Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹11.0 LAdmitted-Technical SARCH GANDERBAL J K 191131 | GANDERBAL | JAMMU AND KASHMIR | 191131 | -27.65% | ₹11.0 L | L1 | Admitted-Technical Reponsive |
| 2 | L2₹13.3 L+₹2.4 L (21.5%)Admitted-Technical | -12.10% | ₹13.3 L+₹2.4 L (21.5%) | L2 | Admitted-Technical Responsive |
| 3 | Not Admitted-Fee/PreQual/Technical/Finance | - | - | - | Not Admitted-Fee/PreQual/Technical/Finance Others-The registration with the latest renewal has either been not updated or not submitted, and the treasury challan has also not been submitted |
| 4 | Not Admitted-Fee/PreQual/Technical/Finance | - | - | - | Not Admitted-Fee/PreQual/Technical/Finance Others-The registration with the latest renewal has either been not updated or not submitted, and the treasury challan has also not been submitted |
Tender Value
₹15.1 L
EMD Value
₹30,295
Closing Date
14 Jan 2026, 4:00 pmClosed
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX
Internal Electrification for New Electrical Division Workshop Building at Sumbal RandB B.W.O Setting and Upgradation of Divisional Workshop for ED Sumbal
2025_PWDJK_299501_1
NIT No.Fresh/247/2025-26 Dt/30/12/2025
Open Tender
Electrical Works
Percentage
sumbal
Please refer Tender documents.
4 documents required · 4 mandatory
₹800
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹30,295
21 Jan 2026
31 Dec 2025
15 Jan 2026
31 Dec 2025
14 Jan 2026
31 Dec 2025
Part-A (Internal Electrification)
Wiring for Light point/Exhaust point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable (Polycab/Finolex/Salzer/Paramount/ eq. make to be approved by EIC) in existing surface/recessed Conduits (Including Cost of Conduit) laid in slabs with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Zencelo)/ eq. Make & shall be approved before execution of work.
Supplying and Fixing of Indicator as required, ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider (Zencelo)/ eq. Make & shall be approved before execution of work.
Wiring for Ceiling Fan point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable (Polycab/Finolex/Salzer/Paramount / eq. make to be approved by EIC) in existing surface/recessed Conduits (Including Cost of Conduit) laid in slabs with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Zencelo)/ eq. Make & shall be approved before execution of work.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required,ISO/IEC Certified of Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Zencelo)/ eq. Make & shall be approved before execution of work.
Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Polycab/ Finolex/ Salzer/ Paramount / eq. make to be approved by EIC)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required, ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Zencelo)/ eq. Make & shall be approved before execution of work.
Wiring for 6Amp Plug(Computer Point) with (P+N+E) 3 x 2.5 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Polycab/Finolex/Salzer/Paramount / eq. make to be approved by EIC)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including proving and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings), ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Zencelo)/ eq. Make & shall be approved before execution of work.
Wiring for Sub main Wiring along with earth Wire with the following Sizes of FRLS PVC insulated copper conductor, single core Cable in surface/Recessed medium class PVC conduit (Polycab/Finolex/Salzer/Paramount/ eq. Make) & shall be approved before execution of work.
4x10 sq.mm+ 2x6 sq.mm (P+N+E) for Power point Sub main in One run from Main Panel to Distribution Boards.
2x6 sq.mm+ 1x6 sq.mm (P+N+E) for Lighting/Inverter/AC Point Sub main in One run from Main Panel to Distribution Boards.
2x2.5 sq.mm+ 1x2.5 sq.mm (P+N+E) for Lighting/Inverter Circuit in One run from switch boards to Distribution Boards.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required of Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Zencelo)/ eq. Make & shall be approved before execution of work.
Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/ABB /Schneider / eq. make to be approved by EIC)
Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/ABB/Schneider / eq. make to be approved by EIC)
Supply/Fixing/Testing and Commissioning of 100 Amp , 4 pole, (TPN) 440 V, C* Curve 10K, in the existing TPN DB complete with connections. (L&T/Siemens/ Legrand/ABB/ Schneider / eq. make to be approved by EIC)
Supplying and Fixing of MCB 8-Way horizontal typed , sheet steel, Double Door Distribution Board, SPN 240V V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ ABB /Schneider / eq. make to be approved by EIC)
Supplying and Fixing of MCB 6-Way (4+18) horizontal typed , sheet steel, Double Door Distribution Board, TPN 240V/415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ ABB /Schneider / eq. make to be approved by EIC)
ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER ROD EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value.Supply,Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 20mm Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through suitable DWC High Density Poly ethylene Pipe having Corrugation complete job.
Supply/Installation/Testing and Commissioning of 18W + LED Surface/Recess Mounted Panel light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of Wipro/Trilux/LT/Polycab/HG / eq. make to be approved by EIC.
Supply/Installation/Testing and Commissioning of 150Watt Next generation, energy saving, environment friendly & robust highbay LED with PDC housing suitable for ceiling (Surface/Suspended) mounting with system effiency upto 150 Im/W Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The Job Includes Supply/Fixing of Suspension Kit for hanging of light.The job further includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of Philips/ Wipro/ Trilux/ Polycab/ Jaguar / eq. make to be approved by EIC.
Providing & Fixing of IK08 IP-66 protected high power LED 100 Watt flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 Im/wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K 355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR:-High Power LED Flood Light Minimum lumen output 6200 Im of Polycab//Crompton/Philips/Trilux/ eq. Make as approved and to be installed on outside block including S/F of suitable size of Gyser bolt.The job further includes replacement warranty of fixture (if damaged/burnt out what so ever reason) for a period of two years reckoned from date of successful commissioning /handing over of site to intending department.
Supply/Installation/Testing and Commissioning of 225-250mm Shutter Typed,320 Cu.m/Hr.AC 220-240 Volts, 50 Hz Exhaust fan made out of ABS Plastic Material with inbuilt thermo cut-off Protection and Noise Level not exceeding 37dB o including connection etc USHA/Anchor/Polycab/Orient / eq. make to be approved by EIC.
Supply/Installation/Testing and Commissioning of BLDC 1200 mm sweep, ceiling fan with 03 No. blades, 30 cm long down rod, 02 No. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Anchor/Polycab/Orient / eq. make to be approved by EIC.(5-Star)
Supply/Installation/Testing and Commissioning of ABC type Fire Extinguisher 4.Kg. Capacity ISI Mark(IS:15683) and dully certified.
Supply/Installation/Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark(IS:15683)suitable for 'B' and 'C' class fires - inflammable liquids, gaseous fires like L.P.G,acetylene and electrical fires.
Supply/Laying of 25/32mm Dia PVC Conduit of Anchor/Ravinder/Polypack/Finolex / eq. make to be approved by EIC with other accessories like bends,etc complete to be laid in wall for downs
Supply and Fixing of single pole blanking plates on existing MCB boxes, excluding cost of Boxes.
Providing and fixing of bakelite hylam sheets of required size including cutting, filing with S/F screws etc.
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required of Legrand/Panasonic/Anchor/Schneider / eq. make to be approved by EIC
Supply/ installation/testing and commissioning of CPRI Approved (IS/IEC:61439) panel Wall / floor mounted) compartmentalized , 415 volts TPN MCCB Mian Distribution panels ,fabricated out of sheet steel of 16 gauge dust protected, painted incl earth terminal with all necessary accessories as required for panel with internal wiring of panel .The Panel is to provided and fitted with following adjustable type controlling /Protection switch gear devices (1) Normal Incoming 160 Amp TPN MCCB with breaking capacity of 36 KAwith extended thimbles of Legrand/Siemens/ABB//LK / eq. make to be approved by EIC = 1 no 200 Amp TPN Bus bar Al Strips = 1 Set Volt meter =1 no, Ammeter = 1 no , CT coils for Am meter 300 /5A = 1 set ,phase indicators =1set (2) Generator Incomer 100 Amp Four Pole Change over switch of Legrand/Siemens/ABB//LK / eq. make to be approved by EIC = 1 no., 100 Amp TPN Bus bar Al Strips = 1 Set Volt meter =1 no, Ammeter = 1 no , CT coils for Am meter 300 /5A = 1 set ,phase indicators =1set & 100 Amp TPN Bus bar Al Strips = 1 Set (3) Invertor /Solar Incomer 63 Amp Double Pole MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T / eq. make to be approved by EIC = 1 no 100 Amp P&N Bus bar Al Strips = 1 Set & Phase indicators =1set (4) Bypass 3-Phase, Four Pole 100 Amp,415V Ac,50Hz Bypass Switch Seimens/LK/ABB / eq. make to be approved by EIC for bypassing 20 KVA AVR. Outgoing . (1) 63 Amps TPN MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T / eq. make to be approved by EIC = 03 No for normal heating sub main (2) 40 Amps DP MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T / eq. make to be approved by EIC = 05 No for Sub main lighting/AC (3) 32 Amps DP MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T / eq. make to be approved by EIC = 03 No for Sub main invertor The Panel manufacturing unit should be CPRI Registered and the Contractor has to submit the test certificate of main switch gear and Drawing of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards) is to approved by Engineer Incharge before manufacturing
Supply/Installation/Testing & Commissioning of 3-phase 20 KVA,50 Hz Oil cooled unbalanced type Voltage Stabilizer SERVO control of Approved brand COPPER wound of AE/Chinar/Cosco / eq. make to be approved by EIC ISI/1SO/IEC certified for smooth functioning/constant voltage supply having Technical Specifications: Input voltage(Ph-N) ranging from 90 Volts to 240 Volts and a balanced output Voltage of 230 Volts, ±2% Buck Boost Transformer Copper wound 99.9% ,OIL Immersed COOLING OIL, High cut/Low Cut /Time delay/Over Cut through Micro Controller and Spike Protection.(For Lighting & Computer Load Only)
Providing and Laying of shock proof rubber mats of 2mx1mx12mm thick in size of Standard Make.
Supply/Laying/Testing and Commissioning of 3.5 Core 70 mm sq. Al armored XLPE Insulated,PVC cable Polycab/RR Kabel/Paramount/KEI / eq. make to be approved by EIC. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping.
Supply/Laying/Testing and Commissioning of 3.5 Core 35 mm sq. Al armored XLPE Insulated,PVC cable Polycab/RR Kabel/Paramount/KEI / eq. make to be approved by EIC. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping.(For Oven)
Supply/Installation/Testing/Commissioning of 100 Amp TPN MCCB with breaking capacity of 36 KAwith extended thimbles of Legrand/Siemens/ABB//LK / eq. make to be approved by EIC along with wall mounted 14/16 gauge kisok.(For Oven)
Supply/Installation/Testing/Commissioning of 03KVA/24V Pure Sinewave Solar Inverter With ISOT Technology, Intelligent Load Sharing & BIS Certified (with 2-Year Warranty), 04 No. of 200Ah,12V Tubular battery (with 36 Months Warranty) & Suitable Trolley Support for Inverter resting & resting of Tubular Battery etc Havells/ Luminious/ EXIDE/ AMRON / eq. make to be approved by EIC.
Supply/Installation/Testing & Commissioning of 6-10W LED Mirror Light of Anchor/Bajaj/Jupiter/ Jaquar / eq. make to be approved by EIC as Bed Light duly fitted on walls including making of necessary Connections & sample shall be approved.
Part-B (Outdoor Illumination)
"Supply and Erection of 09 Mtr Galvanized Iron pole with galvanizing done in single dippine. (Average coating. thickness Minimum 65 Microns) continuously tapered poles having Octagonal / circular erose sectione designed to withstand the maximum wind speed as per Is 875, The pole shaft shall he made from shear steel (47 Steel Conforming to grade 536510) and Confirming to BS&N 1002, and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with tha rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing. Technical Specification:- 1) No. Of Section 1 NO. 2) No of sides 8 NOS. 3) Base plate size 225 X 225 MM 4) Base plate thickness 12 MM. 5) Base plate hole PCD 225 MM. 6) No of holes 4 NOS. 7) Hole dia 24 MM / SLOTTED 8) Size of door opening 250 MM. 9) Pole section length 6000 MM. 10) Pole section Theckness 3 MM. 11) Bottom Dia ( Outer ) 130 MM. 12) Top Dia ( Outer ) 70 MM. 13) Foundation Bolt Length 550 MM. 14) Foundation Bolt Dia 20 MM. 15) Wind Speed 180 Km / Hr. 16) Dimension Tolerance As Per BSEN 40. 17) Material Tolerance As Per IS 1852 - 1985. 18) Shaft Material Type As Per BSEN 10025 S 355 Or Equivalent. 19) Base Plate Type As Per IS 2062. 20) Foundation Bolt Type As Per IS 1367 Gr. 6.8. 21) Material Protection Hot Dip Galvanized. 22) Zinc Coating Thickness 65 Microns. 23) Galvanizing Type AS PER ISO 1461 : 1999. 24) Finishing Type As Per IS 11759 - 198. The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 Sq.mm stud type connector (4 nos) inside the pole at door opening for cable connection (Utkarsh/Valmont/BPP / eq. make to be approved by EIC. Also includes Supply/Fixing of 8 SWG G.I wire run over the cable length properly earthed with main earthing pit/grid (Standard make)
Design/Supply/Fixing of one way Convex Shape Type G.I Bracket & shall hold 04 No. of flood Lights of 200Watt Each & to be approved before Designing & Supplying, as per site requirement on approval of site Incharge.
Providing and Laying RCC Foundation for 09 Mtr Octagonal Poles) as pe rawing attach at Table P.4 with Following Procedure & Al as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . A) Excavation of Pit for Foundation Size upto required depth from Ground level B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness D) Reinforcement for R.C.C. work with MT bars Including straightening, cutting, bending, placing in position and binding all complete. E) Centring and shuttering including strutting, propping etc. and removal of form work for Footing and F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM G) Providing and Laying Reinforce cement Concrete of M-25 grade In Footing and Pedestal including Curing the foundation for 7 days. H) Providing and Fixing Nusing Angle 40 m x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face.
Supply/Installation/Testing and Commissioning of IK08 IP-66 protected high power 200 Watt.LED flood light system with single piece Pressure die cast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 Im/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @›=300 V AC and Auto resetting Safety Power Factor >0.95, THD(1) <10%, driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min >=4KV internal and 10K external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K 355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.The job further includes replacement warranty of fixture (if damaged/burnt out what so ever reason) for a period of two years reckoned from date of successful commissioning /handing over of site to intending department. connection wires Wipro/Philips/Trilux/Jaquar/Crompton / eq. make to be approved by EIC.
Supply/Laying/Testing and Commissioning of 4-Core 10 mm sq. Al armored XLPE Insulated,PVC cable Havells/Polycab/RR Kabel/Paramount / eq. make to be approved by EIC. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (10 Inch below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping.
stage.html
html • 0.03 MB
tech_eval.pdf
finance_971620.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.05 MB
BOQ_971620.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .