Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance 2ND FLOOR SHOP NO 303 MARUTI PLAZA RONCHI BANGAR TOWNSHIP MATHURA | MATHURA | UTTAR PRADESH | 281001 | Admitted-Finance |
| 4 | Admitted-Finance 00 JALESAR MAHAVIR GANJ 00 VILLAGE TOWN JALESAR CITY ETAH ETAH UTTAR PRADESH 207302 INDIA | ETAH | UTTAR PRADESH | 207302 | Admitted-Finance |
Tender Value
₹19.9 L
EMD Value
₹20,000
Closing Date
8 Jun 2023, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC Mathura
132 KV S/S Aurangabad Mathura
Works for Increasing Capacity from 2X40 MVA to 3X40 MVA with construction of transformer bay and other associated works at 220 KV Sub-Station Chhata Under ETD Mathura
2023_UPTCL_806666_1
ET-05/ETC(M)/23-24
Open Tender
Electrical Works
Lump-sum
180 days
Under ETC Mathura
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ATT ETC Mathura
₹20,000
15 Jun 2023
27 May 2023
9 Jun 2023
27 May 2023
8 Jun 2023
27 May 2023
Amount
Construction of 40 MVA Transformer bay ,Erection of 1 Nos capacitor bank (2x5 MVAr), 33KV Cap Bank Bay
Erection of main and auxiliary structure consisting of columns, beams, peaks, masts etc. and auxiliary structure required for installation of Jack busbar isolators, P.I., CTs., L.As. and all other equipments. The job consists of shifting of all material i.e. conductor, fittings, structure parts, nuts, bolts, washer etc. from store to site of erection, erection of structure as per relevant drawing and practices using flat and spring washer with each bolt. Matching of holes, cutting, matching of members if required shall also be done by the contractor without any extra cost to complete the work satisfactorily. All material to be erected shall be supplied by UPPTCL free of cost but all men, material and T&P required for satisfactorily completion of work shall be arranged by the contractor at his own cost.
Dismantling of main and auxiliary structure consisting of columns, beams, peaks, masts etc. and auxiliary structure required for installation of Jack busbar isolators, P.I., CTs., L.As. and all other equipments. The job consists of shifting of all material i.e. conductor, fittings, structure parts, nuts, bolts, washer etc. as per practices. All material to be dismantled shall be shifted to designated place. all men, material and T&P required for satisfactorily completion of work shall be arranged by the contractor at his own cost.
Dismantling of jumpers of 33KV C.B., C.T., ,Isolator, LA by the single/Twin Moose/Zebra/Panther conductor with shifting of material from site to store .
Dismantlingof following equipments as per instruction manual of various equipments and technical specifications including shifting of material/equipments from site to store including all other associated work to complete the job satisfactorily.
33 KV VCB
33 KV BI/LI
Various Dismantling Work
Destringing of 33 KV Jack bus(Approx. 18 mtrs)
Various shifting Equipment 245KV CB 02 No, 33KV VCB 01 No and other Matterials for space of construction place of capacitor bank.
Dismantling of 33 KV complete capacitor bank series reactor 04 Nos., NCT-02 Nos, capacitor bank cells, structure With Pale Fancing & Opening of copper bonds. . Shifting dismantled structure and equipment and other material from site to store/designated place within S/S boundary and other associated work to complete the job satisfactorily as per direction of supervising engineer.
Erection of following equipments as per instruction manual of various equipments and technical specifications including shifting of material/equipments from store to erection site including all other associated work to complete the job satisfactorily.
132 KV CT Junction Box
T/F C&R Panel
33 KV VCB
33 KV BI & LI
33 KV CT/NCT
33KV CT Junction Box
Series Reactor for capacitor bank
Stringing of various main, Transfer & T/F jack bus of 132 KV/33 KV with different type conductor and different length of span mention below including fitting of tension clamp hoisting of insulators cutting of conductor and also shifting of all material form store to work site and all other associated works required for completion of job satisfactorily as per technical specification.
132 KV Transfer Bus with 3x Zebra (Approx 12 Mtr section)
132 KV Transformer Jack bus 3x Zebra (Approx 15 Mtr section)
33 KV Capacitor Bank Jack bus (Approx 18 Mtrs section)
Providing inter connection diagram and cable schedule as per drawing to complete above job including C.B., C.T., Isolator, Panel and Transformer etc.
Laying of following sizes of control cable in the cable trench from control relay panel to various equipments/marshalling boxes/junction box etc. in switchyard as per cable schedule, their saddling at every 750mm distance with M.S. saddles of size 25x3mm size including carriage of cable drums from store to laying site and shifting back the remaining material to store and all other associated work to complete the job satisfactorily as per technical specification.
10x2.5 Sq mm
6x2.5 Sq. mm.
4x2.5 Sq. mm.
2x2.5 Sq. mm.
Termination of following sizes of cable as laid above as per cable schedule including making necessary holes in glands plates or box wherever required. Supply and fixing of cable glands of appropriate size, supply and providing ferrules and Nos. for each core. (The rates of termination of control cable include the all cores of cable at one end with lug)
10x2.5 Sq mm
6x2.5 Sq. mm.
4x2.5 Sq. mm.
2x2.5 Sq. mm.
Cutting, straightening bending & laying 800mm below inside ground and above ground of following size M.S. flat for earthing of main and auxiliary structure, equipment structure etc. including welding with main earthmat and with object to be earthed excavation of trenches, its back filling, painting and all other associated work as required to complete the work satisfactorily excluding the cost of M.S. flat.
To make earthing for L.A. with 06 Nos. Electrode of 03 meter long M.S. round including cutting, welding and making electrode and making a rectangle with 75x10mm M.S. flat inside earth below 0.8mtr. deep including excavation and refilling of soil with T&P and labour etc for completion satisfactorily.
Erection of capacitor bank unit (1X5 MVAR) by erecting of its structure with the help of post insulators, Nut and bolts and then fixing of cells properly and jumpering between each cells and all other associated works required for completion of job satisfactorily as per direction of supervising engineer.
Preparation of Inter connection diagram and cable schedule as per drawing to complete the job of cable termination of capacitor bank completely
Providing and fixing of retro reflective sign board of size 3ftx2ft made out of 2mm thick aluminum sheet, face to fully covered with 3M DG cube retro reflective sheet of green colour. The letters and symbols shall be computer cut and in white colour. Board is to be supplied along with the back support from of size 35x35x5mm & two legs for grouting. Backside of aluminum sheet shall be painted with stove enamel black paint for new 40 MVA, 132/33KV Transformer-I. Language for writing will be provided by the department (UPPTCL).
Providing and fixing of digitally printed glow sign board of Single Line Diagram of 220 KV S/S Chata of size 6'x4' made of minimum 2 mm thick milky acrylic sheet and frame of 28 SWG G.I. Sheet having depth 150mm with 05 Nos. 20W, 230V, day light LED batten tube light fitted inside for glowing the board. Complete wiring should be of 0.75 mm² ISI mark copper wire with 3 mtr connecting cable of same standard including 3 pin ISI mark plug point.
Loading, Carriage, Unloading, Erection and Comissioning of 40 MVA Transformer
Erection of HV/IV bushing for SFRA test afterdismentling of 40 MVA T/F turret of HV/N Testi with torsury and neutrel bushings along with its proper packing at 132 KV S/S Jattari in wooden box.
Shifting of main tank of 40 MVA,132/33 KV transformer from store to loading place to the plinth distance about 30 meter including turning of tank, if required , including all T&P and all other works required to complete the job satisfactorily.
Loading of above 40 MVA 132/33 KV T/F on trailor, Jacking the transformer tank for placing of wooden planks under T/F tank & similarly lifting the transformer tank by jacking & placing continious wooden planks until platform comes at the hight of trailor bed, than shifting the transformer tanks from wooden. platform to trailor bed proper tighting of transformer monted on T/F. With the help of wire rope & heavy turn buckle for the safe transporation
Safe carriage of 40 MVA T/F main tank with all accessories with T/F oil by private/Truck from 132Kv S/S Jattari Aligarh to 220KV S/S Chhata, Mathura Distance up to 100 KM insurance shall be got done by the contractor as per directionn include impect recarder of supervision Engineer Which shall be reimburshed on actual.
Unloading of 40 MVA T/F from Tailor, Jacking the Transformer tank of placing the rail under the tank & shifting it to wooden platform, removal the rail under the T/F tank on Wooden sleeper. Lowring the tank towards ground slowly & removing the Wooden Sleepars under the tank at 220 Kv S/S Chhata.All T&P and necessary items required for provided by contractor
Shifting of 40 MVA T/F with accessories from unloading point to plinth with the help of rail pulling device sleepars etc. up to distance of approx upto 20 mtr. Including turning if required at 220KV S/S Chhata Mathura.
Additional shifting of approx. 5 Mtrs/Job
Complete erection of 40 MVA capacity transformer by erection of radiators conservator tanks, all bushing, turrets, connecting oil pipe lines, cooling fans, motor drive mechanism of tap changer, RTCC panel, etc to complete the job satisfactory.
Attending Leakage of EMCO Make 132/33 KV 40 MVA T/F by replacement of old and Leakage gasket of following
H.V. Side bushing (Top & Bottem Portion) of R.Y.B. Phase
L.V./Neutral bushing (Top & Bottem Portion)
Explosion / PRV of the T/F Gasket
Radiator Pipe flange gasket
Radiator Valve gasket
Radiator air plug gasket
Conservator tank gasket
Equaliser/Header Joint gasket
OLTC Top botton gasket
Conservator drain valve gasket
Bucholz relay gasket
Sampling valve gasket
Drain valve gasket
Gasket for Magnetic oil level gauge
Erection of 40 MVA T/F, 132/33 KV 'RTCC' Panel
Filling of Main Tank & Conservator centrifuged transformer oil in 40 MVA T/F after complete errection of transformer as per direction of supervising engineer.
Centrifuging of transformer oil in transformer main tank for 72 hours by 10 KL/Hour capacity centrifuging machine, to be arranged by the contractor alongwith operator and taking the B.D.V values of the oil periodically till the required value is achieved as per direction of supervising engineer.
Earthing of 40 MVA T/F HV and LV Neutrals, Body, Marshaling box, Drive mechanism etc. with 75X10/50X6 MS flat (To be provided by department) including, bending, cutting & welding etc.
Delta earthing for 40 MVA T/F after fabrication of delta set with 3 nos. 40mm/36mm dia size 3 mtrs. long electrodes their placing inside the ground at distance of 3 Mtr. to each other in delta pettern and connecting all the three electrodes with 75x10mm MS flat 700mm deep and connecting the delta with T/F HV and LV neutral seprately with the help of 75x10 mm MS flat. (M.S flat and M.S rod will be arranged by the Department).
Extension of Hydrant of Mulsifire system with Supply & erection of high velocity water spraying system on 40 MVA, 132/33.KV Transformer including all materials and other associated works i.e. fabrication of rings of air and water of M.S. Pipe with follwing size pipe along with its elbow. tee sockets. flnngs and bends etc. including cutting, welding for fixing of water sprankles.
80mm dia
Supply erection of Pylon support and laying of overhead M.S. pipe line as pr spech (B Grade). Comlete with elbow,Tee, sockets, flanges ets, with anti-corrosive treatment with all material labour etc.
80 mm Dia
Fabricationand ereciton of M.S. angle of size 50x50x6 mm on Pylon supports for holding the air& water ring including cutting. Welding & clamping with 'U' bolt & including all associated works with all required material, labour & T&P.
Providing, fixing, testing and commissioning of follwing size dia gate valve with accessories
80mm dia
Providing, Fixing, testing and commissioning of 80mm dia fire hydrant valve with accessories made of brass (seat and spindle) and body cast iron for 80mm dia MS pipe.
Providing and fixing fire hydrant box and front door glass with proper locking arrangement.
Making of C.C. floor with 1:2:4 ratio of size 2.0x1.0x0.5(LxBxH)mtr. For fire hydrant.
Painting of complete 80mm MS hydrent pipe with 2 coat of synthetic enameled paint red colour for MS Pipe after one coat of red oxide.
Casting of plinth above ground lavel 300mm and blow ground lavel 300mm size 250x250mm² with cement coarse sand and concreteas as per instructions of supervising engineer for supporting 80mm main water line, 25mm air line & 80mm hydrant pipe.
Providing and fixing new generation energy saving and enviournemnt friendly long life versatile pressure die cast aluminium out door high beam flood light with high power 120W LEDs as light source and exclusively design poly carbonate cover satisfying IP65 standard alongwith electronic driver and complete fitting including GI pipe, clamp for round pole or GI structure, suitable for 220 V AC supply make CGL/Havells/Philips and Providing and fixing of junction box of 16 SWG MS sheet duly painted having size 150x150x200mm for above light on bottom of main structure or pole with the help of clamps junction box contain 01 No., 6Amp single pole MCB (L&T/Havells/Schneider make), 01 No. link and cable gland etc. as per specification and Laying, dressing and termination of contorl cable for the light with the help of clamps vertically on the gentry and all other associated to complete the work.
Supply and Fixing of High Mast and S/S Light Various Matterials
Providing and Fixing of 400 W HPSV Ballest for standard make
Providing and Fixing of 400 W HPSV lamp for standard make
Providing and Fixing of 400 W Ignitor for standard make
Providing and Fixing of 400 W 42 MFD Capacitor for standard make
Providing and Fixing of 250 W HPSV Ballest for standard make
Providing and Fixing of 250 W HPSV lamp for standard make
Supply of Portable type fire Extinguisher
Portable AFF Mechanical foam type fire Extinguisher complete with initial charge hose pipe and all other accessories and fitting as per IS 1024 Trolly/Wheel mounted 45/50 Litre Capacity.
Supply of following fire extinghisher carbon di oxide as per IS Specn. No 2878/1986
Supply of sand buckets as per technical spectification
Supply of stand for Sand buckets hanging suitable for 6 buckets
Supply of hardware Accessories
Supply of Bolted type bus bar tension fitting suitable for Zebra conductor made of LM-6 alloy Complete with ball eye socket and ‘D’ shackle single phase type turn buckle in all respect.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Zebra to Zebra conductor.
Supply of 145 KV Post Insulator clamp made of LM-6 alloy along with Nut, Bolt & washer suitable for Twin Zebra conductor.
Supply of 33 KV Isolator clamp for Twin Zebra conductor with nut, bolt & washer.
Supply of 33 KV Isolator clamp for Twin Panther conductor with nut, bolt & washer.
Supply of 33 KV CT Clamp made of LM-6 alloy alongwith nut, bolts & washer suitable for2000/1 Amp. CT for Twin Zebra conductor.
Supply of 33 KV CT Clamp made of LM-6 alloy alongwith nut, bolts & washer suitable for2000/1 Amp. CT for Twin Panther conductor.
Supply of 33 KV V.C.B. clamp for Twin Zebra conductor with nut, bolt & washer.
Supply of 33 KV V.C.B. clamp for Twin Panther conductor with nut, bolt & washer.
Supply of tinned copper bond size 15x550mm long made of 12mm multi stranded rope type 450mm long should be joined together and cramped with copper lug (20mm hole) on both ends as per sample
Supply of Earthing/Discharge rod of first class insulation for system voltage upto 400 KV having total height as 7200mm (24’) one set consisting following items. (a) Earthing pole 6.5Mtr. long in four pieces made of epoxy bonded glass fiber. (b) Earthing cable 12mtr. long with transparent PVC insulated 12 mm2 dia flexiblity copper wire fitted with line end earthing clamp of all alloy suitable for 4” IPS tube Moose/Zebra conductor. (c) Canvas carry bag for above.
Transformer oil sample collection testing of transformer oil at CPRI/ERDA Lab Sonipath & furnishing test report for a- Dissolve Gas Analysis test -01 Nos b- Breakdown Voltage Test - 01 Nos c- Water Content Test- 01 No d- SFRA Test - 02 No
M/s S.S. Refregeration
P&H Engineering
Hi-tech power transmission
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .