Air conditioning work comprising HVAC ducting and VRV etc.
NSL/CEO/NIA/NIT/2024/681
NSL/CEO/NIA/NIT/2024/681
Open Tender-Domestic
Miscellaneous
New Delhi, Delhi
₹2,950
₹47,143
28 Jul 2026
11 Jul 2024
22 Jul 2024
22 Jul 2024
8 Aug 2024
DSR Amount Non DSR Amount
A) AIR COOLED VRV UNITS
1 OUTDOOR UNITS
Supply, installation, testing and commissioning of aircooled variable refrigerant volume modular type
airconditioning system with R410a refrigerant suitable for 415±10%, 50 cycles.The unit shall consist of indoor
and out door units with individual controller as per detail given in specifications and having following
Modular type outdoor units equipped with highly efficient 100% inverter type scroll compressors with special
1.1 precoated heat exchanger, low noise condenser fan housed in compact housing duly powder coated and
Outdoor unit having COP at 100% load to be minimum 3.6. of following capacitites:
1.2 Cost of R 410 A Gas should be inclusive
Cost of any civil work to install the unit including footing, excavation, filling, frames etc should be inclusive
Supply, installation, testing and commissioning of factory built Floor Mounted Air handling units in Double
Skinned air-handling unit with Mixing Chamber alongwith F/A damper with 43+2 mm thick panels Horizontal
type fabricated out of extruded aluminium (1.6 mm thickness min.)section with Thermal break profile at
corners and at joints for double skin air handling units alongwith internal covings with 0.63 mm thick pre-
plasticide galvanised sheet outside & 0.63mm thick polished galvanised Steel sheet inside with 120 GSM zinc
coating and polyurethene foam(PUF) insulation having density of 42 kg/m3,complete with DIDW forward
curved belt driven / Plug type,Refrigerant(R-410A) cooling coil with aluminium finned copper tubes. Filter
section having 50 mm thick with pre filter 90% efficiency down to 10 micron and secondly Bag type fine filter -
99% efficiency down to 5 micron & TEFC Sq cage induction motor suitable for 415 +10% volts,50 Hz, 3 phase
AC supply,drain connections with 1.25 mm thick stainless steel drain pan alongwith duly insulated as
manufacturer standard and necessary vibration isolation arrangement to avoid any vibration , mounting
accessories etc. complete as per specifications and drawings. The item inclused all the civil activities involved
such as: making space foe footings, casting of pedestal etc. complete in all respect
All TFA/AHU With Pre filter and Fine filter , Thermal Break Profile,mixing chamber and with three phase
motore suitable for VFD Drive/BMS Compitable
Digitally signed by AMIT
Supply, installation, tesing and commissioning of Imported Remote controllers (Corded) for operation of
Hiwall/Cassette/ductable indoor units/AHU.
a MR SITC of Expansion and control Kit Required for the above AHU to make the system complete Nos 3 39,136 1,17,408
Supply, Installation, Testing and Commissioning of Control cum Transmission wiring(4C x1.5sqmm.) in suitable
conduits between indoor & outdoor units including supply of screened wires, supports, installation , saddles,
ties, tags, ferrules, lugs, nuts/bolts/hardware etc. complete in all respects as per specifications and any other
item required to make the system complete.
SITC of Interconnected Copper Piping (Soft/Hard both) the piping duly insulated with Nitrile insulation tubes
of respective sizes and control cabling from AHU to Outdoor units.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper
conductor, single core cable in surface/ recessed steel conduit as required
Supply & Installation of Electrical Panel as per requirement to fulfill the above machinary needs and
operationability.
2 AIR SIDE WORKS
2.1 Site Fabricated Duct - GI duct
Supply,Fabrication , Installation and testing of sheet metal ducts in accordance with the approved shop
drawings and specifications of following sheet thickness completed as required
2.2 Factory Fabricated Duct - GI duct
Supply,Installation,balancing and commissioning of factory fabricated GSS sheet metal ducts
(rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers,
supportsetc.) in accordance with the approved shop drawings and specifications of following sheet thickness
completed as required
2.3 Air Registers (Grilles/Diffusers) :-
Supply and fixing of power coated extruded aluminium supply air grills with aluminium volume control
Supply and fixing of power coated extruded aluminium return air grills with louvers but without volume
Supply, Installation, testing and commissioning of GI volume control duct damper complete with neoprene
rubber gasket, Nut, bolts, screw, linkages, flanges, etc. as per specification Sqm.
Digitally signed by AMIT
2.4 Fresh Air/Exhaust Air Louvers
Supply, Installation, Testing and Commissioning of extruded aluminium louvres with frame bird screeen 50
MR mm pre-filter with frame, mounting arrangement etc. as per specifications and drawings.
2.5 MOTORIZED FIRE AND SMOKE DAMPERS
Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air
path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring
return so as to close the damper in the event of power failure automatically and open the same in case of
power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The
damper shall also be closed in the event of fire signal complete as required and as per specifications
c MR Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers. Including all materials Lot 1 45,000 45,000.00
Sealing the openings around the sleeve of the fire dampers with approved fire sealant, as per the
recommendations of the manufacturer and specifications.
e MR Minor civil works; includes wall openings and making good of them Lot 1 25,000 25,000.00
3 MECHANICAL INSULATION
3.1 DUCT LINE ACOUSTIC TREATMENT
Supply and installation of cross linked open cell Foam/XLPE/Nitrile Rubber Acoustic insulation on ducts having
density of 30 to 60 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C
and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014
). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as
per the approved specifications.
15mm thick XLPE/Nitrile Rubber Acoustic open cell insulation on one side for Duct acoustic insulation
3.2 DUCT LINE THERMAL INSULATION
Supply and installation of cross linked closed cell Foam/XLPE/Nitrile Rubber Thermal insulation on ducts
having density 0f 30 ±3 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to
+100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021
A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2
and as per the approved specifications.
32 mm thick insulation oxide acetate foam/Nitrile Rubber with 2 layesr coat 7 mile cloth insulation or
starbond insulation(for exposed duct)
Digitally signed by AMIT
TOTAL CARRIED TO SUMMARY (Mechanical Insulation works) 0.00 3,51,220.00
Grand Total DSR + MR (inclusive of GST) 47,14,207.00
Digitally signed by AMIT
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT NIA Classroom.pdf
Tender Document
BoQ NIA Classroom.pdf
Tender Document
SCC NIA.pdf
Tender Document
GCC PMC 2022 Upto Amendment 9.pdf
Tender Document
Instruction to Bidder for online Bid Submission.pdf
Tender Document
Forms.pdf
Tender Document
list of make.pdf
Tender Document
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].