Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical | Accepted-Technical Accepted |
| 2 | Accepted-Technical | Accepted-Technical Accepted |
| 3 | Not Admitted-Fee/PreQual/Technical 103 SECTOR 16 DEEN DAYAL PURA AWAS VIKAS COLONY SIKANDRA AGRA | AGRA | AGRA | UTTAR PRADESH | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹32.1 L
EMD Value
₹64,500
Closing Date
27 Nov 2025, 6:00 pmClosed
Executive Engineer (West), UPSRT Lucknow
Executive Engineer (West), U.P State Road Transport Corporation, Lucknow
Providing and installation of 1000KVA capacity Transformer, Cable work, Earthling and allied services for opportunity Electric Bus Chager at Bus Station Alambagh, Lucknow, U.P.
2025_UPSRT_1092262_1
1095/B/DA/W/Tender/2025
Open Tender
Civil Works
Percentage
90 days
Alambagh
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,360
Executive Engineer (West), UPSRT Lucknow
₹64,500
16 Dec 2025
19 Nov 2025
28 Nov 2025
19 Nov 2025
27 Nov 2025
19 Nov 2025
Supply, Installations, Testing & Commissioning of 11kV HT PANELS Indoor type 1 panel board, 1 I/C 630 Amps, 11 KV, 3 phase, 25 KA for 1 sec. Vacuum circuit breaker including two bus PT with all necessary protection, metering and other accessories complete in all respect.as per the directions of the Engineer-in-charge Complete in all respects as per direction of the Engineer-in-charge.
Supply,installation,testing & commissioning of Outdoor type distribution transformer 1000KVA 11KV/433V Dyn11 Copper Wounded ONAN Type Transformer with Off load tap links of +5% to -5% @ step of 2.5%. Class of Insulation: A, Temperature rise 90 deg.C. over ambient temp of 50 Deg C. Losses IS 1180 level 2 losses ) , % Impedance - 4.5% ( IS Tol) with Surge Arrester on HT side. Whose GTP Approved in MVVNL having valid CPRI/ERDA type test report]
Providing Plinth for 1000 KVA out door type Transformer of size approx 3.0 x3.0x 0.90 mtr with outer wall foundation depth 0.75 M, base concrete cement concrete 1:3:6 (1 cement : 3 coarse sand :6 graded stone aggregate 40 mm nominal size), 0.35 m thick Brick work wall 1:4 cement & coarse sand mortar, Plinth filled with local sand and top covered 0.10 m thick base cement concrete 1:3::6 (1 cement : 3 coarse sand :6 graded stone aggregate 40 mm nominal size), with 0.15 m thick RCC slab 1:1½:3 (1 Cement, 1½ coarse sand and 3 graded stone aggregate 20 mm nominal size) with 1 % reinforced including all from work etc. as per drawing & specification as per direction of EI..
1.5 M height Fencing with angle iron post placed at 1.50 mtr distance embedded in cement concrete blocks and provided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire or equivelent between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. i/c Cost of posts, struts, earth work and concrete work as per drawing & specification as per direction of EI.
Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Supply and fixing of H.T. Danger notice plate of 250x200mm made of mild steel at least 2mm thick and vitreous enameled white on both side with inscription in signal red colour on front side as required.
Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc., 400 sq. mm 3-1/2 core
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 400 sq. mm 3-1/2 core
MAIN LT PANEL Incomer 2000 A, ACB, 4 Poles, Fixed Manual, 50 KA, Motorised based release for O/C,S/C,ST,UV & E/F Protection On, OFF, TRIP lamps -MFM 2000/5A,CL0.2,2.5VA Outgoing 400 Amp. 35KA TPN MCCB 4 No.INSTRUMENTS 1 set of multifunction of meter with RS 485 port. 1 set of multifunction of meter with RS 485 port. 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). 1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker). 3 Sets auto trip indicating lamp . Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.46 MB
Tender_documentsAlambagh123.pdf
Tender Documents • 0.95 MB
BOQ_2006790.xls
BOQ • 3.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .