –10 °C to +55 °C
Humidity Up to 95 % non-condensing
Enclosure protection degree Not lower than IP21
Noise level Not more than 55 dB
Mounting type Wall-mounted or floor-standing
Additional Requirements
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The ESS shall ensure uninterrupted operation under unstable grid conditions and provide automatic transfer switching without interruption to the connected equipment (UPS function). A battery rack and BMS shall be included, where applicable. A Wi‑Fi module shall be supplied if required for commissioning.
The supply set shall include a Ukrainian-language user manual and a detailed electrical installation diagram.
The Supplier shall provide brief training to hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of conformity (UA certificate) for the hybrid inverter and battery or for the complete system
EMC safety certificates IEC / EN 61000-6-1 / 2 / 3 / 4 (If applicable)
Power converter safety IEC / EN 62109-1, IEC / EN 62109-2
Lithium-ion / lithium battery safety for stationary / energy storage systems IEC 62619
Safety testing for transport of lithium batteries / accumulators / ESS UN 38.3; IEC 61439‑1 / IEC 61439‑2
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP, Pervomaisk City, Mykolaiv Oblast, Ukraine
Annex 3. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 30 kW Battery Energy Storage System (ESS) with 30 kWh Battery Storage for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, primarily in ICUs, including a hybrid inverter, an MPPT solar charge controller, battery charge/discharge monitoring, and an energy storage system.
Technical Specifications
Rated AC output power (inverter) Min 30 kW
Inverter type Hybrid
Output waveform Pure sine wave
Output voltage/frequency 220 V AC, 50 Hz
Input voltage 220 V±10%
Battery type / voltage / minimum capacity LiFePO₄ / 48 V / min 30 kWh
Maximum battery charging time from DoD 20% Not more than 2 hours
System scalability Yes. The system shall support parallel operation of at least four units for capacity expansion and redundancy.
Control functions / modes Modes: “Grid + PV”, “Battery + PV/Grid”, automatic switching, power priority. Ability to limit battery charging currents.
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; MPPT overcurrent/overvoltage; battery overcharge and over-discharge protection via BMS.
Efficiency 93–97 %
Automatic transfer switching ≤ 10 ms
Interfaces RS485, CAN, USB, Wi-Fi / Ethernet. Mobile app for remote monitoring and configuration.
Operating temperature –10 °C to +55 °C
Humidity Up to 95 % non-condensing
Enclosure protection degree Not lower than IP21
Noise level Not more than 55 dB
Mounting type Wall-mounted or floor-standing
Additional Requirements
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The ESS shall ensure uninterrupted operation under unstable grid conditions and provide automatic transfer switching without interruption to the connected equipment (UPS function). A battery rack and BMS shall be included, where applicable. A Wi‑Fi module shall be supplied if required for commissioning.
The supply set shall include a Ukrainian-language user manual and a detailed electrical installation diagram.
The Supplier shall provide brief training to hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of conformity (UA certificate) for the hybrid inverter and battery or for the complete system
EMC safety certificates IEC / EN 61000-6-1 / 2 / 3 / 4 (If applicable)
Power converter safety IEC / EN 62109-1, IEC / EN 62109-2
Lithium-ion / lithium battery safety for stationary / energy storage systems IEC 62619
Safety testing for transport of lithium batteries / accumulators / ESS UN 38.3; IEC 61439‑1 / IEC 61439‑2
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP, Pervomaisk City, Mykolaiv Oblast, Ukraine
Annex 4. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of an 80 kVA Online UPS System for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council (for the X-ray Calypso F) 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 80 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be an 80 kVA online UPS designed to provide backup power supply for the Calypso F X-Ray System installed at the premises of the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP, Pervomaisk City, Mykolaiv Oblast, Ukraine
Annex 5. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 120 kVA Online UPS System for the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council (for CT OPTIMA CT 520, General Electric, nominal power capacity: 90 kVA) 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 120 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 120 kVA online UPS designed to provide backup power supply for the General Electric OPTIMA CT 520 CT Scanner (nominal power capacity: 90 kVA) installed at the premises of the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP, Pervomaisk City, Mykolaiv Oblast, Ukraine
Annex 6. Technical Proposal Information for bidders:
Installation, Testing, and Commissioning of an 80 kVA Online Uninterruptible Power Supply (UPS) System for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Clinical Hospital" of the Mykolaiv Oblast Council to Ensure Backup Power Supply for the Calypso F MTO ES (50 kW, 380 V) 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 80 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be compatible with and intended to provide backup power supply for the Calypso F MTO ES (50 kW, 380 V) installed at the facility. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 7. Technical Proposal Information for bidders:
Installation, Testing, and Commissioning of a 1 kVA Online Uninterruptible Power Supply (UPS) System for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Clinical Hospital" of the Mykolaiv Oblast Council to Ensure Backup Power Supply for the Huvitz HOCT-1F Eye Tomography System (220 V) 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 1 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 1 kVA online UPS designed to provide backup power supply for the Huvitz HOCT-1F Eye Tomography System (220 V) installed at the premises of the hospital. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 8. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 4 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Clinical Hospital" of the Mykolaiv Oblast Council to Ensure Backup Power Supply for Equipment in the Dental, Pathology, and Ultrasound Departments 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 4 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 4 kVA online UPS designed to provide backup power supply for medical equipment used in the Dental, Pathology, and Ultrasound Departments. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 9. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 12 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Clinical Hospital" of the Mykolaiv Oblast Council to Ensure Backup Power Supply for the KeenRAY DR50M, uDR 730i, and GMM (General Medical Merate) MAC D Mobile Radiographic Systems 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 12 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 12 kVA online UPS designed to provide backup power supply for the for the the the KeenRAY DR50M, uDR 730i, and GMM (General Medical Merate) MAC D Mobile Radiographic Systems. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 10. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 120 kVA Online Uninterruptible Power Supply (UPS) System for the Communal Non-Commercial Enterprise "City Hospital No. 3" of the Mykolaiv City Council to Ensure Backup Power Supply for the CT Revolution Maxima Computed Tomography System 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 120 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be compatible with and intended to provide backup power supply for the CT Revolution Maxima Computed Tomography System installed at the facility. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 11. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of an 80 kVA Online UPS System for the Communal Non-Commercial Enterprise "City Hospital No. 3" of the Mykolaiv City Council (for the X-ray Calypso F) 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 80 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be compatible with and intended to provide backup power supply for the X-ray Calypso F installed at the facility. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 12. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 14 kW Battery Energy Storage System (ESS) (220 V) with 16 kWh Battery Storage for the Communal Non-Commercial Enterprise "City Hospital No. 3" of the Mykolaiv City Council to Ensure Backup Power Supply for the Symbol XL and Symbol 5R9 C-Arm Systems 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, primarily in ICUs, including a hybrid inverter, an MPPT solar charge controller, battery charge/discharge monitoring, and an energy storage system.
Technical Specifications
Rated AC output power (inverter) Min 14 kW
Inverter type Hybrid
Output waveform Pure sine wave
Output voltage/frequency 220 V AC, 50 Hz
Input voltage 220 V
Battery type / voltage / minimum capacity LiFePO₄ / 48 V / min 16 kWh
Maximum battery charging time from DoD 20% Not more than 2 hours
System scalability Yes. The system shall support parallel operation of at least four units for capacity expansion and redundancy.
Control functions / modes Modes: “Grid + PV”, “Battery + PV/Grid”, automatic switching, power priority. Ability to limit battery charging currents.
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; MPPT overcurrent/overvoltage; battery overcharge and over-discharge protection via BMS.
Efficiency 93–97 %
Automatic transfer switching ≤ 10 ms
Interfaces RS485, CAN, USB, Wi-Fi / Ethernet. Mobile app for remote monitoring and configuration.
Operating temperature –10 °C to +55 °C
Humidity Up to 95 % non-condensing
Enclosure protection degree Not lower than IP21
Noise level Not more than 55 dB
Mounting type Wall-mounted or floor-standing
Additional Requirements
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The ESS shall ensure uninterrupted operation under unstable grid conditions and provide automatic transfer switching without interruption to the connected equipment (UPS function). A battery rack and BMS shall be included, where applicable. A Wi‑Fi module shall be supplied if required for commissioning.
The supply set shall include a Ukrainian-language user manual and a detailed electrical installation diagram.
The Supplier shall provide brief training to hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of conformity (UA certificate) for the hybrid inverter and battery or for the complete system
EMC safety certificates IEC / EN 61000-6-1 / 2 / 3 / 4
Power converter safety IEC / EN 62109-1, IEC / EN 62109-2
Lithium-ion / lithium battery safety for stationary / energy storage systems IEC 62619
Safety testing for transport of lithium batteries / accumulators / ESS UN 38.3; IEC 61439‑1 / IEC 61439‑2
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 13. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 50 kW Battery Energy Storage System (ESS) (380 V) with 50 kWh Battery Storage for the Communal Non-Commercial Enterprise "Mykolaiv Oblast Oncology Centre" of the Mykolaiv Oblast Council 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, primarily in ICUs, including a hybrid inverter, an MPPT solar charge controller, battery charge/discharge monitoring, and an energy storage system.
Technical Specifications
Rated AC output power (inverter) Min 50 kW
Inverter type Hybrid
Output waveform Pure sine wave
Output voltage/frequency 380 V AC, 50 Hz
Input voltage 380 V
Battery type / voltage / minimum capacity LiFePO₄ / 48 V / min 50 kWh
Maximum battery charging time from DoD 20% Not more than 2 hours
System scalability Yes. Device must support parallel operation with the ability to combine at least 4 units to increase power or provide redundancy.
Control functions / modes Modes: “Grid + PV”, “Battery + PV/Grid”, automatic switching, power priority. Ability to limit battery charging currents.
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; MPPT overcurrent/overvoltage; battery overcharge and over-discharge protection via BMS.
Efficiency 93–97 %
Automatic transfer switching ≤ 10 ms
Interfaces RS485, CAN, USB, Wi-Fi / Ethernet. Mobile app for remote monitoring and configuration.
Operating temperature –10 °C to +55 °C
Humidity Up to 95 % non-condensing
Enclosure protection degree Not lower than IP21
Noise level Not more than 55 dB
Mounting type Wall-mounted or floor-standing
Additional Requirements
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The ESS shall ensure uninterrupted operation under unstable grid conditions and provide automatic transfer switching without interruption to the connected equipment (UPS function). A battery rack and BMS shall be included, where applicable. A Wi‑Fi module shall be supplied if required for commissioning.
The supply set shall include a Ukrainian-language user manual and a detailed electrical installation diagram.
The Supplier shall provide brief training to hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of conformity (UA certificate) for the hybrid inverter and battery or for the complete system
EMC safety certificates IEC / EN 61000-6-1 / 2 / 3 / 4 (If applicable)
Power converter safety IEC / EN 62109-1, IEC / EN 62109-2
Lithium-ion / lithium battery safety for stationary / energy storage systems IEC 62619
Safety testing for transport of lithium batteries / accumulators / ESS UN 38.3; IEC 61439‑1 / IEC 61439‑2
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 14. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 50 kW Battery Energy Storage System (ESS) (380 V) with 50 kWh Battery Storage for the Communal Non-Commercial Enterprise "City Hospital No. 4" of the Mykolaiv City Council (Branch: City Children's Hospital No. 2) 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, primarily in ICUs, including a hybrid inverter, an MPPT solar charge controller, battery charge/discharge monitoring, and an energy storage system.
Technical Specifications
Rated AC output power (inverter) Min 50 kW
Inverter type Hybrid
Output waveform Pure sine wave
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Battery type / voltage / minimum capacity LiFePO₄ / 48 V / min 50 kWh
Maximum battery charging time from DoD 20% Not more than 2 hours
System scalability Yes. Device must support parallel operation with the ability to combine at least 4 units to increase power or provide redundancy.
Control functions / modes Modes: “Grid + PV”, “Battery + PV/Grid”, automatic switching, power priority. Ability to limit battery charging currents.
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; MPPT overcurrent/overvoltage; battery overcharge and over-discharge protection via BMS.
Efficiency 93–97 %
Automatic transfer switching ≤ 10 ms
Interfaces RS485, CAN, USB, Wi-Fi / Ethernet. Mobile app for remote monitoring and configuration.
Operating temperature –10 °C to +55 °C
Humidity Up to 95 % non-condensing
Enclosure protection degree Not lower than IP21
Noise level Not more than 55 dB
Mounting type Wall-mounted or floor-standing
Additional Requirements
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The ESS shall ensure uninterrupted operation under unstable grid conditions and provide automatic transfer switching without interruption to the connected equipment (UPS function). A battery rack and BMS shall be included, where applicable. A Wi‑Fi module shall be supplied if required for commissioning.
The supply set shall include a Ukrainian-language user manual and a detailed electrical installation diagram.
The Supplier shall provide brief training to hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of conformity (UA certificate) for the hybrid inverter and battery or for the complete system
EMC safety certificates IEC / EN 61000-6-1 / 2 / 3 / 4 (If applicable)
Power converter safety IEC / EN 62109-1, IEC / EN 62109-2
Lithium-ion / lithium battery safety for stationary / energy storage systems IEC 62619
Safety testing for transport of lithium batteries / accumulators / ESS UN 38.3; IEC 61439‑1 / IEC 61439‑2
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 15. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 120 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the SOMATOM go.Up Computed Tomography System manufactured by Siemens GmbH (Nominal Power Capacity: 80 kVA) 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 120 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 120 kVA online UPS designed to provide backup power supply for the SOMATOM go.Up Computed Tomography System manufactured by Siemens GmbH (Nominal Power Capacity: 80 kVA) installed at the premises of the the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 16. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 120 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the X-Ray System 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 120 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 120 kVA online UPS designed to provide backup power supply for the X-Ray System installed at the premises of the the Communal Non-Commercial Enterprise "Pervomaisk Central City Multidisciplinary Hospital" of the Pervomaisk City Council. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 17. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 6 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for Ultrasonic Equipment 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 6 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 6 kVA online UPS designed to provide backup power supply for the for Ultrasonic Equipment. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 18. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 3 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for Intensive Care Unit (ICU) Equipment 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 3 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 3 kVA online UPS designed to provide backup power supply for the for the Intensive Care Unit (ICU) Equipment. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 19. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 6 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for Laboratory Equipment 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 6 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 6 kVA online UPS designed to provide backup power supply for the Laboratory Equipment. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 20. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 20 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the C-Arm Imaging System 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 20 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 20 kVA online UPS designed to provide backup power supply for the C-Arm Imaging System. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 21. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 30 kVA Online Uninterruptible Power Supply (UPS) System (220 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the Mammography System 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 30 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 30 kVA online UPS designed to provide backup power supply for the Mammography System. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 22. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 30 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the Fluorography System 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 30 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 30 kVA online UPS designed to provide backup power supply for the Fluorography System. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 23. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 6 kVA Online Uninterruptible Power Supply (UPS) System (220V) for the Communal Non-Commercial Enterprise "City Hospital No. 5" of the Mykolaiv City Council to Ensure Backup Power Supply for the Dental Computed Tomography (CT) System 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 6 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 6 kVA online UPS designed to provide backup power supply for the Dental Computed Tomography (CT) System. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Mykolaiv City, Ukraine
Annex 24. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 140 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Municipal Non-Commercial Enterprise "Chuhuiv Central Hospital named after M.I. Kononenko" to Ensure Backup Power Supply for the Helios DRF Digital X-Ray System (Nominal Capacity: 90 kW) 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 140 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 140 kVA online UPS designed to provide backup power supply for the Helios DRF Digital X-Ray System (Nominal Capacity: 90 kW) installed at the premises of the Communal Non-Commercial Enterprise "Regional Medical Center for Family Health" DOR. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Chuhuiv City, Ukraine
Annex 25. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 100 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Municipal Non-Commercial Enterprise "Chuhuiv Central Hospital named after M.I. Kononenko" to Ensure Backup Power Supply for the Polistat-M X-Ray System 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 100 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be compatible with and intended to provide backup power supply for the Polistat-M X-Ray System. The Bidder shall ensure full compatibility of the proposed solution with the existing electricity distribution grid .
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Chuhuiv, Ukraine
Annex 26. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 100 kVA Online Uninterruptible Power Supply (UPS) System (380 V) for the Municipal Non-Commercial Enterprise "Chuhuiv Central Hospital named after M.I. Kononenko" to Ensure Backup Power Supply for the Hitachi Supria 32 X-Ray System 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 100 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 380/400 V AC, 50 Hz
Input voltage 400 V
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be compatible with and intended to provide backup power supply for the Hitachi Supria X-Ray System. The Bidder shall ensure full compatibility of the proposed solution with the existing electricity distribution grid .
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Chuhuiv, Ukraine
Annex 27. Technical Proposal Information for bidders:
Supply, Installation and Commissioning of a 3 kVA Online Uninterruptible Power Supply (UPS) System (220V) for the Municipal Non-Commercial Enterprise "Chuhuiv Central Hospital named after M.I. Kononenko" to Ensure Reliable Backup Power Supply for Critical Medical Equipment 1. Please provide technical description of the offered product in column #2.
2. In case the parameters of the offered product differ from what is requested, please refer to it in the column #3.
3. Document should be completed, stamped (if applicable), and signed and submitted in PDF format.
ITB: 2026/EURO/UKR/0299
Please indicate your company name here
WHO Description Item and Specification Offered Compliance with Specification (Yes/No; if No, provide details)
Equipment set for providing uninterrupted power supply to medical equipment, including an online double-conversion UPS system, internal inverter, battery system, monitoring and protection functions, and all accessories required for installation and commissioning.
Technical Specifications
Rated AC output power 3 kVA
UPS type VFI Online Double Conversion
Output waveform Pure sine wave
Output Voltage THD ≤ 3% at non-linear load
Output voltage/frequency 220/230 V AC, 50 Hz
Input voltage 230 V AC
Guaranteed power supply time Minimum 20 minutes
Protections Short-circuit; overload; overheat; overvoltage and undervoltage; overcurrent/overvoltage; battery overcharge and over-discharge protection
Efficiency 93-97%
Automatic transfer switching Online operation (zero transfer time)
Interfaces RS485, CAN, USB, Wi‑Fi / Ethernet. Mobile app for remote monitoring and configuration
Mounting type Floor-standing
Additional Requirements
The UPS system shall be a 3 kVA online UPS designed to provide backup power supply for the for the Critical Medical Equipment. The Bidder shall ensure full compatibility of the proposed solution with the existing medical equipment.
The Supplier shall be responsible for the delivery, installation, testing, commissioning, and handover of the equipment at the designated hospital.
The electrical connection point shall be located at a distance of no more than 20 meters from the UPS.
Maintenance bypass shall be included.
The Supplier shall prepare and provide a detailed installation diagram.
The Supplier shall conduct brief training for hospital personnel on the proper operation and safe use of the equipment.
Quality Assurance
Warranty: Minimum 24-month warranty.
Availability of a service center or authorized service provider in Ukraine. Please provide details.
Remote technical support and system configuration assistance during the warranty period.
Declaration of Conformity (UA Certificate) for the UPS system and associated electrical equipment.
IEC 60601 – Medical electrical equipment: safety and essential performance requirements (if applicable).
IEC 62040 – Uninterruptible Power Systems (UPS): safety, performance and testing requirements.
IEC 60364-7-710 – Electrical installations in medical locations (if applicable).
IEC 60896 – Stationary lead-acid batteries (if applicable).
IEC 62619 – Safety requirements for secondary lithium batteries and battery systems used in industrial applications (if applicable).
Compliance with applicable Ukrainian electrical installation and construction standards.
Delivery Requirements
Delivery date The bidder shall complete delivery, installation, testing, and commissioning of the system within 4 weeks from contract signature.
Delivery place / terms (INCOTERMS 2020) DAP Chuhuiv City, Ukraine
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
ITB 2026_EURO_UKR_0299_Supply, Installation and Commissioning of Battery Energy Storage Systems and UPS Systems.pdf
Bidding document • 0.55 MB
Form E. Financial Proposal Template_2026_EURO_UKR_0299.xlsx
Bidding document • 0.01 MB
Annex 1. Technical Proposal Template - 50kW_50kWh_ESS_PervomaiskHospital.xlsx
Bidding document • 0.02 MB
Annex 2. Technical Proposal Template - 40kW_40kWh_ESS_PervomaiskHospital.xlsx
Bidding document • 0.02 MB
Annex 3. Technical Proposal Template - 30kW_30kWh_ESS_PervomaiskHospital.xlsx
Bidding document • 0.02 MB
Annex 4. Technical Proposal Template - 80kVA_UPS_PervomaiskHospital.xlsx
Bidding document • 0.02 MB
Annex 5. Technical Proposal Template - 120kVA_UPS_PervomaiskHospital.xlsx
Bidding document • 0.02 MB
Annex 6. Technical Proposal Template - 80kVA_UPS_MykolaivOblastHospital..xlsx
Bidding document • 0.02 MB
Annex 7. Technical Proposal Template - 1kVA_UPS_MykolaivOblastHospital.xlsx
Bidding document • 0.01 MB
Annex 8. Technical Proposal Template - 4kVA_UPS_MykolaivOblastHospital.xlsx
Bidding document • 0.01 MB
Annex 9. Technical Proposal Template - 12kVA_UPS_MykolaivOblastHospital.xlsx
Bidding document • 0.01 MB
Annex 10. Technical Proposal Template - 120kVA_UPS_MykolaivCityHospital3.xlsx
Bidding document • 0.02 MB
Annex 11. Technical Proposal Template - 80kVA_UPS_MykolaivCityHospital3.xlsx
Bidding document • 0.01 MB
Annex 12. Technical Proposal Template - 14kW_16kWh_ESS_MykolaivCityHospital3.xlsx
Bidding document • 0.01 MB
Annex 13. Technical Proposal Template - 50kW_50kWh_ESS_MykolaivOncologyCentre.xlsx
Bidding document • 0.02 MB
Annex 14. Technical Proposal Template - 50kW_50kWh_ESS_MykolaivOncologyCentre - Copy.xlsx
Bidding document • 0.02 MB
Annex 15. Technical Proposal Template - 120kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.02 MB
Annex 16. Technical Proposal Template - 120kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.02 MB
Annex 17. Technical Proposal Template - 6kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.01 MB
Annex 18. Technical Proposal Template - 3kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.01 MB
Annex 19. Technical Proposal Template - 6kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.01 MB
Annex 20. Technical Proposal Template - 20kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.01 MB
Annex 21. Technical Proposal Template - 30kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.01 MB
Annex 22. Technical Proposal Template - 30kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.01 MB
Annex 23. Technical Proposal Template - 6kVA_UPS_MykolaivCityHospital5.xlsx
Bidding document • 0.01 MB
Annex 24. Technical Proposal Template - 140kVA_UPS_ChuhuivCentralHospital.xlsx
Bidding document • 0.01 MB
Annex 25. Technical Proposal Template - 100kVA_UPS_ChuhuivCentralHospital.xlsx
Bidding document • 0.02 MB
Annex 26. Technical Proposal Template - 100kVA_UPS_ChuhuivCentralHospital.xlsx
Bidding document • 0.02 MB
Annex 27. Technical Proposal Template - 3kVA_UPS_ChuhuivCentralHospital.xlsx
Bidding document • 0.01 MB
Notice on UNGM.html
Notice page • 0.02 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .