EX ENGINEER JAL SHAKTI MECH DIV SGR
OFFICE OF THE EX ENGINEER JAL SHAKTI MECH DIV SGR
Improvement in Protection System of 2X3.15 MVA Power Transformers and Electrical HT works at WSS Tangnar Stage-2nd (Annexure D)
2026_PHE_329971_2
JSMDS/e-NIT-33 of 10/2026
Open Tender
Electrical and Maintenance Works
Percentage
20 days
Tangnar
AS Per NIT
2 documents required · 2 mandatory
₹500
Ex Engineer Jal Shakti PHE Mech. Div. Sgr
₹9,600
26 Nov 2026
31 Oct 2026
26 Nov 2026
31 Oct 2026
25 Nov 2026
31 Oct 2026
180 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | P/F of 33 kV Lightening Arrestors (33 kV, 10kA, Station class, ZnO, Polymer) gap less. (1Set = 03 No's) | 1 | Set | 31,007.65 | ₹31,007.65 |
| 2 | P/F of new 33 kV Current Transformers oil cooled (33 kV, 1Φ, 2 Ratio 3 Core, Outdoor Type ) (1 No. per Φ) 50-100/5-5-5A with Accuracy Class: 0.5 as per site requirement.
The job includes disconnecting & replacing of the old CT metering unit fitted on the pole structure or as per site requirement with the new one and then shifting the same to some safe place within the Tangnar Station. The CT Metering Unit is to be provided with the T-Oil filled up to the required level. All the tools and tackles like CI Tester etc, skilled & unskilled labour etc involved for Installation & testing of the CT Metering Unit on the pole Structure and with existing installed electrical circuit complete, shall be arranged by the firm for the complete job. | 3 | Jobs | 60,325.03 | ₹1,80,975.09 |
| 3 | P/F of new 33 KV/110V, Out Door Type, Single Phase, Oil Cooled Potential Transformer as per IS : 3156 with the following details as per site requirement:
Equipment = 33 KV, Out Door, Single Phase, Oil Cooled Potential Transformer
Reference Standard = IS : 3156
Type = Dead tank
Rated voltage = 33 KV
Highest voltage = 36 KV
Frequency = 50 Hz.
Basic Insulation Level Primary = 36 KV / 70 KV / 170 KV(p) & Secondary = 3 KV for 1 minute
Class of insulation = Class A
Creepage distance = 900 mm (minimum)
Ratio = 33000/√3 : 110/√3 – 110/√3 Volt
Class of accuracy = Core - I : 0.5, Core - II : 3P
Burden = Core - I : 50 VA, Core - II : 50 VA
Voltage factor = 1.2 Continuous, 1.5 times for 30 Sec.
Core identification = Core - I : Metering, Core - II : Protection
Place of installation = Out Door, Structure mounted
The job includes disconnecting & replacing of the old PT metering unit fitted on the pole structure or as per site requirement with the new one and then shifting the same to some safe place within the Tangnar Station. The PT Metering Unit is to be provided with the T-Oil filled up to the required level. All the tools and tackles, skilled & unskilled labour etc involved for Installation & testing of the PT Metering Unit on the pole Structure and with existing installed electrical circuit complete, shall be arranged by the firm for the complete job. | 3 | Jobs | 51,120.64 | ₹1,53,361.92 |
| 4 | P/F of new Resin Cast 11 KV Current Transformer (11 kV, 1Φ, Multi ratio - Multi core, Indoor Type) 100-200-500/1A (3-Core) with following details asper site requirement:
Primary Current : 100-200-500
Secondary Current: 1 A
No. of cores : 3-Cores
Rated Burden: 10 VA
Accuracy Class: 0.5
Frequency : 50 Hz
The job includes disconnecting & replacing of the old CT metering unit fitted in the HT Control Panel or as per site requirement with the new one. All the tools and tackles like CI Tester etc, skilled & unskilled labour etc involved for Installation & testing of the CT Metering Unit with existing installed panel, shall be arranged by the firm for the complete job. | 3 | Jobs | 38,216.36 | ₹1,14,649.08 |
stage.html
html • 0.01 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.50 MB
BOQ_1118727.xls
BOQ • 0.38 MB
CORRIGENDUM-2-Date-Extention-NIT-33.pdf
PDF • 0.15 MB
CORRIGENDUM-Date-Extention-NIT-33.pdf
PDF • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .