| Sl No | Description | Qty | Unit | RHYTHM AUTOMATION CONTROL PVT.LTD L1 | Aaxis Nano Technologies Pvt. Ltd. L2 |
|---|---|---|---|---|---|
| 1.00 | Design, Develope, Integrate and Commission SCADA System along with various analysing equipment for Water Supply System for automation of following installations:-
(a) Clear Water Pump House having Pumps 6 Nos of 60 Hp Each of Make- Kirloskar (Vintage 2009 & 2015) Starter- Manual type Star Delta Starter, Capacity head 30 m, Discharge 340 Cum per hour and Sluice valves of size 150 mm (Make :- Zoloto)
(b) Common Header having 02 outgoing with ultrasonic flow meters installed having Sluice valves of size 500 mm (Make:- Kirloskar)
(c) High Head Pump House having Pumps 4 Nos of 120 Hp Each Make- Kirloskar (Vintage 2011 & 2018) Starter- Manual type Star Delta Starter, Capacity head 60 m, Discharge 340 Cum per hour and Sluice valves of size 150 mm (Make :- Zoloto)
(d) Common Header having 02 outgoing with ultrasonic flow meters installed having Sluice valves of size 500 mm (Make:- Bir)
(e) UG Sump (01 No) of capacity 08 Lakh Gallon
(f) UG Sump (03 Nos) of capacity 04 Lakh Gallon
(g) UG Sump (02 Nos) of capacity 02 Lakh Gallon
(h) UG Sump (02 Nos) of capacity 05 Lakh Gallon
(i) UG Sump (01 No) of capacity 08 Lakh Gallon
(j) Shivaji UG Sump(01 No) of capacity 08 Lakh Gallon having Sluice valves of size 100 mm (Make :- Zoloto)
(k) Shivaji UG Sump(02 Nos) of capacity 02 Lakh Gallon having Sluice valves of size 150 mm (Make :- Zoloto)
(l) Tank no 21 of capacity 0.5 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto)
(m) Tank no 26 of capacity 1 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto)
(n) Tank no 25 of capacity 1 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto)
(o) Tank no 24 of capacity 1 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm & 100mm (Make :- Zoloto) | 1 | Each Job | 72,65,000 ₹72,65,000 Lowest | 2,96,98,996 ₹2,96,98,996 |
| 1.01(p) Tank no 35 of capacity 0.25 Lakh Gallon and staging 21 m and having Sluice valves of size 100 mm (Make :- Zoloto) (q) Tank no 37 of capacity 0.75 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (r) Tank no 31 of capacity 0.75 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (s)Tank no 36 of capacity 0.25 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (t) Tank no 2 of capacity 2.5 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (u)Tank no 3 of capacity 2 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (v)Tank no 4 of capacity 1 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (x)Tank no 5 of capacity 2 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (w)Tank no 13 of capacity 1.5 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (y)Tank no 15 of capacity 2 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (z)Tank no 33 of capacity 0.75 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) | |||||
| 1.02Note:- 1. Layout plan as per scale attached. Also attached as part of the tender is the table having details of instalations to be covered under proposed SCADA and the details of items to be provided by tender should be filled in by the tenderer in this table while quoting. 2. The SCADA system should have provision of both manual and automatic operation of installations. 3. Scope shall include control and monitoring of Pump Operation at Clear water Pump House and High Head Pump House and Monitoring of water Quality at these pump Houses like pH, Residual Chlorine, energy consumption details, Flow Rate, Pressure etc, 3. Monitoring of Reservoir Levels at above mentioned OHT / Sumps, | |||||
| 1.03(a) Master Control station with personal computer with latest processor and monitor of suitable size: A LED VDU with high quality wall mounted suitable size LED screen, ultra-narrow and professional grade shall be provided. (b) Laser Printer | |||||
| 1.04(c)UPS with half an hour backup: The Uninterrupted Power Supply (UPS) must be capable of providing power to essential components, including central processing units, disks, communication processors, screens, servers, workstations, and SCADA Centre devices such as RTUs, PLCs, microprocessor controllers, and modems, for a minimum duration of 30 minutes. The contractor may explore the possibility of integrating or replacing UPS batteries with a centralized battery system connected to a solar power plant for buffering purposes. The UPS should be should be able to handle a 50% increase in load without requiring additional hardware. The UPS systems must be installed in the technical room of the SCADA Centre. Critical services, such as the UPS, generators, and security systems, should be monitored by the SCADA Centre. However, other non-essential devices, such as printers, extra-large screens, and projectors, do not need to be connected to the UPS system. | |||||
| 1.05(d) Server: The redundant server must be of high industrial quality, designed for continuous, reliable operation. It should be capable of handling all key SCADA functions, including data acquisition and storage. The minimum server specifications include: 1. CPU: Quad Core, 3.90 GHz 2. Cache: 10 MB 3. RAM: 16 GB 4. Storage: 4 x 1 TB SATA (Serial Advanced Technology Attachment) hard drive | |||||
| 1.06(e) Data Gateway (f) SCADA software which can be operated, programmed and modified by agencies other than developer. The SCADA software should have a modular structure, supporting client/server functionality and scalable from small to large applications. SCADA computers must have firewalls, ensuring cybersecurity for RTUs and microprocessor-based controllers. (g) PLC/ Microprocessor Controllers with indoor/ outdoor applications for water sensing display, pump operation with RTU/ without RTU or Microprocessor controller and microprocessor transmitter (h) Suitable communication system including payment of bills to telecom service provider. | |||||
| 1.07(i) Motorised butterfly valves (j) Pressure transmitters (k)Ultrasonic sensors (l) Flow meters and switches (m) Air Release solenoid valves Notes: (i)Design of Communication System shall be done by the bidder. Cloud based server/ data storage/ communication shall not be used and only local server based system shall be designed. (ii)The cost of each item shall also be attached to arrive at pricing in case of some addition/ reduction at site. (iii) Operating system, system software and programming shall not be intellectual property of any agency. (iv)The memory in the hard disk shall be suitable for six months data. The backup storage device/ devices shall be provided for archiving of data more than six months old. (v)In case of addition of installations, the system shall be capable of integrating the same. (vi) The responsibility of the agency is restricted to intimate mechanical and electrical failures such as failure of pumps, leakages etc. Such repairs shall be carried out by MES (vii) Operation and maintenance charges to be paid separately. | |||||
| 1.08Operate SCADA system during defect liability period for two years without manning (Contractor to provide month wise breakdown details of the same). (No manning or deployment of manpower required). Note: the payment of this item shall be made as per Sl No vii and viii of Para 4(k) of Particular Specifications on Srl page 117 of this CA | |||||
| 1.09Operation and comprehensive" maintenance of SCADA system including cost of upgradation, cost of spares for 8 years post defect liability period, operation including year payment of bills by telecom service provider Contractor to provide month-wise breakdown details of the same Note: the payment of this item shall be made as per Sl No ix of Para 4(k) of Particular Specifications on Srl page 117 of this CA | |||||
Tender Value
₹93.3 L
EMD Value
₹1.6 L
Closing Date
23 Aug 2025, 6:00 pmClosed
CE Bathinda Zone
HQ CE Bathinda Zone, Bathinda Mil Stn-151004
AUGMENTATION AND IMPROVEMENT OF WATER SUP SYS INCL SCADA FOR PUMPING AND WATER TESTING AT BATHINDA MIL STATION
2025_MES_721557_1
84465 CE BTZ/BTD/TOKEN- 06 OF 2024-25
Open Tender
Miscellaneous Works
Lump-sum
4015 days
GE (U) BATHINDA
As per NIT
8 documents required · 8 mandatory
₹1,000
GE (U) BATHINDA
₹1.6 L
Yes
12 Sept 2025
19 Jul 2025
25 Aug 2025
19 Jul 2025
23 Aug 2025
9 Aug 2025
19 Jul 2025 - 16 Aug 2025
Amount
Design, Develope, Integrate and Commission SCADA System along with various analysing equipment for Water Supply System for automation of following installations:- (a) Clear Water Pump House having Pumps 6 Nos of 60 Hp Each of Make- Kirloskar (Vintage 2009 & 2015) Starter- Manual type Star Delta Starter, Capacity head 30 m, Discharge 340 Cum per hour and Sluice valves of size 150 mm (Make :- Zoloto) (b) Common Header having 02 outgoing with ultrasonic flow meters installed having Sluice valves of size 500 mm (Make:- Kirloskar) (c) High Head Pump House having Pumps 4 Nos of 120 Hp Each Make- Kirloskar (Vintage 2011 & 2018) Starter- Manual type Star Delta Starter, Capacity head 60 m, Discharge 340 Cum per hour and Sluice valves of size 150 mm (Make :- Zoloto) (d) Common Header having 02 outgoing with ultrasonic flow meters installed having Sluice valves of size 500 mm (Make:- Bir) (e) UG Sump (01 No) of capacity 08 Lakh Gallon (f) UG Sump (03 Nos) of capacity 04 Lakh Gallon (g) UG Sump (02 Nos) of capacity 02 Lakh Gallon (h) UG Sump (02 Nos) of capacity 05 Lakh Gallon (i) UG Sump (01 No) of capacity 08 Lakh Gallon (j) Shivaji UG Sump(01 No) of capacity 08 Lakh Gallon having Sluice valves of size 100 mm (Make :- Zoloto) (k) Shivaji UG Sump(02 Nos) of capacity 02 Lakh Gallon having Sluice valves of size 150 mm (Make :- Zoloto) (l) Tank no 21 of capacity 0.5 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (m) Tank no 26 of capacity 1 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (n) Tank no 25 of capacity 1 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (o) Tank no 24 of capacity 1 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm & 100mm (Make :- Zoloto)
(p) Tank no 35 of capacity 0.25 Lakh Gallon and staging 21 m and having Sluice valves of size 100 mm (Make :- Zoloto) (q) Tank no 37 of capacity 0.75 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (r) Tank no 31 of capacity 0.75 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (s)Tank no 36 of capacity 0.25 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto) (t) Tank no 2 of capacity 2.5 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (u)Tank no 3 of capacity 2 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (v)Tank no 4 of capacity 1 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (x)Tank no 5 of capacity 2 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (w)Tank no 13 of capacity 1.5 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (y)Tank no 15 of capacity 2 Lakh Gallon and staging 21.15 m and having Sluice valves of size 200 mm (Make :- Zoloto) (z)Tank no 33 of capacity 0.75 Lakh Gallon and staging 21 m and having Sluice valves of size 150 mm (Make :- Zoloto)
Note:- 1. Layout plan as per scale attached. Also attached as part of the tender is the table having details of instalations to be covered under proposed SCADA and the details of items to be provided by tender should be filled in by the tenderer in this table while quoting. 2. The SCADA system should have provision of both manual and automatic operation of installations. 3. Scope shall include control and monitoring of Pump Operation at Clear water Pump House and High Head Pump House and Monitoring of water Quality at these pump Houses like pH, Residual Chlorine, energy consumption details, Flow Rate, Pressure etc, 3. Monitoring of Reservoir Levels at above mentioned OHT / Sumps,
(a) Master Control station with personal computer with latest processor and monitor of suitable size: A LED VDU with high quality wall mounted suitable size LED screen, ultra-narrow and professional grade shall be provided. (b) Laser Printer
(c)UPS with half an hour backup: The Uninterrupted Power Supply (UPS) must be capable of providing power to essential components, including central processing units, disks, communication processors, screens, servers, workstations, and SCADA Centre devices such as RTUs, PLCs, microprocessor controllers, and modems, for a minimum duration of 30 minutes. The contractor may explore the possibility of integrating or replacing UPS batteries with a centralized battery system connected to a solar power plant for buffering purposes. The UPS should be should be able to handle a 50% increase in load without requiring additional hardware. The UPS systems must be installed in the technical room of the SCADA Centre. Critical services, such as the UPS, generators, and security systems, should be monitored by the SCADA Centre. However, other non-essential devices, such as printers, extra-large screens, and projectors, do not need to be connected to the UPS system.
(d) Server: The redundant server must be of high industrial quality, designed for continuous, reliable operation. It should be capable of handling all key SCADA functions, including data acquisition and storage. The minimum server specifications include: 1. CPU: Quad Core, 3.90 GHz 2. Cache: 10 MB 3. RAM: 16 GB 4. Storage: 4 x 1 TB SATA (Serial Advanced Technology Attachment) hard drive
(e) Data Gateway (f) SCADA software which can be operated, programmed and modified by agencies other than developer. The SCADA software should have a modular structure, supporting client/server functionality and scalable from small to large applications. SCADA computers must have firewalls, ensuring cybersecurity for RTUs and microprocessor-based controllers. (g) PLC/ Microprocessor Controllers with indoor/ outdoor applications for water sensing display, pump operation with RTU/ without RTU or Microprocessor controller and microprocessor transmitter (h) Suitable communication system including payment of bills to telecom service provider.
(i) Motorised butterfly valves (j) Pressure transmitters (k)Ultrasonic sensors (l) Flow meters and switches (m) Air Release solenoid valves Notes: (i)Design of Communication System shall be done by the bidder. Cloud based server/ data storage/ communication shall not be used and only local server based system shall be designed. (ii)The cost of each item shall also be attached to arrive at pricing in case of some addition/ reduction at site. (iii) Operating system, system software and programming shall not be intellectual property of any agency. (iv)The memory in the hard disk shall be suitable for six months data. The backup storage device/ devices shall be provided for archiving of data more than six months old. (v)In case of addition of installations, the system shall be capable of integrating the same. (vi) The responsibility of the agency is restricted to intimate mechanical and electrical failures such as failure of pumps, leakages etc. Such repairs shall be carried out by MES (vii) Operation and maintenance charges to be paid separately.
Operate SCADA system during defect liability period for two years without manning (Contractor to provide month wise breakdown details of the same). (No manning or deployment of manpower required). Note: the payment of this item shall be made as per Sl No vii and viii of Para 4(k) of Particular Specifications on Srl page 117 of this CA
Operation and comprehensive" maintenance of SCADA system including cost of upgradation, cost of spares for 8 years post defect liability period, operation including year payment of bills by telecom service provider Contractor to provide month-wise breakdown details of the same Note: the payment of this item shall be made as per Sl No ix of Para 4(k) of Particular Specifications on Srl page 117 of this CA
Aaxis Nano Technologies Pvt. Ltd. (BID ID -3402006)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .