| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.6 LAccepted-AOC | ₹39.6 L Quoted ₹40.0 L | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹42.8 L+₹2.8 L (6.90%)Rejected-Finance | ₹42.8 L+₹2.8 L (6.90%) | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 3 | L3₹43.9 L+₹3.9 L (9.80%)Rejected-Finance R O WARD NO 08 H NO 108 DHAR ROAD UDHAMPUR TEHSIL DISTT UDHAMPUR 182101 | UDHAMPUR | UDHAMPUR | JAMMU KASHMIR | 182101 | ₹43.9 L+₹3.9 L (9.80%) | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 4 | L4₹44.0 L+₹4.0 L (9.91%)Rejected-Finance | ₹44.0 L+₹4.0 L (9.91%) | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 5 | L5₹44.8 L+₹4.8 L (12.0%)Rejected-Finance C O SECTOR 02 HOUSING COLONY CHANNI HIMMAT JAMMU J K PIN 180015 | JAMMU | JAMMU AND KASHMIR | 180015 | ₹44.8 L+₹4.8 L (12.0%) | L5 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹47.5 L
EMD Value
₹95,000
Closing Date
19 Jun 2025, 6:00 pmClosed
GE NAGROTA
GE NAGROTA
SPECIAL REPAIR REPLACEMENT OF LT OH CONDUCTOR TO UG CABLE FOR PERIMETER SECURITY LIGHTS UNDER GE NAGROTA
2025_MES_703999_2
CANO GEN-02/2025-2026
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
NAGROTA
Class D Cat b (i)
8 documents required · 8 mandatory
₹500
GE NAGROTA
₹95,000
Yes
31 Jul 2025
31 May 2025
26 Jun 2025
31 May 2025
19 Jun 2025
7 Jun 2025
Amount
Excavation in trenches in any type of soil not exc 1.5 mtr in depth and 1.5 mtr wide and getting out for laying of cables complete all as specified.
Returning and filling in including spreading, leveling , watering and well ramming in layers not exceeding 25 cm thick excavated earth complete all as specified and directed.
Removal of surplus soil to a distance not exceeding 50 mtr and depositing at a leval not exceeding 1.5 mtrs above the starting point complete all as specified and directed.
Supply and fix DWC pipe for cable protection with outer dia 50 mm and inner dia 38 mm including suitable size of coupler for connection of pipe complete all as specfied and directed. Note : Pipe are manufactured as per IS 16205 ( Part-24) have a smmoth internal surface and corrugated external surface for cable protection
Supply and fix DWC pipe for cable protection with outer dia 40 mm and inner dia 32 mm including suitable size of coupler for connection of pipe complete all as specfied and directed . Note : Pipe are manufactured as per IS 16205 ( Part-24) have a smooth internal surface and corrugated external surface for cable protection
Supply, laying, testing and commissioning aluminium conductor, XLPE insulated,PVC inner sheathed, GI strip or wire armoured and overall PVC sheathed ,heavy duty 1100 volts grade in trenches/on surface of wall/ in DWC pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc of cross-sectional area 95 Sqmm 3.5 core complete all as specified and directed .
Supply, laying, testing and commissioning aluminium conductor, XLPE insulated,PVC inner sheathed, GI strip or wire armoured and overall PVC sheathed ,heavy duty 1100 volts grade in trenches/on surface of wall/ in DWC pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc of cross-sectional area 35 Sqmm 3.5 core complete all as specified and directed .
Supply, laying, testing and commissioning aluminium conductor,XLPE insulated,PVC inner sheathed, GI strip or wire armoured and overall PVC sheathed ,heavy duty 1100 volts grade in trenches/on surface of wall/ in DWC pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc of cross-sectional area 25 Sqmm 4 core complete all as specified and directed .
Supply, laying, testing and commissioning aluminium conductor, XLPE insulated,PVC inner sheathed, GI strip or wire armoured and overall PVC sheathed ,heavy duty 1100 volts grade in trenches/on surface of wall/ in DWC pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc of cross-sectional area 16 Sqmm 4 core complete all as specified and directed .
Supply, laying, testing and commissioning aluminium conductor, XLPE insulated,PVC inner sheathed, GI strip or wire armoured and overall PVC sheathed ,heavy duty 1100 volts grade in trenches/on surface of wall/ in DWC pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc of cross-sectional area 16 Sqmm 2 core complete all as specified and directed .
Supply, laying, testing and commissioning aluminium conductor, PVC insulated,PVC inner sheathed, GI strip or wire unarmoured and overall PVC sheathed ,heavy duty 1100 volts grade in on surface of wall/ in DWC pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc of cross-sectional area 16 Sqmm 4 core complete all as specified and directed .
M& L for Steel tubular swaged pole type 410 SP-31 (09 mtr long) with 300x300x6mm mild steel plate continuously welded to pole , finial taper plug, bolts, nuts and screws complete all as specified and directed including painted with black bituminous paint internally and externally with anti corrosive paint in alternate black and white strips 30 cm each up to 1.5 mtr height from top edge of concrete and remaining pole with two coats of aluminium paint over a coat of red oxide primer including writing the number etc complete all as specified and directed by Engineer-in-charge. Note: Excavation and Earth work, PCC in foundation and coping shall be measured and paid separately.
M&L for PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in foundation, filling and mass concrete in foundatin of pole/stay, complete all as specified and as directed.
M&L for PCC 1:2:4 type B-1, (using 20 mm graded crushed stone aggregate) as in copying above ground level around the pole, complete all as specified and directed.
Supply,fixing,commissioning & testing of Feeder piller box out door type ‘factory made’ made out from 16 SWG MS sheet supported with legs of 45cm long made of iron angle 25x25x4mm thick of size 75cm x60cm x45 cm with 04 Nos aluminium bus bar of 200 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement, with MCCB FP 160 Amp, 25 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge Note:- Feeder pillar box shall be mounted on brickwork in CM 1:4 not less than 60 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
Supply, fixing,commissioning and testing of outdoor cubical type LT Feeder piller box as per CPRI approved, IP-54 Protection for outdoor shell suitable for 415V,3 phase, 4 wire 50Hz, AC supply system fabricated from CRCA powder coated totally enclosed,Dust,Weather & vermin proof, 3.15 mm thick for outer shell having TPN aluminium busbar mounted in porcelin insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement and provn for incoming and outgoing cables with suitable glands including control wiring with minimum 2.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB, Powder coated complete all as specified and directed by Engrineer-in-Charge. Note:- Feeder piller box shall be mounted on 50x50x6 mm thick angle iron embedded in PCC 1:2:4,type B-I (Using 20mm gradewd stone aggregate) 30 cm deep and 45 cm above ground level. Danger notice plate should also be mounted on panel. angle iron shall be painted with two coat of synthetic enameled paint over a coat of red oxide primer)
(a) Onload Change over switch 200 Amp 4 Pole - 01 Nos.
(b) Aluminium bus bar 300 Amp TPN - 01 Set
(c) Digital Multifuntional meter Showing V,I, PF , HZ etc with suitable CT ratio
(d) Indicator lamp LED type (RYB) complete - 01 set
(e) MCCB 4 Pole, 160 Amp, 35/36 KA,Adjustable Thermal & Adjustable Magnetic setting Ics = 100% of Icu - 02 Nos.
S&F of 60 W LED Street Light luminaire confirmining including all necessary arrangement for fixing on Pole made up SITC of high quality integrated LED street light with a miniumum system lumen of 6600 Lm and system wattage not exceeding 60 W with nominal efficiency 110 lumen/Watt. CCT of 5700K with SDCM of <5 and CRI>70. The houing should be of non- Corrosive high -pressure die cast aluminum with heat resistant toughened clear glass to with stand extreme environments with PF>0.95. Life time of 50K Hrs @L70. The ingress protection should be minimum IP 66 with IK rating of 07. The luminaire should have 5 KV internal 10 KV external surge protection in the luminaire complete all as specified and directed by Engr in Charge.
S&F of 120W LED Flood Light luminaire made up of Matt black ptextured powder coated pressure Die Cast aluminum housing and frame with heat resistant toughened clear glass fixed with SS screw/ Ant dust exposed lens, sturdiness and embossed brand name/ logo name of manufacturer on fixture . The luminaire should have a minimum system lumen output of 14400 lumens and 120 Watts. The fixture shall have a CRI of minimum 70. The fixture shall be designed for a sysytem life of 50000 hours @ 70 % lumen maintenence , Ingress protection of IP 66 (lamp and gear compartment ) and Mechanical impact resistance ratinfg of IK>=07. The fixture driver should have an operating voltage range of 120-277V, surge protection of internal 4 KV amd external surge protection of 10 KV, PF.0.95, THD<10%. complete all as specified and directed by Engr in- Charge.
M&L for earthing complete with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters below ground level) with top edge of earth plate not less than 1.5 meters below ground level connected to galvanized earth wire 4.00 mm dia by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, PCC (concrete chamber of size 300 mm x 300 mm x 300 mm inside dimension) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish , internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire mesh of 22 gauge, 80 mm thick PCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI pit shall be filled with charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) as specified including provision of 15mm dia light grade GI pipe for earth wire protection and 20 mm dia for watering complete , all excavation and earth work & connecting the earthing to an earthing test point / main switch board as specified and testing on completion complete.
M & L for Earthing complete with galvanised mild steel earth plate electrode 60cmx60cmx6mm thick, burried directly in ground preferably in vertical position (Earth pit not less than 2.25 mtr below ground level) with top edge of the earth plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 25×4 mm by means of bolts, nuts, check nuts and washers of galvanised iron including pit of PCC (1:2:4) type B-1, pre cast RCC cover slab of size 550x550x75mm, XPM reinforced not less than 1.60Kg/Sqm with suitable built in handle made from 12mm dia MS round bar, excavation and earth work in any type of soil, 20mm dia bore medium grade galvanised iron water tubing fixed with cast iron funnel and wire mesh at one end, 15mm bore light grade galvanised iron protection pipe for earth lead wire upto 5m length, charcol, common salt complete all as shown in electric plate No 5 of SSR 2009 Part I connected to equipment, complete all as specified and testing on completion all as directed.
Dismantling cross arms of M.S. channel or angle sections , stay wire etc. complete all as specified and directed .
Dismantling insulators any type, any size complete all as specified and directed .
Dismantling ACSR conductor any type any size complete all as specified and directed .
Dismantling and taking down of street light fittings of any wattage or any size including GI bracket with all accessories and refixing the same street light on old LT pole/ new pole complete all as specified and directed. Note : The Contractor should fix the clamp as per site requirment.
M&L for route indicator including excavation and other civil work made out of PCC Solid block type B1 1:2:4 using 20 mm graded aggergrate set in cement Mortar 1:4 of size 30x45 cm above ground level and 25 cm below ground level for LT cable mentioning the size of Cable with paint on PCC block as per direction by Engr-in - charge complete all as specified and directed.
M & L for Cutting of Road / Nalla/ Temp trench up to 6 mtr to 8 mtr in width and min 1.5 mtr in depth for passing pipe line and making good the distrubed road/nalla /temp trench including resurfacing / plastering with PCC of suitable type comlplete all as specfied and directed
M&L for three core Copper wire FRLS insulated cable 2.5 Sqmm with and drawn through pole from junction box to street light connection including PVC conduit pipe 20 mm Dia, complete all as specified and directed
S&F Mounting arm for installation of LED light made from 1.5"(40mm) GI pipe light grade(B class) of total length 2 mts (to be fabricated as per approved design), to be supplied alongwith mounting clamps-02 Nos,fabricated from (65mm x 5mm)MS providing 04 no Nut Bolt washer including with suitable size ofclamps , nuts bolts etc complete all as specified & directed.Note : The Contractor should fix the clamp as per site requirment.
Supply & fix hot Press moulded junction box of size 400mmx300mmx 190mm hinged type including 04 No aluminium Bus Bar of suitable capacity with fixing arrangement like suitable size clamps, Nuts, bolts and washers etc and including SP MCB 6 Amps clamped with Pole complete all as specified and directed.
M/S JIWAN SINGH (BID ID -3329251)
slathia construction works (BID ID -3320883)
PROACH ASSOCIATES BUILDERS & ENGINEERS (BID ID -3321384)
MAMTA ENTERPRISES (BID ID -3329765)
kailu construction co (BID ID -3321364)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .