| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.7 LAccepted-AOC 9 EZRA STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L1 | Accepted-AOC being L1 | |
| 2 | L2₹36.5 L+₹1.5 L (4.31%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹37.0 L+₹2.0 L (5.72%)Rejected-Finance | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹41.8 L+₹6.8 L (19.4%)Rejected-Finance | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹42.0 L+₹7.0 L (20.0%)Rejected-Finance | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹32 L
EMD Value
₹64,000
Closing Date
26 Dec 2022, 6:00 pmClosed
GE Minniebay
Junglilghat PO Port Blair Andaman and Nicobar Islands
ADDN ALTN OF MT STORE NEAR T-12 BLDG MINNIE BAY AND PROVN OF 100 KVA DG SET MOUNTED ON SINGLE TRAILER FOR RPA OPERATION AT UTKROSH UNDER GE MINNIE BAY
2022_MES_552641_4
8177/E8
Open Tender
Civil Works
Item Rate
180 days
GE Minniebay
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE Minniebay
₹64,000
Yes
9 Feb 2023
13 Dec 2022
29 Dec 2022
13 Dec 2022
26 Dec 2022
20 Dec 2022
Amount
Demolition of Cement Concrete of any description and in any position not otherwise specifically provided for complete all as specified and as directed by Engr-in-Charge.
Demolition of precast concrete block walling built in Cement Mortar including all quoins arches pillars etc complete all as specified and as directed by Engr-in-Charge.
M&L for dismantling of wrought iron or mild steel work of any description not otherwise provided for complete all as specified and as directed by Engr-in-Charge.
Dismantling of plain or corrugated steel sheeting any gauge thickness or similar pattern roof coverings complete all as specified and as directed by Engr-in-Charge.
Excavating in soft/loose soil not exceeding 1.5 m wide and not exceeding 1.5m in depth and n exc 10 sqm on plan complete all as specified and as directed by Engr-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed by Engr-in-Charge.
Removing surplus excavated material n exc. 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed by Engr-in-Charge.
M&L for Plain Cement Concrete 1:4:8 type D2 (nominal mix) using 40mm graded stone aggregate as in foundation, filling & mass concrete complete all as specified and as directed by Engr-in-Charge.
M&L for formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits of foundation and plinth beams, and similar work for rough finished flat surfaces complete all as specified and as directed by Engr-in-Charge.
M&L for Formwork to sides of pillars, posts, struts, piers, columns, and coping beam stanchions complete all as specified and as directed by Engr-in-Charge.
M&L for form work in lintel beams and roof beams of rough finished concrete surfaces complete all as specified and as directed by Engr-in-Charge.
M&L for Reinforced Cement Concrete M-30 grade (Design Mix) using 20mm graded stone aggregate as in foundations including rafts, footings, foundation beams, plinth beams; bases for coloumns, etc basement slabs, under-reamed piles and mass concrete complete all as specified and as directed by Engr-in-Charge.
M&L for Reinforced Cement Concrete M-30 grade (Design Mix) using 20mm graded stone aggregate as in columns, pillars, piers, post and struts etc., complete all as specified and as directed by Engr-in-Charge.
M&L for Reinforced Cement Concrete M-30 grade (Design Mix) using 20mm graded stone aggregate as in beams, cantilevers, bressummers, coping, lintel over 1.5m span etc complete all as specified and as directed by Engr-in-Charge.
M&L for Mild steel TMT bars 10mm dia and over cut to length, bent to shape required incl cranking, bending, spirally for hooping for columns, hooking end and binding with and incl mild steel wire not less than 0.9mm dia or securing with clip quality confirming to deformed or twisted bars complete all as specified and as directed by Engr-in-Charge.
M&L for Mild steel TMT bars 5mm dia and over upto and including 10mm dia, as in stirrups cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with the including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed by Engr-in-Charge.
M & L for 100 mm thick Plain Cement Concrete 1:3:6 type C-2 (nominal mix) using 20 mm graded stone aggregate as in sub base etc complete all as specified and as directed by Engr-in-Charge.
M & L for 40 mm thick Plain Cement Concrete 1:2:4, Type B-1 (nominal mix) using 20mm graded aggregate as in Sub base for flooring/levelling coarse etc complete all as specified and as directed by Engr-in-Charge.
M&L Mild steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to IS.1161- 1979 grade St.-240 complete all as specified and as directed by Engr-in-Charge.
S & F Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment confirming to Fe-410 W (Grade E-250) quality A complete all as specified and as directed by Engr-in-Charge.
S & F mild steel screw bolts (machine made) of any dia with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exc 5cm but n.exc10 cm long complete all as specified and as directed by Engr-in-Charge.
M&L for preparation of new steel or iron surfaces of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed by Engr-in-Charge.
S&F pre-painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified complete all as manufacturer's instruction and as directed by Engr-in-Charge
S&F pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550Mpa as in roof covering/cladding to wall, fixed with self tapping screws as in ridges, hips, valley gutter, drip, and straight flashing complete all as specified and as directed by Engr-in-Charge.
S&F Aluminium wind ties for roof including all necessary drilling, bolting or rivetting fixed with GI self tapping screws for roof sheeting complete all as specified and as directed.
S & F anodized aluminium grid work 605 x 605 mm with using 36.5mmx23.5mmx1.5mm thick main tee, 23.5 x23.5mmx1.28mm cross tee and 25x25x1.5mm angles fixed to perimeter of wall for false ceiling including hangers 6 mm dia. G.I. (upto 1200mm length) adjusting level fixed to roof by means of ceilling cleats made out of G.I. flat 40 x 3 mm size 60mm long and expansion hold fasteners 12.5mm dia. 40mm long including 4mm thick Non asbestos fibre cement building boards fixed or laid / inserted to timber/ GI/aluminium framework with screws including preparation of surfaces and applying two coats of oil emulsion distemper over a coat of primer complete all as specified & directed all as specified & directed
M&L for aluminium anodised frame for doors, windows, ventilators and partition with one or more rebates including joining cleat for fixing etc. complete all as specified and as directed by Engr-in-Charge.
S&F anodised aluminium door shutters, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified
S & F anodised aluminium window and ventilator shutters, side hung type without sash bars, aluminium sections weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws, anodised aluminium fittings such as peg stays 150mm long (1 no.). hinges type B-21 100mm long (2 no.) suitable handle (1 no.) complete all as specified by Engr-in-Charge.
S & F 4 mm Plain sheet glass ordinary quality, in square not exc 0.5 sqm each complete all as specified and as directed by Engr-in-Charge.
S & F 4 mm Plain sheet glass ordinary quality, in square exc 0.5 sqm each complete all as specified and as directed by Engr-in-Charge..
S&F 12mm thick prelaminated particle board, interior grade, prelaminated on both sides lamination fixed as in panels of aluminium door shutters, partition etc complete all as specified and as directed by Engr-in-Charge.
S & F aluminium alloy wire cloth, 0.45mm nominal dia of wire and average width of aperture 1.40mm and fixed with aluminium wire staples complete all as specified and as directed by Engr-in-Charge.
M&L for Non skid joint free coloured ceramic tiles 7 to 8mm thick (Square/rectangular) area of each tile exceeding 0.18 but not exceeding 0.38 Sqm, in floors etc. set and jointed in neat cement slurry over & including 15mm thick screed bed in CM 1:4 and pointed in white or coloured cement to match complete all as specified and as directed by Engr-in-Charge.
M&L for Glazed Ceramic tiles 450x300x 8-10 mm thick in vertical surface set and jointed in neat cement slurry and pointed in white or colour cement to match over 10mm thick backing in cement mortar (1:3) complete all as specified and as directed by Engr-in-Charge.
M&L for precast cement concrete block masonry with solid block , exc 10 cm in width in PCC type C-1 ,1:3:6 using 20 mm graded stone aggregate set in CM (1:6) complete all as specified and as directed
Taking down Cement Plaster of any description on brick or stone walls or concrete surfaces, ceiling including raking out joints, hacking for key, scrubbing down with water etc complete all as specified and as directed by Engr-in-Charge.
M & L for 10mm thick in CM1:6 rendering to concrete or block masonry surfaces or surfaces other than fair faces of brick surfaces, surfaces finished even and smooth without using extra cement complete all as specified and as directed by Engr-in-Charge.
M & L for rendering 5 mm thick in cement mortar 1:4 over a backing coat of 10mm thick in CM 1:6 (Total 15 mm thick) on concrete or brick masonry surfaces including mixing water proofing compound as per manufacurer's instructions and finishing the top surface even and fair complete all as specified and as directed by Engr-in-Charge. Note: Water proofing compound shall be measured and paid separately under relevant item of this schedule as 'Supply only'
Supply only Integral water proofing compound ISI marked complete all as specified and as directed by Engr-in-Charge.
M&L for preparation of newly plastered surfaces of wall and applying two coats of oil emulsion distemper over a coat of primer complete all as specified and as directed by Engr-in-Charge.
M & L for complete removal of existing treatment on wall, finishing the surface and applying two coats of oil bound distemper over a coat of primer complete all as specified and as directed by Engr-in-Charge.
M&L for preparation of newly plastered surface and applying two coats of exterior emulsion weather coat premium quality matt finish antifungal paint over a coat of primer complete all as specified and as directed by Engr-in-Charge
M&L for complete removal of existing treatment and applying two coats of exterior emulsion weather coat premium quality matt finish antifungal paint over a coat of primer complete all as specified and as directed by Engr-in-Charge
M&L for hard core of gauge n.exc. 63mm deposited spread and levelled in layers n.exc. 15 cm thick watered and rolled / rammed to a true surface complete all as specified and as directed by Engr-in-Charge
M&L for 100mm thick plain cement concrete 1:2:4 type B-1 (nominal mix) using 20 mm graded stone aggregate as in floors sub base complete all as specified and as directed by Engr-in-Charge
M&L for heavy duty chequered cement concrete tiles 30cm x 30cm x 25 mm thick, set, jointed and pointed in near cement slurry in floors with grey cement and pigments and including screed bed 15mm thick CM 1:4 complete all as specified and as directed by Engr-in-Charge
M & L for 75mm thick plain cement concrete 1:3:6 type C-2 (nominal mix) using 20 mm graded stone aggregate as in sub base, plinth protection etc., complete all as specified and as directed by Engr-in-Charge
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc removing materials to store for keeping in safe custody or against schedule for credit and making good disturbed surfaces of walls, floors, etc complete all as specified and as directed by Engr-in-Charge
M&L for point wiring with 1.5 Sqmm (nominal area) PVC FRLSH unsheathed multi stranded copper conductor PVC insulated 1100 volt FRLS grade single core cable drawn through concealed/surface and including rigid steel conduit medium grade ISI marked minimum 25mm size and its accessories complete along with 1.5 Sqmm cable but in green colour as continuous earthing wire and connecting to common earth dolly completely concealed ,ceiling/roofs with and including 1.2 mm thick MS sheet terminal boxes duly fabricated flush mounting in the wall for mounting switches,switch socket combinations fan regulators etc., as required with 3 mm CRCA sheet metal enclosure box as per required size complete all as specified and as directed by Engr-in-Charge for the following:-
One light /fan point controlled by one switch complete all as specified and as directed by Engr-in-Charge.
One switch socket 5 pin 5/6 Amp flush type on independent board complete all as specified and as directedby Engr-in-Charge..
One switch socket 5 pin 5/6 amps flush type on same board complete all as specified and as directedby Engr-in-Charge..
All as per item No 50.00 above but with 2.5 Sqmm PVC FRLSH single core multi stranded unsheathed copper conductor for one 5 Pin 15/16 Amps socket on independant board including continuous earth wire complete complete all as specified and as directedby Engr-in-Charge.
All as per item No 50.00 above but with 2.5 Sqmm PVC FRLSH single core multi stranded unsheathed copper conductor for security light point controlled by one switch/MCB complete all as specified and as directedby Engr-in-Charge.
S&F switch piano flush type single pole 230V, 5/6 amps complete all as specified and as directed by Engr-in-Charge
S&F switch socket outlet 3 Pin 5/6 amps flush type single pole 230V complete all as specified and as directed by Engr-in-Charge
S&F switch socket combination flush type multi purpose 5A/16A 5in1 controlled by one switch, 230V complete all as specified and as directed by Engr-in-Charge
S&F PVC ceiling rose surface type 50mm dia, three terminals including PVC mounting block complete all as specified and as directed by Engr-in-Charge
S&F in repairs building security light of 25w controlled by MCB of IP 66 with path lighting luminaries with high Power LED complete all as specified and as directed. Note : MCB shall be measured and paid separately under relevent item of this schedule.
M&L in repair for sub main wiring complete with 2 x 1.5 sqmm, single core, multi stranded copper conductor FRLSH PVC insulated and sheathed cable 1100 volts grade, drawn in 25mm enamelled steel conduit on surface/concealed (as required) along walls roofs etc including 1.5 sqmmm size PVC FRLSH insulated unsheathed copper earth continuity conductor to common earth and connecting to earth dolly including taking down old unsv wiring complete all as specified and as directedby Engr-in-Charge. Note : (i) All three wire/cable (phase, neutral and earth) should be run through for each individual circuit from the DBs. (ii) Three runs of cableS and one run of PVC conduit shall be measured as one unit run.
M&L in repair for earthing complete with GI earth electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 meter below normal ground level with top edge of earth plate at a depth not less than 1.5 meter below normal ground surrounded from all sides by 15 CM thick and packed layer of charcoal dust and common salt filling in alternate layers cleaned connected to and including GI earth strip 25 x 4 mm size up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected light grade 20 mm bore for watering and including funnel wire mesh, RCC pit cover 50 mm thick and PCC chamber pit with PCC 1:3:6 type C-2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 meter) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 complete all as specified and as directed by Engr-in-Charge
S&F in replacement sheet metal factory made double door, powder coated MCB DB 4 way with bus bar 400 Amps , Neutral link , Earth bar , double door type TPN, 240v complete all as specified and as directed by Engr-in-Charge
S&F in replacement sheet metal factory made double door, powder coated MCB DB 8 way with bus bar 200 Amps , Neutral link , Earth bar , double door type SPN, 240v complete all as specified and as directed by Engr-in-Charge
S&F in repair MCB SPN 6-32 Amps, 240 Volt, breaking capacity 10KA complete all as specified and as directed by Engr-in-Charge
S&F in repair MCB SP 6-32 Amps, 240 Volt, breaking capacity 10 KA complete all as specified and as directed by Engr-in-Charge
S&F in repair MCCB four pole 63 Amps, 440 Voltt, breaking capacity 25kA complete all as specified and as directed by Engr-in-Charge
S&F in repair LED tube light fitting, 1x20 w, 230v, surface and wall mounted LED batten, extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver, flicker free, high efficiency and connected batten option & connecting up with twin core twisted flexible copper conductor cable with suitable size all as specified directed by Engr-in-Charge.
Supply & lay and testing of LT cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16.0 Sqmm 4 core including taking down of old unserviceable cable complete all as specified and as directed by Engr-in-Charge
Supply install testing and commissioning of Silent Diesel Engine driven generating set 415 Volt (at 0.8 PF) 100 KVA 3 phase 50 Hz. 1500 RPM with accostic enclosure and canopy type (indoor use) made out of 14 gauge CRCA sheet with inbuilt AMF Panel and including all excavation PCC foundation(as per manufacture), anti vibration pads tamper standard control panel as per manufacture instructions as directed by manufacturer and conforming to latest CPCB norms. The DG set shall comprise of following : - (a) Alternator : Standard design alternator rated at 100 KVA net out put at site, self excited ,self regulated through an AVR, screen protected, revolving field, brushless design with permanent lubricated bearings with winding in each pole, insulation class H, voltage regulation ± 1.5 % of rated voltage 'No load to full load'. The alternator shall be in a position to generate supply with frequency regulation within ± 1 % tolerance and permissible overload of 10 % for one hour in 12 hrs continuous run and conforming to IS 13364. (b) Diesel Engine : Adequate capacity suitable for 100 KVA Alternator water cooled to drive independently the above alternator directly coupled through flexible coupling Six cylinder Four stroke direct injection cold starting 1500 RPM as per relevant IS, IS:10001/ 10002 BS 5514 with in overload capacity of 12hrs continuous running complete with standard accessories all as specified and required for site handling and operation generally the scope of accessories shall be as under :-
(i) Air intake system : Air intake manifold air cleaner. (ii) Exhaust system : Turbo charger SS Flexible bellow silencer complete with MS exhaust piping of minimum size 100 mm dia upto and outside the building covered with glass wool covered under aluminum foil of 28 gauge, adequate to exhaust without transferring vibration to building/walls. (iii) Coolant system : Engine water pump ,radiator with fan and fan belt. (iv) Lubricating system : Oil pump of suitable capacity, lub oil pump and lub oil filter. (v) Fuel system : Fuel injection pump 12/24 Volts (as per OEM recommendation) DC solenoid switch nozzle mechanical/electronic governor, replaceable fuel filter, fuel tank made of 14 SWG sheet with drain valve, air vent inlet and outlet connection, fuel supply piping from tank to pump & to engine including return of over flow fuel with level indicating arrangement duly marked in inches/Litres. Fuel tank should be of adequate capacity for 12hrs running at full load. (c) Starting system : 12/24 V DC self starter 12 V DC battery charging alternator, start & stop push button, ignitor key/ switch, Battery of reputed make of suitable capacity in changed condition with its copper leads of adequate size as per OEM recommendation. (d) Base frame: Common base plate with AVM pads for mounting the engine & alternator. (e) Engine mounted Instrument Panel fitted with and having digital display for following:(i) Start-stop switch with key,(ii) Water temperature indication,(iii) Lubrication oil pressure indication,(iv) Lubrication oil temperature indication,(v) Battery charging indication,(vi) RPM indication,(vii) Over speed indication,(viii) Low lub. Oil trip indication & (ix) Engine Hours indication
(f) Safety control : Lub oil pressure trip, High water temp trip & over speed trip. (g) Acoustic enclosure : Modular construction with the provision to assemble & dismantle easily at site, powder coated & stainless steel nut & bolts/external hardware, provision for filling fuel from outside the enclosure with locking arrangement, Sound proofing of enclosure with high quality rock wool /mineral wool The rock wool is further covered with fiber glass tissue & perforated sheet . A special residential silencer within the enclosure to reduce exhaust noise. Noise level 75 db (A) at 3 m distance. Make :Cummins Model No C100DSP or equivilant makes in Kirloskar/GREAVES/Mahindra (j) The following documents shall be provided with DG set: (i) O & M manual of Diesel Engine spare parts catalogue of Diesel Engine, test certificate of Diesel engine, Test cert of Diesel engine. Test certificate of Alternator, DG set complete. (ii) Standard testing of DG sets shall be carried out with 10 % overload for one hour (iii) All Civil work related to foundation as per manufactures recommendation will be carried out at no extra cost. (iv) Load bank, accessories, fuel required for 12 hours testing is to be provided by contractors will inclusive quoted rate. (v) Repair/Maint tools to be supplied with DG set are as under :- (i) STANLEY 91-931-12-Master Tool set-120 Pieces of Make : STANLEY (ii) Cutting pliers 10 " - 01 No
4. The contractor shall submit the manufacturer drawing of trolley for approval before commencement of actual fabrication. Making/Fabrication shall be carried out only after approval of drawings. 5. All the structural materials shall conform to IS 2062. Materials of reputed make such as VIZAG Steel, TATA Steel, Jindal, SAIL. 6. The trolley handle shall be capable of turning 90° in either direction with minimum turn radius for towing by Vehicle. The design shall take care of easy handling for safe operation. 7. Self-lubricating bush shall be provided for trolley handle. 9. The pin/bolt connecting the Base frame of trolley & handle shall be of hardened steel to prevent rupture under full load condition. 8. Suitable Taper roller bearing of make such as SKF, NTN or equivalent shall be provided at the joint connecting trolley to the handle assembly. 9. The locking arrangement shall be provided to restrict the movement of trolley (either loaded / empty). 10. The locking arrangement of all the wheels to the shaft shall be preferably of threaded type with locknut arrangement to avoid wheel slippages.
11. The trolley shall be well protected against rust, etc. Good engineering practice such as free from burrs, avoiding sharp corners, etc to be followed. 12. The wheels are designed of solid tubeless tyres with direct mounting hub shall clearly indicate the MOC of hub, tyre and its size. Type of wheel bearing, number & load bearing capacity, Break assemble for each type etc. The hub and tyres shall be capable of taking a load of minimum 2000 Kgs each wheel and wheel shall have free movement even on rough surfaces. The Contractor shall submit manufacturer’s test certificate for the load carrying capacity of the tyres, failing which such wheels shall not be accepted. 13.. The wheels tyres shall be tubeless of make :- MRF. 14. Each wheel shall have 04 numbers of 6305 ZZ heavy duty sealed ball bearing of make such as SKF, NTN TESTING OF DG SET :Contractor shall be responsible for carrying out of testing of DG set by IEM before commissioning at site. Test report , Purchase vocher , DG manual book, manufacturer's test certificate etc shall be handover to concerned JE and no payment shall be released without the submission of above documents. Documents, fuel, load bank and any other items required for testing of DG set shall be included in the quotatd rate. If desired test report shall not be obtained, the test shall be repeated without any extra cost till obtaining desired test result.
Supply & lay and testing of LT cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 Sqmm 3.5 core, laid in duct / fixed on wall/trenches complete all as specified and directed by Engineer-in-Charge.
Supply & lay of Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 110 mm and inner dia 95 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed by Engineer-in-Charge. Make : Rex poly extrusion Ltd / Tirupathi Plastomatics Pvt Ltd
Supplying and laying GI tubing medium grade ISI marked for cable protection in trenches/duct/fixing to pole/wall or in such similar position of 80mm bore complete all as specified and directed by Engineer-in-Charge.
Excavation in hard / dense soil Including road cutting etc not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out including forming of bottom for laying cable all as specified and directed by Engineer-in-Charge.
M&L for providing earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick buried directly in ground earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to copper earth strip 20 x 3 mm by means of bolts, nuts, check nuts & washers of copper and connecting to earth dolly all as shown in electrical plate No. 3 of SSR Part I of 1991 & testing complete including 15mm dia light grade GI pipe up to 7.5mtr long, excavation in any type of strata, PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm with frame, test box , funnel, wire mesh with GI watering pipe etc) all as specified and directed by Engineer-in-Charge.
S&F copper strips 20x3 mm to connect DG sets laid on wall, trenches complete all as directed by Engr - in - Charge.
GAYATRI ENTERPRISES
OPS Associates
NAVJEEVAN ENTERPRISES
T.THIYAGARAJAN
Kakolil Trade Agencies
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .