CWE Shimla Hills Jutogh
CWE Shimla Hills Jutogh Jutogh Cantt Shimla - 171008
REPAIR / MAINTENANCE OF HT ELECTRIC INSTALLATION AND DISTRIBUTION AND OTHER CONNECTED ITEMS AT SUBATHU
2020_MES_384854_1
CA NO CWE/KAS-48 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Subathu
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE Kasauli
₹24,800
Yes
7 Jan 2021
9 Oct 2020
14 Nov 2020
9 Oct 2020
12 Nov 2020
29 Oct 2020
60 days
Amount
Excavation in trenches not.exc 1.5 m wide and n.exc 1.5 m in depth and getting out in hard/dense soil including dressing / trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified.
Returning, filling in including spreading, levelling and watering and well ramming in layers n.exc 25 cm thick complete all as specified.
Removing excavated surplus soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified.
Sand cushioning to UG cable 8cm thick before laying the cable and 15cm above the cable, stretching and testing of cable complete all as specified. Notes : (i) Consolidated / Punned thickness shall be considered for purpose of payment (ii) Sand shall be same as specified for plastering work.
Burnt bricks sub class 'B' laid flat dry across the cable for cable protection complete all as specified.
GI tubing light grade 80 mm bore including specials such as bends etc, along the pole / across road crossing /passing through culvert for protection of UG cable complete all as specified.
Straight through (Heat shrinkable) joint kit suitable for 11 KV UG XLPE cable of size 50 to 95 Sqmm 3.0 core in repair complete all as specified.
End termination (Heat shrinkable) joint kit suitable for 11 KV UG XLPE cable of size 50 to 95 Sqmm 3.0 core in repair complete all as specified.
HT XLPE insulated cable, PVC bedded, galvanised steel strip, armoured heavy duty electric cable with aluminium conductor, 11000 volts grade, cross-sectional area 95 sq. mm 3.0 core including taking out existing unserviceable cable, testing and commissioning complete all as specified. Note: Excavation, earth work and pipe protection shall be measured and paid separately.
Overhauling of step down outdoor/indoor transformer 11/0.433 KV (400-750 kVA) by disconnecting HT/LT terminals, decanning transformer oil removing sludge, cleaning of HT /LT bushings to remove dust particles /dirt etc. Cleaning the core and winding with compressed air and re-assemble complete including replacement of copper windings, copper washers, rubber bushes of HT/LT bushings replacement of cork sheet of 6 mm thick suitable for transformer top cover, terminal boxes refilling the transformer oil and toping up with new transformer oil and centrifuging to achieve the dielectric strength upto 50KV painting with two coats of synthetic enamel paint over a coat of red oxide primer after preparation of painted surfaces of transformer and testing and recommissioning on load etc complete all as specified. Note : Dehydration of transformer oil by filtration, topping up transformer oil, shall be measured and paid separately as supply only under respective items.
All as per item No. 10 above but capacity of transformer 100 KVA to 250 KVA.
Disconnecting electrical connections of transformer of capacity 400 to 750 KVA of any make & any type loading the transformer on heavy vehicle (open chassis) type from existing platform/four pole structure, by heavy crane long boom type suitable for shifting and loading transformer and transporting of transformer for repair / rewinding at workshop at Dharampur from Subathu Stn Area including unloading of transformer from vehicle at workshop & Opening up transformer step down 11/0.433 KV by unscrewing all nuts/bolts and washers of top cover duly draining out complete transformer oil and kept aside for re-use. Disconnecting of all HT/LT wiring tap changer, complete LT/HT bushing, air breather etc and kept aside for re-use the serviceable parts and removal of unserviceable parts and taking out complete core assembly of transformer with help of chain pully to carry out the following works:-
Deslurring of transformer tank by taking out the complete deposited transformer oil sludge and cleaning thoroughly the transformer tank by washing & wiping out all dirt/rust accumulated including making preparation of old painted internal/external surfaces of transformer. Painting the internal surfaces of transformer with two coats of high grade anticorrosive varnishing paint over a coat of red oxide primer. Painting to external surfaces of transformer with two coats of Ist grade synthetic enamelled paint over a coat of red oxide primer all as directed.
Cleaning the transformer core assembly using electric blower and making the core free from sludge, dirt and any other foreign materials from its surfaces including provision of high grade insulation varnish and raising insulation of the core through heat chamber and raising of IR valve /LV-E > 500 Mega ohms HV-E >1000 Mega ohms
Assembling the transformer including supply of complete set including replacement of defective accessories such as oil seal , gasket , LT/HT bushing, stud, air breather, tap changer, making necessary LT/HT wiring as dismantled( Supply only spares as required shall be measured & paid separately under relavent items, Unit rate quoted shall deemed to include the cost of oil seal & gasket. Powering of dehydration/filtered transformer oil (dehydration charges shall be measured and paid separately) as obtained during dismantling and top up balance quantum with new transformer oil as required (New transformer oil shall be measured & paid under relavent item) after successfully repairing the transformer reloading the same & place to its original location and installation complete including making LT/HT side cable connection, earth connection and testing complete .
All as per item No. 12 above but capacity of transformer 100 KVA to 250 KVA.
Replacement of worn out copper strip/ wire /rod as per existing gauge/size complete all as specified.
HV Bushing of transformer with Brass metal connecting rod, nut bolt and washer,suitable for 400 KVA to 750 KVA capacity of tranaformer 11000 Volt as per IS 3347/1967 complete all as specified.
All as per item No. 15 above but capacity of transformer 100 KVA to 250 KVA.
LV Bushing of transformer with Brass metal connecting rod, nut bolt and washer,suitable for 400 KVA to 750 KVA capacity of transformer 1100 Volt as per IS 3347/1967 complete all as specified.
All as per item No. 17 above but capacity of transformer 100 KVA to 250 KVA.
Silica gel crystal in replacement in any type and capacity of transformers complete all as specified.
Silica gel breather assembly fixed in repair complete with silica gel crystal complete for transformer of capacity 400 KVA to 750 KVA complete all as specified.
All as per item No.20 above but capacity of transformer 100 KVA to 250 KVA.
Filtration & Dehydration of transformer oil using ON-LINE filtration plant to achieve dielectric strength minimum 50 KV/ 4mm etc. complete all as specified.
Supply of transformer oil conforming to IS 395-1983 having die electric strength minimum 50 KV / 4mm including topping up in transformer complete all as specified.
PCC 1:4:8 type D-2 (using 40 mm graded stone aggregate) in foundation of electric poles, struts surface sinished fair and even without using extra cement complete all as specified.
Anti-climbing device, spikes type fabricated out of M.S bars ( round, square and flat ) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole suitable for PCC/Steel poles including two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified.
Lightening arrestor expulsion type for out door use complete with all fitting transmission class discharge capacity 65 KA suitable for 11000 volts including brackets, clamps, nuts and washers and connecting to earth wire 4 mm dia GI wire fixed in repair complete all as specified.
Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green, single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified.
Drop out expulsion type fuse with fuse barrels out door HT 11KV tripple pole mounted on HT 11 KV insulators & MS frame fixed in repair including two coats of aluminium paint over a coat of red oxide primer on MS work complete all as specified.
Switch Air brake, gang operated, triple pole, mechanically operated mounted on HT insulators (12 insulators pin type ) and MS galvanised steel frame with operating mechanism operated from ground level with fixed contacts of phosphorous bronze and moving contacts of copper including operating rod for current rating upto 200 Amps, 11000 volts complete with locking arrangement, including 3 Nos drop out explusion type fuses with fuse barrels of required capacity to suit load at site, including provision of two coats of aluminium paint over a coat of red oxide primer on MS work complete all as specified.
Earthing complete with and including galvanised steel earth plate electrode 60 cmx 60cm x 6 mm thick surrounded by mixture of charcoal and salt in alternate layers , buried directly in ground vertically in a pit of depth not less than 2.25 meter deep below ground level with top edge of the plate at a depth of not less than 1.5 mtrs below normal ground level connected to equipment by using GI strips of size 32x6 mm as earthing lead by means of bolts ,nuts, check nuts and washers of galvanised iron or steel earth wire protected by galvanised steel pipe 15 mm bore light grade and 20mm bore Light grade GI watering pipe connected to main switch or main control board or GOD or lightening arrester all as shown in electrical plate No. 3 of MES Schedule Part - I & including necessary excavation and earth work in any type of soil complete all as specified.. Note : (i) Unit rate quoted shall include the cost of charcoal and salt in alternate layers, 20 mm bore GI pipe (Light grade ) for watering , protection pipe, funnel, wire mesh , PCC 1:2:4 type B1 chamber in cement concrete ,50 mm thick precast RCC M-25 ( Design mix) cover duly reinforced with XPM (weight not less than 3 kg /sqm ) and CI frame etc , and including provision of test point , connecting to test point and testing on completion etc, complete all as specified. (ii) Unit rate quoted shall include earthing lead and protection pipe upto 7.5 metre from top of earth plate
Glavanised iron strip 32x6mm buried in ground complete all as specified.
Chemical earthing (Pipe in pipe technology) Two B class IS mild steel pipe, one inside the other, hot dip galvanised with 100 micron coating outside and about 300 micron coating inside filled with high conductive and corrosion Resistant Crystalline Mixture inside and Backfill compound around the outer electrode) outer electrode dia 72 to 80mm and inner electrode dia 35 to 40 mm both 10' long, including making earth pit of size 4' x 4' and 11' deep fill the entire pit with black cotton soil or normal soil, pour enough water so that pit is full with water, leave it for three days so that soil soaks up the water, the soil level has goes down, again top up the pit with soil & fill the water. After two or three days when the pit is sturdy and ready for earthing purpose, install the earthing electrode as per installation method as below:- (a) Mix backfill compound evenly with soil. (b) Remove plastic sleeve carefully from electrode. (c) Place naked electrode at centre of pit. (d) Start refilling empty space around electrode with backfill compound in layers. (e) Pour some water and poke the pit with a long wooden rod to allow trapped air to escape. (f) Gradually continue refilling process till electrode is buried in the pit up to the green patch painted on the top portion of electrode.
(g) Ensure that pit is not watery (h) Pack electrode with compound nicely and tightly, so that it stands firmly in pit. (j) Pour a few buckets of water around pit. (k) Pour a few buckets of water around in the pit everday for 10-15 days for system to set. (l) Connect the earth electrode with equipments by 25mm x 3mm aluminium strip. (m) Earthing test point terminal block made of gun metal size 150x100x50 mm drilled and screwed including 4 Nos 8 mm dia 40 mm long hexagonal head bolts and washers duly fixed on walls with fasteners 4 Nos. Note : (a) Earth resistance shall not be more than 5 Ohm. (b) Aluminium strip for connections shall be measured and paid separately. Make of Electrode and back fill compound - Ash, Model Ash39, Dia 76-80mm. Length-10 ft or equivalent of VIPRA/Earthtech.
Time switch astro type 110 - 240 VAC 3 Phase - 4W 3 Channel, Base/DIN with necessary electric connection including setting the time and other specification as directed Make:L&T cat No. T3DDT0 or its equivalent in the makes mentioned in Appendix 'A'.
Time switch astro type 1 Phase - 2W 2 Channel, Base/DIN with necessary electric connection including setting the time and other specification as directed. Make: L&T cat No. T2DDT0 or its equivalent in the makes mentioned in Appendix 'A'.
Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and applying one primer coat, one under coat and one finishing coat of paint complete all as specified.
Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20 cm size complete all as specified.
Vasudeva Trading Co.
bharat refrigeration and electric co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .