Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAdmitted-Finance | ₹1.3 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.3 Cr+₹76,900.42 (0.58%)Admitted-Finance 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹1.3 Cr+₹76,900.42 (0.58%) | L2 | Admitted-Finance |
| 3 | L3₹1.4 Cr+₹8.6 L (6.45%)Admitted-Finance | ₹1.4 Cr+₹8.6 L (6.45%) | L3 | Admitted-Finance |
| 4 | L4₹1.4 Cr+₹8.6 L (6.45%)Admitted-Finance | ₹1.4 Cr+₹8.6 L (6.45%) | L4 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/s Friends Engineering Works L4 | FAVOURITE ELECTRICALS L1 | M/s Blue Star Ltd L2 | M/S HI TECH ENGINEERING SERVICES L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | SITC of VFD based, AHRI/ Eurovent certified, water-cooled, Mono/ Twin Screw Type Chiller of capacity not less than 100 TR with allied items. The item shall be complete and ready to be connected with main headers in the existing Central Air Conditioning Plant of SKIMS Soura. The chiller shall be accompanied with microprocessor based control panel with all safety, switch gears needed for safe, smooth and hassle-free operation. The job includes laying of foundation as per OEM recommendation which shall be not less than 6 inches above the finished floor level. The technical specifications are further detailed in Annexure B. | 2 | Job | 38,99,786 ₹77,99,572 | 35,25,000 ₹70,50,000 Lowest | 39,81,639.5 ₹79,63,279 | 38,50,000 ₹77,00,000 |
| 2.00 | SITC electric-motor driven Centrifugal Pump for condenser and chiller sides having a discharge of 15 to 18 Litres per second, Head of 30 metres, 1450 rpm. The technical specifications are furhter detailled in Annexure B. | 4 | Job | 90,000 ₹3,60,000 | 1,80,000 ₹7,20,000 | 7,885 ₹31,540 Lowest | 1,30,000 ₹5,20,000 |
| 3.00INSULATED CHILLED WATER PIPING (Nitrile rubber Insulation) Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg/ cum density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note: The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. | |||||||
| 3.10 | 300 NB(32mm nitrile insulation thickness) | 30 | RMT | 7,628 ₹2,28,840 | 7,565 ₹2,26,950 | 6,588 ₹1,97,640 | 5,900 ₹1,77,000 Lowest |
| 3.20 | 250 NB (32mm nitrile insulationthickness) | 15 | RMT | 6,565 ₹98,475 | 6,297 ₹94,455 | 3,728 ₹55,920 Lowest | 5,000 ₹75,000 |
| 3.30 | 150 NB(32mm nitrile insulationthickness) | 75 | RMT | 3,637 ₹2,72,775 | 3,420 ₹2,56,500 | 3,207 ₹2,40,525 | 2,700 ₹2,02,500 Lowest |
| 3.40 | 125NB(32mm nitrile insulation thickness) | 20 | RMT | 3,100 ₹62,000 | 2,848 ₹56,960 | 2,618 ₹52,360 | 2,100 ₹42,000 Lowest |
| 3.50 | 100 NB (32mm nitrile insulationthickness) | 20 | RMT | 2,600 ₹52,000 | 2,328 ₹46,560 | 1,935 ₹38,700 Lowest | 2,000 ₹40,000 |
| 3.60 | 80 NB(32mm nitrile insulation thickness) | 15 | RMT | 2,000 ₹30,000 | 1,681 ₹25,215 | 1,935 ₹29,025 | 1,600 ₹24,000 Lowest |
| 3.70 | 65 NB (32mm nitrile insulationthickness) | 15 | RMT | 1,800 ₹27,000 | 1,376 ₹20,640 Lowest | 1,661 ₹24,915 | 1,400 ₹21,000 |
Tender Value
₹1.8 Cr
EMD Value
₹3.5 L
Closing Date
6 Sept 2025, 12:10 pmClosed
Executive Engineer MHD SKIMS/JVC
SKIMS Soura
SITC of 2 No. Chillers with cooling tower in central AC Plant of Main Hospital at SKIMS Soura
2025_PWDJK_285698_1
MHD/SKIMS/JVC/43 0F 2025-26 DATED.27.08.2025
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
120 days
SKIMS Soura
Please refer Tender documents.
12 documents required · 12 mandatory
₹1,500
Executive Engineer MHD SKIMS/JVC
₹3.5 L
26 Sept 2025
28 Aug 2025
6 Sept 2025
28 Aug 2025
6 Sept 2025
28 Aug 2025
Amount
SITC of VFD based, AHRI/ Eurovent certified, water-cooled, Mono/ Twin Screw Type Chiller of capacity not less than 100 TR with allied items. The item shall be complete and ready to be connected with main headers in the existing Central Air Conditioning Plant of SKIMS Soura. The chiller shall be accompanied with microprocessor based control panel with all safety, switch gears needed for safe, smooth and hassle-free operation. The job includes laying of foundation as per OEM recommendation which shall be not less than 6 inches above the finished floor level. The technical specifications are further detailed in Annexure B.
SITC electric-motor driven Centrifugal Pump for condenser and chiller sides having a discharge of 15 to 18 Litres per second, Head of 30 metres, 1450 rpm. The technical specifications are furhter detailled in Annexure B.
INSULATED CHILLED WATER PIPING (Nitrile rubber Insulation) Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg/ cum density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note: The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia.
300 NB(32mm nitrile insulation thickness)
250 NB (32mm nitrile insulationthickness)
150 NB(32mm nitrile insulationthickness)
125NB(32mm nitrile insulation thickness)
100 NB (32mm nitrile insulationthickness)
80 NB(32mm nitrile insulation thickness)
65 NB (32mm nitrile insulationthickness)
SITC of Butterfly Valves with DI body double flanged construction with EPDM coated disc with long pitch and PN 16 pressure rating as per IS 13095 (1991)
Providing and fixing of Aluminum Cladding of 0.63 mm thick sheet to the insulated pipelines including bends, valves, fittings, etc. The job includes grooving, providing and fixing of screws, washers etc. as per IS : 2676 - 1981
300 NB (32mm nitrile insulation thickness)
250 NB(32mm nitrile insulation thickness)
150 NB(32mm nitrile insulationthickness)
125NB (32mm nitrile insulationthickness)
100 NB (32mm nitrile insulation thickness)
80 NB (32mm nitrile insulationthickness)
65 NB(32mmnitrile insulation thickness)
SITC of ductile iron Non-return valve of following size with allied jobs as per site requirement. The valve shall be conforming to IS-5312. Pressure Rating : PN16
SITC of Y-Strainer (CI) flanged end, of following size with allied jobs as per site requirement. Pressure Rating : PN16
SITC of Balancing valve (ductile iron) of following size with allied jobs as per site requirement. Pressure Rating : PN16
SITC of T-Strainer (C.I.) of following size with allied jobs as per site requirement. Pressure Rating : PN16
SITC in position the Bi-metal Dial thermometer Temperature Guage 4” Dail Size ½ “ BSP (M) connection, SS case and SS Wetted parts completer as required
SITC of Air Release Valve of following size. Air release valves shall be provided at all higher points in piping system for venting.
25 mm dia ϕ
SITC of forged brass Ball Valve (PN-16) for drain of following size.
SITC of powder coated, vermin proof, Electric Panel fabricated out of 14 SWG CRCA sheet laid over MS angle frmae, internally wired, with modular construction having incoming and outgoing MCCBs, cable way module, metering module, copper bus bars with all protections and as per Technical specifications detailed in Annexure B.
Electric Cable:- SITC of PVC insulated armored sheathed XLPE copper conductor cables from main panel boards to various equipments and from sub-panel to cooling tower and centrifugal pumps through walls/ceiling with appropriate clamps and fixing arrangement. The job includes electric cable tray with all accessories for laying of electric cable The electric cable shall be conforming to IS-7098
35 mm sq. 3.5 core, 11 kV,LV
10 NB sq. 3 core 11 kV,LV
6 NB sq. 3 core 11 kV,LV
Annual CMC for two (02) no. chillers of 100 TR capacity.
Cooling Tower: Supply, testing and commissioning of round/square/rectangular induced draft counter flow Cooling Tower. The cooling capacity shall be adequate as shall be required, for chilller of Capacity not less than 200 TR and as per the technical specifications detailed in Annexure B B
Earthing for chillers/ pumping units/ Steel strtuctral frame work cooling towers by way of chemical earthing as per IS 3043. The job includes providing and laying of GI strip of size 25 mm x 5 mm from earthing electrode to the Panel, chiller/ cooling tower, motors, etc. of required length as per site requirement.
Platform Works FOR COOLING TOWER
Demolishing existing cement concrete manually/ by mechanical means including disposal of material within 50 meters lead as per direction of Engineer-in to make space for foundation pillars charge: 1:3:6 or richer mix (i/c equivalent design mix) Size = [3' x 3' x 6"] x 6 (no)
Earth work in bulk excavation by manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 m2 on plan) including disposal of excavated earth lead upto 50 meters and lift upto 1.5 m, as directed by Engineer-in-Charge. All kinds of soil Size = [3' x 3' x 6"] x 6 (no)
Supply, Filling, Spreading and levelling soling stone for foundation of Column Foundation in required thickness with all leads and lifts complete. Size = (3' x 3' x 6") x 06 Nos.
CEMENT CONCRETE (CAST-IN-SITU) Mudmat Providing and laying in position cement concrete (by making use of mechanical vibrator) of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with: 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) Size = (3' x 3' x 2") x 06 Nos.
FORM WORK Centering and shuttering including strutting, propping etc. and removal of form for: Columns, pillars, piers, abutments, posts and struts. Size = 12' x 3'4" x 6 nos
CAST-IN-SITU Providing and laying in position specified grade of reinforced cement concrete including curing but excluding the cost of centering, shuttering, finishing and reinforcement. All works upto plinth level: 1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size) Size: 3' x 3' x 3'4" x 6 nos.
STEEL REINFORCEMENT Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more.
Demolishing brick work in cement mortar manually/by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 meters lead as per direction of Engineer-in-charge:
Proving and laying of 20mm Cement plaster of mix: 13.3.1 1 : 4 ( 1 cement : 4 fine sand)
Providing and applying white cement based putty of specified thickness, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. 2 mm thick
Distempering with 1st quality acrylic distemper, having VOC (Volatile Organic Compound) content less than 50 grams/ liter, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. Two coats
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting , hoisting , fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished seamless type tubes, Round section 200 mm dia and 8 mm thick, 50 mm 2.9 mm thick
Providing and laying cement concrete (by making use of mechanical vibrator) in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts,struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchors blocks, plain window sills, fillets etcupto floor V level, including curing but excluding the cost of centring, shuttering and finishing with. 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
Structural steel work (Welded) in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. Setions to be used ISMB 250, ISMC 150, ISMC 75, ISA 50506, hollow square section of size 25x25x3mm etc. as per the details given in Annexure B
Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete. MS Plate 25 mm thick, MS Plate 16 mm thick, MS Chequered Plate 8 mm thick, etc. as per the details given in Annexure B
Providing and fixing in position M20 J Foundation Anchor Bolt with washers and double nuts to hold on to the foundation plates. M20 of length not less than 4 feet 8 x 6 nos
M/s Blue Star Ltd (BID ID -2479200)
M/S HI TECH ENGINEERING SERVICES (BID ID -2480111)
M/s Friends Engineering Works (BID ID -2478020)
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .