Loading…
Loading…
Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
8 Jun 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
TENDER ELG
14 conditions · 2 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less where V= Advertised value of the tender in crores of Rupees, N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.(In this connection scanned copy of Annexure VIB duly filled up must be attached with offer).
The tenderer must have successfully completed any of the following during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works costing not less than the amount equal to 40% of advertised value of the tender, or One similar work costing not less than the amount equal to 60% of advertised value of the tender .Other terms and conditions shall follow of GCC, April 2022. Definition of Similar nature of work has given below (1.1)
Defination of Similar Work :- Item Sl. No. 1.(iii) under "HT Electrical Works" : Supply, Installation, Testing and Commissioning of HT Sub- Station of same KV or higher KV including associated Electrical work with / without AMC. O R Replacement / Maintenance / Modification/Upgradation /Augmentation of same KV or higher KV Sub- Station related work with / without HT Panel .
13 conditions · 4 needing a document upload
Scanned copy of valid GST (Goods & Service Tax)Registration Certificate.
The following documents should be attached with the tender ( Annexure-V (A) certificate is to be given by attorney/authorized signatory/each member of Partnership firm/Joint Venture (JV) / Hindu Undivided Family (HUF) / Limited Liability Partnership (LLP) etc. & Scanned copy POA/Partnership deed is to be uploaded Duly filled up by the bidder
Partnership deeds, power of Attorney etc. (if any) : The tender shall clearly specify whether the tender is submitted on his own or on behalf of a partnership concern. If the tender is submitted on behalf of partnership concern he should submit the certified copy of the partnership deed along with the tender authorisation to sign the documents on behalf of the partnership firm. If these documents are not enclosed along with the tender document, the tender will be treated as hearing lease submitted by the individual signing the tender documents. The Railway will not consider any power of Attorney granted by the tender or any changes in the composition of the firm made subsequent to the execution of the contract. It may however recognize such power of Attorney and change after obtaining proper legal advice, the cost of which will be chargeable to the contract.(Scanned copy POA/Partnership deed is to be uploaded Duly filled up by the bidder. As per clause no. 14(e) of GCC'22, the following documents to be uploaded in terms of Company registered under Companies Act2013: (i) The copies of MOA (Memorandum of Association) / AOA (Articles of Association) of the company (ii) A copy of Certificate of Incorporation (iii) A copy of Authorization/Power of Attorney issued by the Company (backed by the resolution of Board of Directors) in favour of the individual to sign the tender on behalf of the company and create liability against the company. (iv) All other documents in terms Para 10 of the Tender Form (Second Sheet) above.
Scanned copy of valid Trade license or Propitorship Certificate.
List of the Works completed in the last three financial years giving description of work. Organization for whom executed, approximate value of contract at the time of award, date of award and date of scheduled completion of work. Date of actual start, actual completion and date of payment and final value of contract should also be given. (Supportive documents/ certificates from the organization with whom worked/are working should be enclosed) (Please attach scanned copy of Annexure-I duly filled up).
List of works in hand indicating Supportive documents/certificates from the organization with whom worked/are working should be enclosed) description of work, contract value, approximate value of balance work yet to be done and date of award. (Supportive documents/certificates form the organization with whom worked/are working should be enclosed).(Please attach scanned copy of Annexure-IV duly filled up)
Railway Officers Associated with tenderer:RAILWAY OFFICERS ASSOCIATED WITH TENDERER 1. ExRailway Officer as tenderer: Should tenderer be a retired Gazetted Officer working before his retirement on any of the Railways owned and administered by the President of India, or should the tenderer being partnership firm have as one of its partners a retired Gazetted Officer as aforesaid, or should the tenderer being an incorporated company have any such retired Officer as one of its Directors, or should the tenderer have in his employment any retired Gazetted Officer as aforesaid, full information of such person shall be submitted along with his tender in the format given in annexure-VI to this chapter of this tender document. (Authority: ACS No.3 to GCC July,2014vide Boards letter No.2014/CEI/CT/O/9/RET dt.22.01.2015)(please attach scanned copy of Annexure-VI duly filled up by the firm).
Option for receiving payment through Letter of Credit . (Please attach scannedcopy of ANNEXURE 1 LC & ANNEXURE 2 LC duly filled up by the firm if optedfor)
The following documents should be attached with the tender: (i)Scanned copy of Pan Card. (ii)Scanned Copy of EFTMANDATE FORM Duly filled up by the bidder(iii)Tender Document (duly digitally signed by the bidder)
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Submission of Documents in support of Eligibility Criteria : All documents in support of fulfillment of eligibility criteria with respect to completion of 'Similar Nature of work for technical Eligibility criteria 'and 'Total Contract value for Financial Eligibility Criteria' should be uploaded online in the website with scanned copy at the time of tender bidding with the details. No post - tender communication , in any form will be made or entertained , after opening of tenders in this regard .Railways may however call for the originals of the credentials for verification or any clarifications/Confirmations on the contents of the documents submitted .Eligibility of tenderers shall be decided solely on the basis of the documents submitted alongwith the tender offers and any subsequent document whatsoever submitted in this connection would not be given any cognizance on any account.
The Contractor/(firm) must go through the entire tender document along with all attachment for any kind of guidance regarding execution of the job & payment there after. In case any thing is left out or not clear then they should consult the General Condition of Contract & standard Specification as attached (uploaded ).The bidders are also advised to preserve a copy of entire tender document/ (Set) for their convenience.
Augmentation & Improvement of Electrical Substations, Switch Rooms with associated HT/LT switchgear panel, cables, Transformer, Earthing & other safety items under the jurisdiction of SSE/G/BDC.
EL-HWH-25-21-3583
EL-HWH-25-21-3583
Open
Works - General
180 Days
Howrah, West Bengal
₹0
₹2.6 L
8 Jun 2026
16 May 2026
25 May 2026
117 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 1,29,53,874 | ||
| — | — | — | 31,00,021 | ||
| Supply of Outdoor type compact type secondary sub-station (CSS) consistining of cast resin dry type AN cooling transformer of capacity 500 kVA, 11KV/415V with off load tap switch, vector group -DYn11 11KV, 630 Amps, 21kA for 3 sec. SF6 gas insulated non extensible compact switchgear (RMU) consisting of 02 nos. motorized load break switch and 01 no motorized VCB and bus PT metering panel self power series trip microprocessor base numerical over current & amp; earth relay (idmtl+inst) for protection in VCB and fault passage indicator in both lbs. LT panel consisting of 1 no. 1000A Air Circuit breaker 4 pole, drawout type motorized, 50kA microprocessor based for release for O/L, S/C & amp; E/F protection as outgoing suitable for 415V operation microprocessor based MCCBs ( 2 nos. 160-400A MCCB, 4P, 50kA and 4 nos. 100-250A MCCB, 4P, 50kA ) with LSIG protection along with 7 nos. MFM, including necessary HT, LT and control cabling works, internal earthing connection by GI strips etc. and the said CSS should be fully compatible for SCADA based Remote operation and monitoring facility ( Make - Siemens / ABB / Schneider / EATON ) ( Please see detailed technical specification ) | — | 1.00 | — | — | |
| — | — | — | 55,508 | ||
| Installation, connection, testing and commissioning of above CSS including cable glanding, socketing and plinth construction alongwith construction of Iron shed structure with metal and transparent sheet top cover and MS grill structure duly painted at four sides of CSS. | — | 1.00 | — | — | |
| — | — | — | 5,46,923 | ||
| Supply of Fully motorised indoor extensible type Ring Main Units ( RMU ) of rated Voltage ( Nominal / Max ) 11 / 12KV, rated current 630A, short time withstand current 21 / 26.3 KA for 3 sec., compact switch gear encapsulated in SF6 gas filled stainless steel tank complete with numerical protection relay and metering facilities and remote operation facility ( SCADA Compatible ) consisting of : a) Vacuum Circuit Breaker for Incomer & Outgoer - 1 no. with Bus PT ( Extensible type ) ( Make - Siemens / ABB / Schneider / EATON ) ( Please see detailed technical specification ) | — | 1.00 | — | — | |
| — | — | — | 27,346 | ||
| Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation as per site condition with all associated accessories. | — | 1.00 | — | — | |
| — | — | — | 20,99,273 | ||
| "Supply of LT cubicle Indoor Type Wall / Floor Mounted Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following items and all Microprocessor protection-based MCCB / ACB must have facility of individual 'LSIG' fault indication with complete SCADA compatible remote operation and monitoring facility :- a) ACB, 4 Pole, 1600 Amp, 415V, 50 Hz, 50 kA, MDO Type, Motorized, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model :- LK (L&T) C Power S1- 4 Pole With SR18G Trip Release, CAT No.- SL96065 or equivalent - 3 nos. b) MCCB, 4 Pole, ( 160 - 400)Amp, 415V, 50Hz, 36kA, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model :- LK (L&T) DN3-400D 160-400 A, MTX2.0, CAT No. -CM93003OOOOAG or equivalent - 4 nos. c) MCCB, 4 Pole, ( 100 - 250 )Amp, 415V, 50Hz, 36kA, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model :- LK (L&T) DN2-250D 100- 250 A, MTX2.0, CAT No. -CM92151OOOOAG or equivalent - 4 nos. d) MCCB, 4 Pole, ( 63 - 160 )Amp, 415V, 50Hz, 36kA, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model :- LK (L&T) DN2-250D 63-160 A, MTX2.0, CAT No. -CM92152OOOOAG or equivalent - 4 nos. e) MCCB, 4 Pole, ( 40 - 100 )Amp, 415V, 50Hz, 36kA, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model :- LK (L&T) DN2-250D 40-100 A, MTX2.0, CAT No.-CM92153OOOOAG or equivalent - 4 nos. f) Tinned Copper Busbar (4 Bar) each of capacity 2000 Amps., 415V, 50 Hz. With extension Bus Bar for interconnection with existing LT distribution panel - 1 set g) Static Multifunction panel mounting Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Accuracy CL1 with Maximum Demand (kW & kVA) and Bi-directional (Import-Export) Energy integrating facility and RS485 Communication port Model :- LK (L&T) MFM 4430, CAT No.- WL443011OOOO or equivalent - 2 nos. h) Static Multifunction panel mounting Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Accuracy CL1 and RS485 Communication port Model :- LK (L&T) MFM 4410, CAT No.- WL441011OOOO or equivalent - 16 nos. i) CT of suitable ratio for MFM & Ammeter - 54 nos. j) LED indication lamp for 3-Phases for incoming feeders and ""ON, OFF & TRIP"" indication for all incoming and outgoing feeders - 63 nos. k) Petty Store for control cable, MCBs, gland, socket, fuse, push button, TNC switch, selector switch, rotary handle operating mechanism, spreader terminals, interlocking arrangement, auxiliary contacts, shunt release, terminal blocks & NO/NC relays for SCADA RTU connectivity etc. - 1 job. l) Fabrication work for above panel - 1 job. complete with internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade. " ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S ) | — | 1.00 | — | — | |
| — | — | — | 1,04,964 | ||
| Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories | — | 1.00 | — | — | |
| — | — | — | 15,54,216 | ||
| "Supply of LT Wall Mounted / Floor Mounted Double Door Cubical Outdoor type Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following items for 250KVA to 300 KVA Load : a) MCCB, 4 Pole, ( 160 - 400 )Amp, 415V, 50Hz, 36kA, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model : LK (L&T) DN3-400D160- 400 A, MTX2.0, CAT No. -CM93003OOOOAG or equivalent - 2 nos. b) MCCB, 4 Pole, ( 100 -250 )Amp, 415V, 50Hz, 36kA, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model :- LK (L&T) DN2-250D 100-250A, MTX2.0, CAT No. -CM92151OOOOAG or equivalent - 2 nos. c) MCCB, 4 Pole, ( 40 - 160)Amp, 415V, 50Hz, 36kA, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model : LK (L&T) DZ1-160D 40-160 A, iTRP3, CAT No. - DZ1F0160DXH1A or equivalent - 2 nos. d) MCCB, 4 Pole, ( 25 - 100 )Amp, 415V, 50Hz, 36kA, Microprocessor based release for O/L, S/C, E/F & Neutral protection Model : LK (L&T) DZ1-160D25-100 A, iTRP3, CAT No. -DZ1F0100DXH1A or equivalent - 6 nos. e) MCCB, 4 Pole, 400 Amp, 415V, 50Hz, 36kA, without protection release, used as buscoupler isolation. Model : LK (L&T) DN3B-400SD - 400 A, CAT No. -CM98412OOROOG or equivalent - 1 no. f) RCBO, 4 Pole, 32 Amp, 415V, 50Hz, 10kA, Sensitivities -300mA, Suitable for AC +Pulsating DC (Type A) +Harmonics - 4 nos. g) RCBO, 4 Pole, 63 Amp, 415V, 50Hz, 10kA, Sensitivities - 300mA, Suitable for AC + Pulsating DC (Type A) +Harmonics - 6 nos. h) Tinned Copper Busbar (4 Bar) each of capacity 600 Amps., 415V, 50Hz. - 1 set. i) Static Multifunction panel mounting Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Accuracy CL1 and RS485 Communication port Model : LK (L&T) MFM 4410, CAT No.-WL441011OOOO or equivalent - 12 nos. j) CT of suitable ratio for MFM - 36 nos. k) LED indication lamp for 3-Phases for incoming feeders and ""ON, OFF & TRIP"" indication for all incoming and outgoing feeders - 64 nos. l) Petty Store for control cable, MCBs, gland, socket, fuse, push button,TNC switch, selector switch, rotary handle operating mechanism, spreader terminals, interlocking arrangement, auxiliary contacts, shunt release, terminal blocks & NO/NC relays etc.- 1 job m) Fabrication work for above panel - 1 job. complete with internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade."( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S ) | — | 2.00 | — | — | |
| — | — | — | 77,712 | ||
| Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories | — | 2.00 | — | — | |
| — | — | — | 2,22,304 | ||
| Supply of cubicle LT panel boards, made of 14 SWG (2mm) MS sheet duly powder coated for APFC Capacitor Bank consisting with the following : a) Super Heavy Duty Capacitor ( MPP ) suitable for 3 Ph, 440V, 50 Hz supply system (25 KVAR x 4 nos.) - 100 KVAR b) Power Factor Controller similar to EPCOS Model No. BR 6000 series or equivalent including CT's - 1 no. c) Capacitor Contactor suitable for operation on 3 Ph, 440V, 50 Hz supply system suitable for 25 KVAR capacitor - 4 nos. d) MCCB, TP, 320-400A, 415V, 50 Hz, 50 kA - 1 no. Complete with CTs, Ammeter, Voltmeter, Selector Switches for ammeter and voltmeter, LED indication lamps for Phases and ON / OFF indication for breaker including fabrication and copper banking ( Make for Capacitor - EPCOS / ABB / Siemens / Keltron / Havells / Alcon / Usha ) ( Make for Power Factor Controller and Contactor etc. - LK (L&T) / Siemens / ABB / Schneider / EPCOS ) ( Make for MCCB etc. - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Meters - Secure / LK (L&T) / Genus / Conzerv / Selec / Rishabh / Socomec / C&S ) | — | 2.00 | — | — | |
| — | — | — | 11,116 | ||
| Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories | — | 2.00 | — | — | |
| — | — | — | 8,000 | ||
| Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut- bolts and commissioning of cable ( Cable will be supplied by Railway ) | — | 200.00 | — | — | |
| — | — | — | 93,600 | ||
| Trenching and laying of cable underground by pucca floor / concrete cutting with covering of cable through suitabe dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN-10 or higher) along with refilling the trench and make good of surface as its original condition ( Cable will be supplied by Railway ) | — | 400.00 | — | — | |
| — | — | — | 1,67,200 | ||
| Trenching and laying of cable under ground by soil cutting through suitable dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN-10 or higher) alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway ) | — | 1100.00 | — | — | |
| — | — | — | 1,50,000 | ||
| Laying of cable underground through 100 mm diameter HDPE pipe by Micro Tunneling cable laying method including supply and jointing of HDPE pipe (PE-100 grade, PN-10 or higher). ( Cable will be supplied by Railway ) | — | 100.00 | — | — | |
| — | — | — | 8,500 | ||
| Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) | — | 100.00 | — | — | |
| — | — | — | 49,210 | ||
| Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable through 80mm dia GI pipe including supply of GI pipe alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) | — | 70.00 | — | — | |
| — | — | — | 47,500 | ||
| Trenching, laying under road / track through 100 mm dia GI pipe ( medium gauge ) including supply of GI pipe and commi- ssioning of cable including back filling of trench with excavated soil after laying of cable ( Cable will be supplied by Railway ) | — | 100.00 | — | — | |
| — | — | — | 8,650 | ||
| Drawing of cable through one no. 2" dia, 3.0 Mtrs. long GI pipe ( Make - Tata / Jindal / Bansal ) for protection of cable on pole with proper GI clamps and GI nuts & bolts including supply of GI pipe ( Cable will be supplied by Railway ) | — | 10.00 | — | — | |
| — | — | — | 5,374 | ||
| Supply of Straight Through jointing kits ( Heat shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 4 / 3.5 x 50-95 sq.mm., 1100V grade complete with all accessories including jointing, testing and commissioning. ( Make - m-seal / Raychem / Mahindra / Densons / 3M / Polycab ) | — | 2.00 | — | — | |
| — | — | — | 3,244 | ||
| Supply of Straight Through jointing kits ( Heat shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 4 / 3.5 x 120-185 sq.mm., 1100V grade complete with all accessories including jointing, testing and commissioning. ( Make - m-seal / Raychem / Mahindra / Densons / 3M / Polycab ) | — | 1.00 | — | — | |
| — | — | — | 3,788 | ||
| Supply of Straight Through jointing kits ( Heat shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 4 / 3.5 x 225-300 sq.mm., 1100V grade complete with all accessories including jointing, testing and commissioning. ( Make - m-seal / Raychem / Mahindra / Densons / 3M / Polycab ) | — | 1.00 | — | — | |
| — | — | — | 21,112 | ||
| Supply of Straight Through jointing kits ( Heat shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 4 x 400 sq.mm., 1100V grade complete with all accessories including jointing, testing and commissioning. ( Make - m-seal / Raychem / Mahindra / Densons / 3M / Polycab ) | — | 4.00 | — | — | |
| — | — | — | 51,830 | ||
| Supply of Straight Through jointing kits ( Heat shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 3 x 120-150 sq.mm., 11 KV grade complete with all accessories including jointing, testing and commissioning. ( Make - m-seal / Raychem / Mahindra / Densons / 3M / Polycab ) | — | 2.00 | — | — | |
| — | — | — | 20,980 | ||
| Supply of Indoor End Termination jointing kits ( Heat shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 3 x 120-150 sq.mm., 11 KV grade complete with all accessories including jointing, testing and commissioning. ( Make - m-seal / Raychem / Mahindra / Densons / 3M / Polycab ) | — | 2.00 | — | — | |
| — | — | — | 38,000 | ||
| Releasing of old, unused LT cables of various sizes. | — | 1000.00 | — | — | |
| — | — | — | 24,800 | ||
| Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 200.00 | — | — | |
| — | — | — | 87,000 | ||
| Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 600.00 | — | — | |
| — | — | — | 61,200 | ||
| Wiring of Light / Fan / Call Bell / Glow Sign point by 4 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for 03 phases and 01 neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 400.00 | — | — | |
| — | — | — | 19,856 | ||
| Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 68.00 | — | — | |
| — | — | — | 1,630 | ||
| Wiring of 6A / 3 pin Plug board consisting with one plug socket and one 6A switch by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 10.00 | — | — | |
| — | — | — | 3,080 | ||
| Wiring of 6/16A 3 pin Plug board consisting with one 16/6A 3 pin plug socket and one 16A switch by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 8.00 | — | — | |
| — | — | — | 13,600 | ||
| Wiring of Submain by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 200.00 | — | — | |
| — | — | — | 49,600 | ||
| Wiring of Mainline by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 6.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 400.00 | — | — | |
| — | — | — | 46,400 | ||
| Wiring of Mainline by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 10 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 200.00 | — | — | |
| — | — | — | 1,50,000 | ||
| Wiring of Mainline by 4 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 10 sq.mm, 1100V grade for 03 phases and 01 neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) | — | 200.00 | — | — | |
| — | — | — | 5,246 | ||
| Extra cost for conceal wiring in respect to PVC conduit / casing for light, fan, plug, power plug, multi-plug point etc. including make good of wall surface as its original condition | — | 86.00 | — | — | |
| — | — | — | 19,000 | ||
| Extra cost for conceal wiring for main / submain with respect to PVC conduit / casing including make good of wall surface as its original condition | — | 1000.00 | — | — | |
| — | — | — | 11,172 | ||
| Extra cost involvement for modular switch, bell push, plug socket, fan regulator, USB point, TV socket etc. with other accessories ( Make of Modular switch, socket, box, cover plate etc. - ABB / Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 114.00 | — | — | |
| — | — | — | 2,664 | ||
| Fixing, connection, testing and commissioning of indoor LED luminaire fittings with suitable arrangement. ( LED indoor light fitting will be supplied by Railway ) | — | 36.00 | — | — | |
| — | — | — | 1,040 | ||
| Fixing, connection and commissioning of BLDC Ceiling fan with suitable size GI clamps made of GI flat and GI nut-bolts. ( BLDC Ceiling Fan will be supplied by Railway ) | — | 20.00 | — | — | |
| — | — | — | 5,520 | ||
| Supply of Down Rod made of heavy gauge GI pipe of size 20mm dia for suspension of ceiling fan. ( Make - TATA / Jindal / Bansal ) | — | 30.00 | — | — | |
| — | — | — | 660 | ||
| Fixing, connection and commissioning of AC Exhaust Fan with suitable size and shape GI clamps / GI nut & bolts including necessary masonry work ( AC Exhaust Fan will be supplied by Railway ) | — | 4.00 | — | — | |
| — | — | — | 292 | ||
| Installation, connection and commissioning of Wall Bracket fan with GI clamps made of GI flat of suitable size and GI nut-bolts on wall / structure. ( Wall Bracket Fan will be supplied by Railway ) | — | 4.00 | — | — | |
| — | — | — | 1,182 | ||
| Installation, connection and commissioning of Air Circulator Bracket fan with GI clamps made of GI flat of suitable size and GI nut-bolts on wall / structure. ( Air Circulator Bracket Fan will be supplied by Railway ) | — | 6.00 | — | — | |
| — | — | — | 47,694 | ||
| Supply of TPN MCB DB ( Heavy duty, Outdoor type, UV ray protected, self fire- extinguishing and resistant to abnormal heat and fire up to 650 degree C GWT, shock resistance IK08 or above and IP65 degree of protection grade transparent DB box, similar to ABB Mistral65 - 20 Modules or equivalent ), 3Ph, 50Hz, 415V, 4 way per phase, 415V, 50Hz, complete with total 12 nos. SP MCB of current rating from 6A to 32A, 10 kA, 240 Volt, 50Hz per phase as per requirement of load and one no. FP RCBO 63A, 300mA, 10 kA, 415V, 50Hz, Suitable for AC + Pulsating DC (Type A) + Harmonics ( Make of MCB & RCBO - LK (L&T) / Siemens / ABB / Hager Legrand / Schneider ) ( Make of TPN DB - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / Spelsberg / Hensel / Eaton ) | — | 3.00 | — | — | |
| — | — | — | 411 | ||
| Fixing, connection, testing and commissioning of above TPN MCB DB including all incoming and outgoing cables glanding, cable connection with cable termination and suitable wall hanging arrangement as per site condition with all associated accessories. | — | 3.00 | — | — | |
| — | — | — | 48,005 | ||
| Supply of SPN DB ( Metal Enclosure with Metal Door ), 14 way, 50Hz, complete with 10 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 63A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) | — | 5.00 | — | — | |
| — | — | — | 13,602 | ||
| Supply of SPN DB ( Metal Enclosure with Metal Door ), 10 way, 50Hz, complete with 6 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) | — | 2.00 | — | — | |
| — | — | — | 847 | ||
| Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. | — | 7.00 | — | — | |
| — | — | — | 12,24,335 | ||
| Supply of LT 6 Way VTPN/ SMDB Wall Mounted Double Door Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder comprising with the following items :- a) MCCB, 4 Pole, ( 40 - 100 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt Ground Fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memorry, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication - 1 no. b) MCCB, 4 Pole, ( 25 - 63 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release with above mentioned features in (a) - 4 nos. c) RCBO, 2 Pole, 10 Amp, 240V, 50Hz, 10kA, Sensitivities - 300 mA - 4 nos. d) Tinned Copper Busbar (4 Bar) each of capacity 200 Amps., 415V, 50 Hz - 1 set e) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 5 nos. f) CT of suitable ratio for MFM - 15 nos. g) LED indication lamp for 3-Phases for incoming feeders and "ON, OFF & TRIP" indication for all incoming and outgoing feeders - 26 nos. h) Petty Store for control cable, MCBs, gland, socket, fuse, push button, spreader terminals, auxiliary contacts, shunt release, terminal blocks etc. - 1 job. i) Fabrication work for above panel - 1 job. complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - Secure / LK (L&T) / Genus / Conzerv / Stelmec / HPL / Socomec / Anchor / C&S ) | — | 5.00 | — | — | |
| — | — | — | 61,215 | ||
| Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. | — | 5.00 | — | — | |
| — | — | — | 3,27,844 | ||
| Supply of LT Wall Mounted/ Floor Mounted Double Door Cubical Outdoor type Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder comprising with the following items for 100 KVA to 125 KVA Load :- a) MCCB, 4 Pole, ( 40 - 160 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release similar to iTRP3 type of LK (L&T)-make or equivalent with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt Ground Fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memorry, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication - 2 nos. b) MCCB, 4 Pole, ( 25 - 100 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release similar to iTRP3 type of LK (L&T)-make or equivalent with above mentioned features - 4 nos. c) MCCB, 4 Pole, 160 Amp, 415V, 50Hz, 36kA, without protechtion release, used as bus coupler isolation - 1 no. d) RCBO, 4 Pole, 32 Amp, 415V, 50Hz, 10kA, "Sensitivities - 300 mA , Suitable for AC + Pulsating " DC (Type A) + Harmonics - 2 nos. e) RCBO, 4 Pole, 63 Amp, 415V, 50Hz, 10kA, "Sensitivities- 300 mA , Suitable for AC + Pulsating " DC (Type A) + Harmonics - 4 nos. f) Tinned Copper Busbar (4 Bar) each of capacity 300 Amps., 415V, 50 Hz. - 1 set. g) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 communication port having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 6 nos. h) CT of suitable ratio for MFM - 18 nos. i) LED indication lamp for 3-Phases for incoming feeders and "ON, OFF & TRIP" indication for all incoming and outgoing feeders - 38 nos. j) Petty Store for control cable, MCBs, gland, socket, fuse, push button, TNC switch, selector switch, rotary handle operating mechanism, spreader terminals, interlocking arrangement, auxiliary contacts, shunt release, terminal blocks & NO/NC relays etc. - 1 job. k) Fabrication work for above panel including internal wiring - 1 job. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - Secure / LK (L&T) / Genus / Conzerv / Stelmec / HPL / Socomec / Anchor / C&S ) | — | 1.00 | — | — | |
| — | — | — | 16,393 | ||
| Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. | — | 1.00 | — | — | |
| — | — | — | 48,911 | ||
| Dismantling, Shifting, reinstallation, testing and commissioning of existing LT/HT distribution panel board / Transformer including all incoming and outgoing cable connection. | — | 1.00 | — | — | |
| — | — | — | 1,22,830 | ||
| Sub-station earth by supply, digging and insertion of earth pipe made of heavy gauge GI pipe of size 50 mm dia x 3 mtrs.long ( Make - Tata / Jindal / Bansal ) including construction of total 4 nos. earth pit as per Sr.DEE/G/E.Rly/HWH's drg. no. Misc./ 10/Rev. Each earth pit provided with 3 nos. of above pipe duly sorted by GI strip of size 50 mm x 6 mm including necessary earth connection from pit to CSS / HT / LT panel board / transfor- mers etc. by GI strip of size 50mm x 6mm with GI nuts & bolts. | — | 5.00 | — | — | |
| — | — | — | 60,589 | ||
| Supply of Gl Flat for Earth Bus including connection from "earth pit and fixing and commissioning on Sub-station " building wall by Gl nut-bolts and washer with supporter for earthing of HT and LT equipments | — | 1.00 | — | — | |
| — | — | — | 24,870 | ||
| Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed ) | — | 10.00 | — | — | |
| — | — | — | 19,76,015 | ||
| Goods & Services Tax ( at present @ 18% ) | — | 1.00 | Lumpsum | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
AnnexureVIB.pdf
ATTACHMENT
Drg.No.-MISC-10-REV2.pdf
ATTACHMENT
Annexure-VA_1.pdf
ATTACHMENT
DetailTechnicalSpecificationTC3583_1.pdf Detailed Technical Specification
ATTACHMENT
TenderFormandAnnexuresnew_1.pdf
ATTACHMENT
Advancecorrectionslips_1.pdf
ATTACHMENT
GCC_April-2022_1.pdf
ATTACHMENT
TenderBooklet_1.pdf
ATTACHMENT
HTLTstandardspecification_1.pdf
ATTACHMENT
3583Clause_1.pdf
ATTACHMENT
DetailTechnicalSpecificationTC3583_1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .