Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.7 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹3.2 L+₹46,301 (17.2%)Accepted-AOC | L2 | Accepted-AOC L1 Bidder | |
| 3 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹4.1 L
EMD Value
₹5,000
Closing Date
14 Nov 2022, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC I, Lucknow
Pareshan Bhawan, Vibhuti Khand, Luciknow
Work of installation and commissioning of new 63 MVA transformer in place of damage transformer at 132KV Substation GIS Mehtab Bagh, Lucknow under ETD I, Lucknow
2022_UPTCL_742955_1
Very short term e-tender 47/2022-23
Open Tender
Electrical Works
Piece-work
10 days
Lucknow
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
A/c No 2408002190005438, IFS PUNB0691100, PNB, Lko
₹5,000
13 Jan 2023
29 Oct 2022
15 Nov 2022
29 Oct 2022
14 Nov 2022
29 Oct 2022
Amount
Following works are to be carried out at 132kv GIS sub station Mehtabbagh Lucknow for dismantling of damage 63 MVA T/F & the installation of new 63 MVA 132/33 KV Transformer along with associated works including all cost of men, miscellaneous consumables, T&P, Centrifuging machine, crane etc to complete the job satisfactory
A) Dismantlling of 63 MVA T/f -II TAL Make , RTCC Panel and shifting etc.
1) Dismantling of 33kv L.A along with ALP structure and Proper Stacking after opening of jumpers and disconnection of earthing (1 Job for each set of L.A and ALP Structure)
2) Opening of Connection of Control cable and Power cable of existing Defective 63 MVA T/F at Both end and C&R Panel Cooling Fans , Marshalling Box etc.
3) Dismantelling and Shifting of 63 MVA T/f -II RTCC Panel From ACDB Room including Necessary Work
4) Complete safe Dismantelling of the accessories of existing defective 132/33 KV 63 MVA T/F -II Including opening of Jumper , Removal of earthing .Draining out of Transformer OIL up required Level in 209 LTR. Capacity Oil Drums. Removal of Conservator tank , Pipe Line, Bushing cooling Fan , Marshelling Box, Radiator after draining of radiator Oil etc. and Fixing of Blanking Plate on the radiator, Pipe Line, Conservator tank.Turret etc. with Proper staking.Blanking Plate Including Nut & Bolt and Packing of Bushing in wooden Box Providing By Contractor.
5) Shifting of Main Tank of of existing defective TAL Make 132/33KV 63 MVA Transformer to Storage Place from the Plinth Up 20 Mtr Distance Including of Tank Turning
6) Additional Shifting of Transformer Tank up to 35 Mtr ( 1 Job for every 5 Mtr)
B) Erection of Transformer, RTCC panel including shifting etc. As detailed below:
1) Dragging and shifting of Main tank of 63 MVA T/F from unloading point to pinth (Distance 65 metres). The work includes turning of main tank if required
i) Up to 20 metres distance
ii) Additional shifting of Transformer tank up to 60 mtr distance (1 job for every 5 metres)
2) Complete erection of 63 MVA Transformer including radiators, conservator tank, bushings with their turrets, connecting pipelines, cooling fans and pumps, motor drive mechanism with tap changer, marshalling box , OTI, WTI, capillary pipes, etc
3) Safe carriage of 20KL T/F oil tank from 220KV sub station Kursi road , Lucknow or any other sub station in Lucknow to 132 kV sub station Mehta bagh , Lucklnow including loading & unloading ( approx. distance 30 KM)
4) Filling of fresh T/F oil from T/F oil drums (approx 20KL) in suitable capacity oil tank and then centrifuging of T/F oil by Ultra high vacuum Oil Filtration Plant after connecting pipes with storage tanker to oil filtration plant including taking BDV values of oil nad megger values of the T/F periodically till the required value is achieved . Centrifuging machine must be equipped with megger , PPM & BDV measuring instruments with all cost of centrifuging machine, CFM operator, lubricants etc
5) Centrifuging/ dehydration oif the complete T/F oil of new 63 MVA T/F by Ultra high Vacuum oil filtration plant after connecting the centrifuging pipes with T/F tank to oil filtration plant including taking the BDV values of oil and megger values of the T/F periodically till the required value is achieved including filling and topping up of the above prepared T/F oil under vacuum in main tank , radiator, conservator tank etc and attending the oil leakages if any with all cost of centrifuging machine, CFM operator , lubricants etc
6) Earthing of Main tank of the Transformer, RTCC Panel, Marshalling Box, drive mechanism of the cooling fans, T/F neutral etc of 63 MVA Transformer with the help of 50*6 mm/ 75*10 mm size MS flat ( to be provided by department), its joining with already laid earth mat and necessary modification in existing support for earthing of Neutral bushing and then painting of earthing strips as per technical specification/ standard practices.
7) Making of additional Delta of 63 MVA T/F HV/LV neutral bushing with fabrication of 3 Nos, 3 meter long electrodes of 36mm/40mm dia MS round bar, piercing it inside ground at equal distance of 1 meter up to depth of 700mm, by digging of earth and connecting all the 3 No electrodes with 75mm*10mm size MS flats and connecting with existing earth mat and taking out riser by due cutting, bending, welding, etc as per techincal specification .( MS bar will be provided by department). Above work also includes painting of earthing strips with one coat of red oxide primer and two coat of bus green synthetic enamelled paint. 1 job for each Delta earthing.
8) Interconnection and termination of the already laid control cable between control and relay panel & errected equipment of 63 MVA T/F ( Both HV & LV Side) the work also include making necessary Holes in gland Plate of Boxes where ever required cable gland of appropriate size , providing of ferrules for each core of the cable & its termination with crimping type copper lugs.
9) Erection of 63 MVA Transformer RTCC panel including grouting, earthing after shifting from storage place to relay room as per instruction of site engineer.
C) Jumpering, stringing etc of various equipment, Bus sections & 63 MVA T/F etc.
1) Jumpering of various equipment with AACC trantulla conductor in T/F HV bay between 132KV HV side bushing of T/F and LAs by due cutting and bending of conductor and fixing & tighting etc of the conductor/ clamps/ connectors/ spacers etc(01 job for all 3 phases)
2) Jumpering of various equipment with AAC trantulla conductor in T/F LV bay between 33KV bushing of T/F to LV side LAs including isolators, CTs,LAs by due cutting and bending of conductor and fixing & tighting of the conductor/ clamps/ connectors/ spacers etc(01 job for all 3 phases)
D) Erection of old 03 No. ALP structure and fitting with LAs and Counter Meter and earthing of ALP Structure and LAs
E) Proper Packing of HV/LV & Neutral Bushing of Dismentaled 63 MVA Transformer including Proper Wrapping with Polythene Sheet in Wooden Craret of New Bushing Of 63 MVA Transformer
HARE KRISHNA ENERGY PROJECTS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .