Loading…
Loading…
Tender ID
Tender Value
₹26.0 L
EMD Value
₹52,043
Closing Date
14 Feb 2026, 6:55 pmClosed
Executive Engineer PWD Howrah Electrical Division
Office of the Executive Engineer PWD Howrah Electrical Division Onkarmal Jetia Road Howrah 711103
Renovation Work of Electrical installation in Administration Building (Two Storied) Building in the campus of WBCEF, Howrah.
2026_WBPWD_992640_1
WBPWD/EE/HED/NIT- 06 (2nd Call) of 2025-2026
Open Tender
ELECTRICAL WORKS ORG
Percentage
30 days
Administration Building (Two Storied) Building in
Please refer Tender documents.
11 documents required · 11 mandatory
₹52,043
17 Feb 2026
21 Jan 2026
17 Feb 2026
22 Jan 2026
14 Feb 2026
30 Jan 2026
Dismantling the existing and damged electrical installations ( Cable, DB's, wiring, fittings etc.) from its existing position and deposit to the authority with challan as per direction by the EIC.[NS]
Supply & Delivery of 1.1KV grade following sizes PVC/A aluminium Cable (Make-Polycab/Havells/ Gloster/Finolex/RR Cable/Mescab) 4 core 16 sqmm ( existing VTPN to HTPN) [NS]
2 core 10 sqmm (HTPN to SPN ) [NS]
Laying of cable as below, after cutting floor/pavement /wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish a) From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/ wall etc.[F-3/5(i)]
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. a) 10 SWG.[G-2/5(iv)]
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting.[F-1/2(a)]
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting.[F-1/2(b)]
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : [F-4/7(c)] 4 core 16sqmm
2 core 10 sqmm [F-4/7(a)]
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : 4 core 16 sqmm [F-4/8 (b)(xii)]
2 core 10 sqmm [F-4/8 (b)(iii)]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment a) 6 way Enclosure-01No, b) 16-32Amp SPMCB-18 Nos, c) 63Amp,4 pole Isolator-01 Nos. ( MAKE-Legrand/Seimens/ L & T) [D-10/14+D-6/7+ D-5/6]
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. a) 12way Enclosure-01 No,b) 6-16Amp SPMCB-10 Nos, c) 40Amp Isolator-01 No, ( MAKE- L& T/Seimens /ABB) [D-9/13+ D-6/7+D-5/6]
Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles a) 19 mm dia 3 mm thick polythene pipe without earth continuity wire. [E-3/6(a)]
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Polycab/Havells/Gloster/Finolex/Mescab) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required a) 2x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) [E-9/1(b)]
b) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) [E-9/1(s)]
c) 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC [E-9/1(v)]
d) 2x 84/0.3 (6 sqmm) + 1x56/0.3 (4.0 sqmm) as ECC [E-9/1(v)]
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. a) 1.5sqmm [F-5/9]
b)2.5sq mm
c) 4.0sq mm
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for horizontal run & above false ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed]a) Average run 9 mtr [E-25/5(d)]
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Make-Polycab/Precision) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed] a) Average run 8 mtr [E-25/4(c)]
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish. ( 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC) a) On Board [E-20/3(a)]
Supply & Delivery 240 Volt,50Hz,4 ft long , Max20 Watt,efficacy-100lm/w, PC body/Al housing Double LED Tube Light fittings complete with all accessories including LED Tube. [Make: PHILIPS /CROMPTON/ wipro or Manufacturer with own NABL accredited lab with valid test certificate ] [NS]
Supply & Delivery 240 Volt,50Hz,4 ft long , Max20 Watt,efficacy-100lm/w, PC body/Al housing Single LED Tube Light fittings complete with all accessories including LED Tube. [Make: PHILIPS /CROMPTON/ wipro or Manufacturer with own NABL accredited lab with valid test certificate ] [NS]
Fixing only single /twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener.[C-2/14(b)]
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.[[C-2/17]]
Supply & fixing 240V, 12 W,CDL, B22, LED Lamp on the existing place as per direction of EIC . ( Make- Havells/Philips/ Cromton)[NS]
Supply & Fixing of 2'X2' recess mounted fitting , Wattage: Max. 36 W, Lumen output: Min.100lm/W, Luminous flux: Min.3600 lm, complete after cutting false ceiling as per direction of EIC ( Make: Crompton, Philips, Wipro or manufacturer with own NABL accredited lab with valid test certificate.)
Supply & fixing Recess mounted 3W spot Round light,Lumen Output:min 120lm/W Temp 3000K,PDC Housing after cutting false ceiling as per direction of EIC ( Make: Crompton, Philips, Wipro or manufacturer with own NABL accredited lab with valid test certificate.)
Supply & fixing 220-240V AC, 50 Hz, 25W Strip light Temp 6500K,LED 5W/m Strip with adaptor after cutting false ceiling as per direction of EIC ( Make: Crompton, Magic,Wipro or manufacturer with own NABL accredited lab with valid test certificate.)IP 20 Protection including 2 yrs warranty.
Supply & Fixing of Recess mounted round light fitting on ceiling after cutting the false ceiling as per actual size Wattage: Max. 12 W, Lumen output: Min.100lm/W, 1250lm/12W ,PDC housing, ( Make: Cromton, Philips, Wipro or manufacturer with own NABL accredited lab with valid test certificate.) [NS]
Supply & Fixing of Bulk Head light fitting on wall by screws etc ,Wattage: Max. 6 W, Lumen output: Min.100lm/W, pressure die cast housing, Driver rating should be higher than the bluk fitting rating, Make: Cromton, Philips, Wipro or manufacturer with own NABL accredited lab with valid test certificate. [NS+ C-2/13]
Supply & Delivery of 240 Volt, 50Hz ac ceiling fan. BEE star rated (Make -Crompton,Orient, Polar) 65W, 200CMM,1200mm(48'') sweep [NS]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 3x1.5 sqmm flexible copper wire.[C-3/21(a)]
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.[E-18/10]
Supplying & Fixing iron beam fan clamp of two piece type, as per approved specification, fabricated from 40 mm x 9 mm MS sheet flat suitable for beam having flange upto 150 mm wide – (As per Drawing no. 476 of PWD Specification Book – May 1991) [D-14/30]
Engraving the deptt. number with 10 mm lettering on the body as per GS.[C-3/24a]
Extra for additional one letter incl. hifen, stroke and stop as per GS. [C-3/24b]
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS. [C-3/26a]
Extra painting for additional one letter of the engraved number as per GS. [C-3/26b]
Supply & Delivery of 240 V,450 mm wall mounting type bracket fan incl. all accessories as per direction of EIC (Make-Cromton/ Orient) [NS]
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. Length. [C-4/29]
S&F 300mm dia 1400RPM heavy duty, Full Metal Body, Exhaust fan complete with frame, motor, spider arm bracket blade etc. ( Make-EPC/Crompton/Orient) [NS]
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter: a) 30 cm (12") [C-4/28(b)]
S&F louver shutter ( Aluminium) on wall with necy. bolts & nuts (6mm dia x 62mm long) a) 30cm (12"). [C-4/30(b)]
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Make- Legrand-Myrius/Arteor/Panasonic vision), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-18/12]
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Make- Legrand-Myrius/Arteor/Panasonic vision) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-18/9(a)]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Make- Legrand-Myrius/Arteor/Panasonic vision) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-18/9(b)]
Supplying & Fixing GI Modular Switch Board of the following sizes complete with top cover plate flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works a) 6 module [E-17/1(b)]
Supply & Fixing 240 V 6 A Modular type switch (Make- Legrand-Myrius/Arteor/Panasonic vision) on existing GI Modular type switch board having top cover plate and making necessary connections as required. [E-17/3(a)]
Supply & Fixing 240 V, 6A, 5 pin Modular type plug socket(Make- Legrand-Myrius/Arteor/Panasonic vision), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/4(a)]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Make- Legrand-Myrius/Arteor/Panasonic vision), without plug top and switch with 2 Module GI /PVC Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/5(a)]
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Make- Legrand-Myrius/Arteor/Panasonic vision) & necy. Connections. [E-17/5(b)]
Supply & Fixing 240 V, 25A Modular starter (Make- Legrand-Myrius/Arteor/Panasonic vision) on 2 module GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/2(a)+ E-19/20]
Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board on the existing place.[D-13/20(a)]
Supply & Fixing 240 V, Bell push type switch (Anchor) on sheet metal switch board incl. S & F 100x100x65mm MS (16SWG) switch board and bakelite/ perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.[NS]
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works. 200 mm x 150 mm x 65 mm [E-4/11(d)]
240 mm x 200 mm x 65 mm [E-4/11(e)]
Supply & Fixing bakelite / perspex top cover on existing Inspection board by Brass screws 200 mm x 150 mm x 65 mm. [E-5/13(d)]
240 mm x 200 mm x 65 mm [E-5/13(e)]
Supplying & Fixing two way CI Round box with cover concealed in ceiling/wall.[E-6/20(b)]
S & F Lightning Conductor Air Terminal made of 20 mm dia 1000 mm long GI pipe (lSI Medium) having five discharge prongs of 4 SWG GI (Hot Dip) wire at top duly soldered/ welded with 7 /16 stranded GI (Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. complete duly grouted on the parapet etc. in CC mortar ( 4:2:1), including thimble joints of 7/16 SWG wire and (25 x 6) mm GI strip with SS nuts, bolts &washers, (P-J-2/Item 14+NS)
Supply & fixing of 25 mm x 6 mm thick GI (Hot Dip) flat / strips for Horizontal & Vertical run on wall / floor with GI shaddles as required including drilling holes, bolts, nuts, washers, etc./ and mending good the damages to building works , (Page : G-3/ltem-5d).
Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (lSI- Medium) GI pipe protection as below and mending good damages to the building works; (P:J-1/ltem-4)Length upto 0.5 Mtr
Length Above 0.5 Mtr
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run, (P :J-1/ltem-7)
Supply & Fixing of Testing Joints by 25 mm x 6 mm thick GI (Hot Dip) strip 125 mm long on wall after making suitable arrangement to establish a clearance of 50mm from wall for making junction connection with vertical conductor and conductor from earth electrode complete with S & F GI bolts, nuts, check- nuts, spring washers etc. as required. (Rate arrived from G.S. Page J-2/ltem-13)
Earthing with 65 mm dia GI pipe (TATA-Medium) 3.0 Mts. long with welded 2 nos. half circle bracket made of GI strip (65 x 8) mm. with two holes on extended portion of the each strip of length min. 250 mm, and 1 No, 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (lSl-Medium) protection [3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts. (Rate arrived from G.S' Page : G-1"/ltem-2d)
Excavation of soil for installation of Earth Electrode and filling & ramming as to GS. (For morum soil)(Page : G-1lltem-1b) .
Supply, Laying & Fixing of 50mm x 6mm galvanized (Hot Dip) steel strip in underground trench for interconnection between the Earth Points by joining (As per item no 11). (Rate arrived from G.S. Page : K- 3/ltem -134 + G-Llltem-1a.)
Cost of jointing for Horijontal & vertical run of GI strip through welded joint of (25 x 6) mm or (50 x 6) mm GI Strip to Lap joints/ 'T' joints, etc. and painting the joints with 2 [two) coats of bituminous paint. (NS)
S&F of 25A timer controlled starter DB for 1no single phase AC/Compound light in SS double door 12-way DB enclosure (Make:L&T/ Legrand/ABB) with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish.All connections should be made by copper wire of 4mm² & 1.5 mm² and finishing with dowells solderless socket by crimping method incl necessary connection & provision for earthing attachment incl Ferruling & marking with S&F following Electrical accessories as per direction of EIC:- [NS]
25A DP MCB c curve breaking capacity 10kA (Make:L&T)-- 1no
24Hr x 7days programmable Digital timer (Make:L&T Cat no 67DDT0) -- 1no
3-pole power contactor(Make:L&T cat no MNX22/240V) -- 1 no
2-Modular AC motor starter (Make:Legrand/Myrius Cat no 673031) -- 1 no
2 Modular Plate and frame (Make:Legrand/Myrius Cat no 673242) -- 1 no
10A,250V AC ON-OFF-ON SPDT toggle switch (Make-Kaycee Model No:KT1032BY) - 1 no
230V AC LED indication lamp (Make-L&T) RED COLOUR-- 1 No
Din rail mounted Terminal Block for Outgoing & Incoming(Make:Elmax Model:KUT4) -- 4 nos
6A SP MCB c curve breaking Capacity 10kA-- 1 no(Make:L&T)
S&F of 40 A timer DB for 1no Three phase Compound light in SS double door 14-way DB enclosure (Make:L&T/ Legrand/ABB) with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish.All connections should be made by copper wire of 4mm² & 1.5 mm² and finishing with dowells solderless socket by crimping method incl necessary connection & provision for earthing attachment & neutral link incl Ferruling & marking with S&F following Electrical accessories as per direction of EIC:- [NS]
40 A FP MCB c curve breaking capacity 10kA (Make:L&T)-- 1no
24Hr x 7days programmable Digital timer (Make:L&T Cat no 67DDT0) -- 1no
40A, 3-pole power contactor (Make:L&T cat no MNX40/240V) -- 1 no
10A,250V AC ON-OFF-ON SPDT toggle switch (Make-Kaycee Model No:KT1032BY) - 1 no
230V AC LED indication lamp (Make-L&T) RED COLOUR-- 1 No
Din rail mounted Terminal Block for Outgoing & Incoming(Make:Elmax Model:KUT4) -- 7 nos
6A SP MCB c curve breaking Capacity 10kA-- 1 no(Make:L&T)
Supply 1.1KV grade following sizes PVC/A aluminium Cable (Make-polycab/Havells/ Gloster) a) 4 core 10 sqmm (Timmer to existing loop box of Roof light ) [NS]
b) 2 core 10 sqmm (Timer to existing loop box of Roof light) [NS]
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. [F-2/1(a)]
Laying of cable as below, after cutting floor/pavement /wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish a) From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/ wall etc. [F-3/5(i)]
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. a) 10 SWG [G-2/5(iv)]
Laying of 2 core 10 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. [F-1/2(a)]
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : 4 core 10sqmm [F-4/7(c)]
2 core 10 sqmm [F-4/7(a)]
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : a) 4 core 10 sqmm [F-4/8 (b)(xii)]
b) 2 core 10 sqmm [F-4/8 (b)(iii)]
Supply, Installation Testing & commissioning of 10 KVA 1 Phase, 50 Hz, 160V-300V input, 1 phase output UPS system with required nos of SMF Battery, Rack DC connecting cables and complies with following feature/ specifications. (Make- APC/Numeric/Emmerson /Powerone/Microtek) [NS]
iii) Power Supply-1 Phase, 50 Hz,160V- 300V AC
iv) Voltage Range 110V-300 VAC @ 50% load
v) Input power frequency range 50 Hz-60Hz± 5% auto sensing
vi)THD of input current <10%
vii) DC Voltage: 192-240 V
UPS Output
i) Phase- Single
ii) Voltage - Single Phase - 220/230/240 VAC
iii) Frequency - 50 Hz
iv)Frequency Synchronisation - 47.5 Hz to 52.5 Hz
v) Output Voltage Regulation - ±1%
vi) THD of output Voltage
THD < 3% (Linear Load)
THD < 5% (Non Linear Load)
vii) Power Factor 0.8
viii) Crest Factor 3.1
ix) AC to AC overall efficiency: 92%
x) ECO mode: NA
xi)Converter : Yes
xii)Configurable bypass: Yes
Static Bypass Switch
1. The statich shall consist of fully rated Silicon Controlled Rectifiers (SCRs)
2. The static bypass switch shall automatically transfer the critical load to bypass input supply without interruption after the logic senses one of the following conditions Inverter overload beyond rating. Battery runtime expired and bypass available. Inverter failure. Fatal error in control system.
3. The static bypass switch shall be equipped with a manual means of transferring the load to bypass and back to inverter.
4. Also UPS should have separate manual bypas switch.
Overload Capacity
i) 105-110%- 3 mins.
ii) 111-130%- 30 sec.
A) The Display panel should capable for display of following measurement/ as per standard availability of specified manufacturer.
i) Input - Voltage/ Frequency/ Current.
ii) By- pass - Voltage/ Frequency.
iii) Output - Voltage/ Frequency/ Current.
iv) Battery - Voltage/ Current/ Percentage
v) Load - KVA/ KW/ Percentage
vi) Others standard measurement as per manufacturer standard & IS specification.
B) The display panel should also capable to display following indication
i) DC bus boltage - High/ Low
ii) Inverter - Overload / Short Circuit
iii) Over Temperature -Battery / By-pass/ Inverter
iv) Fault - Rectifier/ By-pass / Inverter/ Paralleling
v) Fuse failure- Input / Output
vi) Battery - Low/ Overcharged
Alarms
The UPS should generates an audioble alarm for following condition.
Mains failour
Battery Low
UPS Over Load (>_ 110 %)
Fault
Shut Down
Battery Bank / Charger/ Rack
i) Backup Capacity - 30 min on Full load
ii) Battery Bank VAH - 10080 VAH
iii) Battery Type - 12V, VRLS SMF type
iv) Make - Amara Raja/ Exide/ Quanta
v) Minimum charger rating- 10% of battery AH rating offered
vi) Battery recharge time (after complete discharge) to 90% capacity - 10-12 Hrs.
vii) Battery Protection - DC MCCB (Internal/ External)
viii) Battery Housing - MS steel rack of compact & space saving design.
ix) Battery End Cell Voltage - 1.75/ 1.80 V
UPS Physical Condition
i) Operating Temperature- 0-40°C Continuous
ii) Humidity-O - 95% Rh (non-condensing)
iii) Protection Class - IP-20
iv) Type of Cooling - Forced Air
v) Noice Level - <58db at 1 mtr distance
vi) All the electronic cards inside shall be with conformal coating to protect from harsh / Moist environment.
vii) UPS panel should have Dust filter protection with sensor.
Certification
Standard IS/IEC certification must be submit along with offer. Product should have BIS,CE & RoHS,PEP(Product Environmental Profile) Compliance.EN 62040-2(EMC),EN 62040-1(Safety),IEC 62040-3(Performance)
Terms & Condition
i) 24 months onsite warrantee on complete installation inclusive of spare parts. ( except physical damages of installation i.e. Rat etc. attack)
ii) Any Problem must be set right with 24 hrs after reporting.
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required. a) 2x80/0.4 (10 sqmm) + 1x84/0.3 (6 sqmm) as ECC [E-9/C-1(a1)]
Cutting Channel of size (43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles a) 25 mm dia 3 mm thick polythene pipe without earth continuity wire. [E-13/10(b)]
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 10sqmm [F-5/9(iv)]
6 sqmm [F-5/9(iii)]
Supplying and fixing 2 way MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment a) 63 Amp Amp DP MCB (incoming & Outgoing side of UPS) [D-9/11& D-6/7]
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. a) 2+16 way Enclosure-01 No,b) 10Amp SPMCB-14 Nos, c) 63Amp Isolator-01 No, ( MAKE- Legrand/Seimens /ABB) (UPS SPNDB) [D-9/13+D-6/7+D-5/6]
SITC OF AC MACHINE
Supply & Delivery of inverter type of Split Air Condition machine having cooling capacity not less tan 6900W, ISSER 3.8 to 4.39, BEErating not less than 3 star, Noise Level not more than50db. This split Air Conditioning machine fittedwit rotarycompressors,LCD remote & all other accessories suitable for Refrigeration R32/R410A. [O-General/Daikin /Hitachi/ MitsubishiElectric/ Mitsubishi Heavy duty industries as per approved by EIC/authority). ( Accountant Room-02 sets, Store office room-01set & ML Section-02 Sets) [NS]
Supply & Delivery of Split Air Condition machine having cooling capacity not less tan 5000W, ISSER 3.8 to 4.39, BEE rating not less than 3 star, Noise Level not more than50db. This split Air Conditioning machine fittedwit rotarycompressors,LCD remote & all other accessories suitable for Refrigeration R32/R410A. [O-General/Daikin /Hitachi/MitsubishiElectric/Mitsubishi Heavy duty industries as per approved by EIC/authority). (Commandant Chember-01 Set) [NS]
Installation,testing & commissioning of the above- said split Acs incl. supply & fixing required Angle Iron Structure on wall for placing outdoor unit & mending good the damges as per direction of E.I.C. [NS]
Supply & installation of extra add-on items-HVAC grade 5/8" ( For suction) & 1/4" ( for Discharge) copper refrigerant pipe with 9mm thick the nitril rubber, insulation including shaddle, screw, insulation tape,Fastner etc for above AC machine as per direction of EIC. [NS]
Supply & Laying 20mm hard PVC Pipe ( Heavy duty) for water drainage. [NS]
Supply & Laying 1.1KV,grade,3 core 4sqmm flexible copper cable with screw, saddle, drill macchine, nut bolt etc all necessary items needed for connection. (From starter to AC out door connection) (Make-Havells/KEI/polycab/Fenolex as per approved by EIC) [NS]
FIRE DETECTION SYSTEM AT ADMIN. BLDG ONLY
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel ) [NS]
Supply, Installation.Testing & Commisioning of Addreaaable Manual can Point ( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make : Cerberus Pro/ Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo/ Morley/ Eaton/ GST /Ravel) [NS]
Supply, Installation, Testing & Commissioning of IP Addreuable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make: Cerberus Pro/Honeywell/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST ) [NS]
Supply, lnstallation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have maimum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to lectromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. (Approved Make : Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST) [NS]
Supply, Installation, Testing & Commissioning of Addressable Monitor Modules ( VDS / UL /ERTL/ LPCB / FM approved ) for monitoring Flow switches / Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton/ GST /Ravel) [NS]
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Cerberus Pro/Honeywell/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley/ Eaton/ GST/System Sensor/Agni Suraksha /Ravel ) [NS]
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/Gloster/ RR Kable/Polycab) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall. [NS]
Supply, Installation,Testing & Commisioning of Microprocessor based addrenable fully networkable (03 LOOP PANEL) fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, LC D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. [NS]
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make : Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo/ Morley/ Eaton/ GST / Ravel)
NOTE :- 1) The Fire Alarm system shall comply with latest requirements of -- (i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189, (iii) NFPA 70 National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code , (v) Local Statutory Regulations , (vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand.
TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done.
TERMS & CONDITIONS :-
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Add GST @ 18%
Add LWC @ 1%
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.50 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.38 MB
BOQ_2427403.xls
BOQ • 1.23 MB
2911.pdf
Tender Documents • 1.86 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .