Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.7 LAccepted-AOC | L1 | Accepted-AOC Lowest and Reasonable | |
| 2 | L2₹30.2 L+₹1.5 L (5.28%)Rejected-Finance | L2 | Rejected-Finance Other than Reasonable | |
| 3 | L3₹30.9 L+₹2.2 L (7.65%)Rejected-Finance | L3 | Rejected-Finance Other than Reasonable | |
| 4 | L4₹34.4 L+₹5.7 L (19.8%)Rejected-Finance AT ROAD MES TINALI PO CHABUA DISTT DIBRUGARH ASSAM 84 | CHABUA | DIBRUGARH | ASSAM | 786102 | L4 | Rejected-Finance Other than Reasonable |
Tender Value
Refer Docs
EMD Value
₹55,000
Closing Date
18 Jun 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) JORHAT
HQ CWE (AF) JORHAT, ROWRIAH, ASSAM - 785005
WORK SERVICES FOR CREATION OF FSP AND OTHER RELEATED INFRASTRUCTURE AT AF STN JORHAT UNDER GE (AF) JORHAT
2021_MES_436936_2
83917/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) JORHAT
Please refer Tender documents
5 documents required · 5 mandatory
₹500
Yes
GE (AF) JORHAT
₹55,000
Yes
1 Jul 2021
28 May 2021
24 Jun 2021
28 May 2021
18 Jun 2021
4 Jun 2021
60 days
Amount
Excavation over areas not exc. 1.5 metres deep and getting out for foundation/ taking out and laying of cables etc. in soft/ loose soil complete all as specified and as directed.
Material and labour for sand filling under floors or in foundations including watering and consolidation complete all as specified and as directed.
Removing of excavated material (soil) to distance not exc.50metres and deposited where directed at a level not exc.1.5 metre above the starting point complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick with soils complete all as specified and as directed.
Excavation in trenches not exc. 1.5 m wide and not exc. 1.5 m in depth for foundation etc. or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. and getting out in soft/ loose soil complete all as specified and as directed.
Material and labour for PCC (1:3:6) type C-2 (using 40 mm graded broken stone aggregate) as in foundations, filling and mass concrete all as specified and as directed.
Material and labour for formwork to sides of concrete foundations, footings, bases of column, raft and raft beams, side and soffit (if any ) of foundation and plinth beam and similar works, vertical or batter etc for rough finished flat surfaces of concrete complete all as specified and directed.
Material and labour for RCC (design mix) M-25 (using 20mm graded broken stone aggregates) as in foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, complete all as specified and as directed.
Material and labour for formwork to sides of pillars, posts, struts, columns and stanchions, square, rectungular or polygonal for fair finished surfaces of concrete complete all as specified and as directed.
Material labour for RCC (design mix) M-25 (using 20mm graded broken stone aggregates) as in columns, pillars, piers,posts and struts complete all as specified and as directed.
Material and labour for mild steel TMT bars 10 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns,hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.
Material and labour for mild steel TMT bars, 6mm dia and over upto and including 10mm dia as in stirrups, spacers and binders , cut to length, bent to shape required, including cranking, bending spirally for hooping for columns,hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia. or securing with clips complete all as specified and as directed.
Supply and fix for mild steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I.S.1161-1979 grade St.-240 complete all as specified and as directed.
Supply and fix for rolled mild steel roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat sections) including distance pieces, cleats etc. conforming Fe 410-W(Gde-E-250) quality -B complete all as specified and as directed.
Material and labour for mild steel Fe 410-W(Gde-E-250) quality-B in plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment complete all as specified and as directed.
Supply and fix for bolts 20mm dia neck purpose made with hexagonal or square head one end and screwed the other or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut exc. 30 cm long complete all as specified and as directed.
Supply and fix for 0.50mm thick (Arch shape) pre-painted galvalume aluminium zinc coating (AZ-150) GI based corrugated steel sheet of any colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall fixed with self tapping screws with two corrugation side lap complete all as specified and as directed.
Material and labour for preparation of new steel or iron surfaces of any description over 10cm width or girth not otherwise described and applying two coats of synthetic enamel paint over a coat of zinc chrome red oxide primer complete all as specified and as directed.
Surface excavation not exc. 30 cm deep and averaging 15 cm deep and getting out in soft/ loose soil complete all as specified and as directed.
Removing excavated soils to distance exc.250 metres but not ex.500 metres and depositing where directed at a level not exceeding 1.5 metre above the starting point all as specified and as directed.
Bringing approved earth from outside Ministry of Defence (MOD) land and deposited where directed including forming embankments and including raising (or lowering) earth, spreading in layers n.exc. 30 cm thick, watering, ramming/ rolling and finishing to required size, shape etc not exc 1.5m high from base complete all as specified and as directed. Notes:- (i) Payment shall be made for net quantity after compaction, work out on the basis of initial levels and finished levels as specified. (ii) Sample of earth to be brought in shall be got approved by GE in writing by the contractor before bringing in the earth required under this item.
Rolling and consolidating of formation surfaces in cutting to the required gradient and camber including filling depression and hollow watering , leveling etc. using 8 to 12 tonne power roller to achieve 98% MDD of OMC complete all as specified and as directed.
Material and labour for 150 mm thick soling (or sub base) with broken boulders or quarried stone, inter stices filled, surface formed and rolled and consolidated to required gradient and camber complete all as specified and as directed.
Material and labour for 150 mm thick PCC (1:4:8) type D2 (using 40mm graded broken stone aggregate) as in sub base complete all as specified and as directed.
Material and labour for 80 mm thick machine pressed precast concrete interlocking paver block M-40 grade any shape and size confirming to IS 15658-2006 including 50 mm thick sand filling under floors or in foundation including watering and consolidation complete all as specified and directed.
Material and labour for broken stone (granite/ basalt) hard core of gauge n.exc 63mm deposited, spread and leveled in layers not exc 15cm thick, watered and rolled, rammed to a true surface complete all as specified and as directed.
Material and labour for 75mm thick PCC (1:3:6) type C2 (using 40mm graded crushed stone aggregates) as in plinth protection finishing the surface even and smooth without using extra cement complete all as specified and as directed.
Material and labour for PCC (1:3:6) type C2 (using 40mm graded broken stone aggregates) as in surface channel and drain complete all as specified and as directed.
Material and labour for 150mm bore RCC pipes, class NP3 laid and jointed in cement mortar complete with collars and tested complete all as specified and as directed.
Material and labour for point wiring for flame proof using approved colour coding as per IS, with multistranded FRLS copper conductor 1.5 Sq. mm (nominal area), two single core PVC insulated and unsheathed multistranded cable 1100 volts grade ISI-694 marked through and including 20mm dia stove enemelled steel heavy duty conduit and all conduit accessories, ISI marked, fixed to roof, ceiling/ wall etc, including PVC insulated multistranded unsheathed FRLS copper conductor 1.5 Sqmm (nominal area) single core cable as earth continuity conductor and fixed to flame proof type switches for one light point controlled by one, one way switch 5 Amps complete all as specified and as directed.
Supply and fix for LED frame proof batten, suitable for single and twin T8 tube of 16/ 20 Watts with all accessories prewired and including making electrical connection all as per Cat Part No. EXTN2LT8-16/20 of make Crompton or equivalent model in make Bajas/ Philips as approved by GE complete all as specified and as directed.
Supply and fix for LED glass T8 tube 20 Watts suitable for flame proof tube light fitting all as per Cat Part No. LGT8-20-865-2 of make Crompton or equivalent model in make Bajas/ Philips as approved by GE complete all as specified and as directed.
Supply and fix for FLP WP rotary switch with cable terminal box LM-6 material single pole, on and off 16 Amps complete all as specified and as directed.
Supply and fix for sheet metal enclosure MCB DB SPN 8 way with 200 Amps rated bus bar 240 volts double door with magnetic locking system and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed.
Supply and fix for MCB SP rated capacity 6 to 32 Amps, 240 Volts breaking capacity 10 KA 'C' series complete all as specified and as directed.
Supply and fix for MCB TPN rated capacity 32 Amps, 415Volts breaking capacity 10 KA 'C' series complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning LT XLPE under ground cable1100 volts grade, XLPE insulated screened PVC bedded, galvanised steel strip or armoured and sheathed with aluminium conductor heavy duty electric cable including cable glands, lugs, jointing materials etc laid in trenches/ floors/ ducts of cross sectional area 10 Sqmm, 4 core complete all as specified and as directed. Note: Earth work and excavation shall be measured and paid seperately under relevant item.
Material and labour for dry river sand as in sand cushioning in trenches/ ducts for protection of underground cable (below, above and around the UG cable laid in trenches) of 23 cm spread thickness ( 8 cm in depth before laying the cable and 15 cm in depth after laying the cable) and consolidated (punned) up to 18 cm thickness complete all as specified and as directed. Note : - Thickness after punning shall be measured for payment
Material and labour for sub class 'B', old size bricks for cable protection cover, common burnt clay building bricks, laid dry and flat abutting each other with width equal to length of brick and gap between adjacent bricks not exc.10mm complete all as specified and as directed.
Supply and fix for single pointed air termination aluminium rod 12mm dia 300mm long complete all as specified and as directed.
Supply and fix for GI pipe medium grade 25mm dia ISI marked duly grouted on the roof for fixing air terminals including nut and bolts as per IS 2309 complete all as specified and as directed.
Supply and fix for aluminium strips 25mm X 3.15mm complete with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and as directed.
Material and labour for earthing complete with copper earth plate electrode 600 x 600x 3.0 mm thick buried directly in ground (earth pit not less then 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to copper earth lead strip 20 X 3mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel and connected to neutral of transformer as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm including 8mm dia TMT bars @ 100mm centre to centre both way with one handle for lifting made out of 10mm dia MS bar, funnel, wire mesh, 20 mm bore galvanized steel tubing (medium grade) for watering, filling charcoal or coke and salt in alternate layers, 40mm bore galvanized steel tubing light grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing complete all as shown on electrical plate No.3 of SSR Part-I . (Note: Copper earth strip and protection pipe upto 7.5metres shall deem to be included in the quoted rate)
Supply and fix for thermoplastic weather proof emty box (IP 65) with plain wall of size 200mm X 140mm X 95mm, fix on wall with provision of nut, bolts, washer etc including fixing of test point terminal block inside the box which made out of gun metal or phosphorous bronze of size 75 X 75 X 25 mm, drilled and screwed including 3 Nos 8 mm dia, 25 mm long hexagonal head screws complete all as specified and as directed.
Chief Builders &Consultants
M/S AT DHAR AND CO
M/S R G Construction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .