Executive Engineer Electrical
Engineering Works and Services Section CSIR-SERC CSIR Campus Taramani Chennai 113
Rectification of faulty outdoor OLTC transformer and associated HT LT switch gears in Sub stations at CSIR SERC Campus Taramani Chennai 600 113
2021_CSIR_99185_1
50(41)/21-22/EW/SE
Open Tender
Electrical Works
Item Rate
90 days
CSIR-SERC Chennai
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
Exempted
25 Jan 2022
22 Dec 2021
14 Jan 2022
22 Dec 2021
12 Jan 2022
22 Dec 2021
22 Dec 2021 - 5 Jan 2022
Amount
Charges for Re Winding of 1000 KVA,11kV/433V Transformer for the H V & LV THREE PHASE Windings, drain out oil from transformer, open the top cover,disconnect the primary and secondary winding connections lifting the core and winding,inspect the core and windings, de breasing the primary and secondary terminal and tap switch connections, remove the existing HV & LV coil from core (R,Y,B Phase), re winding the HV & LV New Wire coils ( For three phase )assembling the core and winding with new insulating materials breasing the HV & LV connections, fixing the tap switch and connected, improving the insulation values. Cleaning the tank,Transformer Complete Inside Insulation Painting WorkOut Side Epoxy with spray Painting work,replaced water proof tape fixing in bus duct & hood, Complete Gaskets / Oil Seals,for top cover and HT & LT treminal bushings, tanking the core and winding,close the top cover, filtered and filling the new oil up to top leval testing the transformer.Rates includes Less Old Copper.
Charges for Filtration of Transformer Oil through streamline filter unit to improve Dl-Electrlc strength to optimum value ,Charges for Testing and lssuing Test Report for Dl-Electric of Transformer oil. Charges for Testing and lssuing Test Report for Acidity of Transformer oil.
Replacing the existng Dehydrating Silica Gel and Filling Fresh Silica Gel Suitable for 1000 KVA Transformers
Supply and filling of Transformer oil , as per : IS : 335 /1993 (actual quantity will be billed based on the site requirement)
Filteration of On Load Tap Changer by flushing with transformer oil using stream line filter unit including Removing and Refilling of transformer oil and Replacing top Cover Cork Rubberized Gaskets of existing 1000kVA Transformer and OLTC Electrical and Mechanical Fixed and Moving Contact Servicing and Overhauling Work & Checking the lnternal Wiring of RTCC & OLTC Panel.
Charges for lmproving of lR Value in after rewinding transformer, the existing 1000 KVA,11kV/433V outdoor Transformer .
Charges for Testing of Transformer and issuing Testing Certificate. a) Insulation Value Test b) Voltage Ratio Test c) Short Circuit Test d) Open Circuit Test e) Winding Resistance Test f) High Voltage Test g) Magnetic Balance Test h) DVDF Test
Transportation charges of 1000kVA,11kVA/433V transformer from CSIR to testing site and testing site to CSIR Tharamani including crane charges for lifting ,loading and unloading of1000kVA outdoor transformer at CSIR & testing site.
Supply ,installation,testing and commissioing of suitable Buchholz Relay including internal wiring for 1000kVA ,11kV/433V outdoor transformer in the existing transformer as per site condition as required.
Supplying ,installation,testing and commissioing of Vaccum Circuit Breaker (VCB) spare parts in the existing 3 Pole VCB of Kirloskar Make ,Type:C-500,Rated voltage:11kV,Normal Current :630A,Breaking Capacity :26.3kA as per specification IEC 56
VCB Vaccum Bottle Interrrupter
VCB Vaccum Bottle Interrrupter Housing
Moving Insulator
VCB Sprout Top Left
VCB Sprout Top Middle
VCB Sprout Top Right
Overhauling and Maintenance of HT VCB for the following . Removing the existing VCB 630A 3 Pole EDO (Electrical Draw Out) dismantiling the all parts including the primary and secondary contacts of the clening the dust, checking mechanism,lubrication and refixing the same. Measure the insulation resistance values for all poles with open condition and closed condition.Make: Kirloskar
Chargers for testing & issuing of test Certificates with suitable mesuring kit for HT VCB panels for the following : a) Over Current, Earth Fault Relay and short ckt test b) Auxiliary Relay c) Master Trip Relay d) Under Voltage / Over Voltage Relay.
Charges for Outdoor sandwich LT Bus duct spray painting work as per ISI Standard with existing Colour spray paint with two coat for SS-1,2 & 3 including painting of supporting structure with black paint as required. Note : 1. The Tenderers are requested to inspect the ste and submit the tender before quoting. 2. The rates quoted for all items shall be inclusive of income tax, GST & TNCWW Cess etc., as applicable. 3. TNCWW Cess @ 1% Income Tax @ 2% and TDS on GST @ 2% will be deducted from the bill.
A K ENGINEERING SERVICES
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .