Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.6 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹48.8 L+₹15.2 L (45.2%)Admitted-Finance 0 BETTER POWER SERVICES PVT LTD A K AZAD ROAD REHABARI KAMRUP ASSAM 781008 | KAMRUP METRO | ASSAM | 781008 | L2 | Admitted-Finance | |
| 3 | Rejected-Technical | - | Rejected-Technical Dis Qualified | |
| 4 | Rejected-Technical | - | Rejected-Technical Dis Qualified | |
| 5 | Rejected-Technical 953 16TH CROSS 1ST PHASE 1ST STAGE CHANDRA LAYOUT BANGALORE KARNATAKA 560072 | BENGALURU URBAN | KARNATAKA | 560072 | - | Rejected-Technical Dis Qualified |
| Sl No | Description | Qty | Unit | BETTER POWER SERVICES PVT. LTD. L2 | MARSUN POWER SYSTEMS L1 |
|---|---|---|---|---|---|
| 1.00BATTERIES | |||||
| 1.01Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 120Ah Sealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT, • Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities. Each module shall have a rated capacity of 120Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applications Installation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices. Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA) Nominal Voltage : 12V Battery Rating / Capacity : 12V-120 AH to 1.75 ECV @ C20 at 27°C. Float charging voltage : ≥13.5 volts per module @ 27°C. Boost charging voltage : ≥13.8 volts per module @ 27°C Current limit : 12 Amps Minimum to 6.5 Amps Maximum. Voltage ripple allowable : < 2% of the RMS. Value AH efficiency : Above 95% WH efficiency : Above 85% Operating Temperature Range of Battery : -20°C to +60°C Self-Discharge/Week : < 1% of rated capacity. | |||||
| 1.02Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C : Life of battery at 27 deg c1150 to 1300 cycles at 30 % DOD (OR) 550 to 650 cycles at 50 % DOD (OR) 370 to 450 cycles at 80 % DOD.Batteries generally conform to : JIS 8702C international standard.Internal Resistance (IR) : Approx. 9.8 mΩ for a fully charged battery (27°C). Short Circuit Current (As per IEC) : 1278A,Operating Temp. range : -20°C to +60°C (50 to 60°C for shorter duration),Nominal Operating Temp. range : 27°C ±3°C, Standby use (27°C) : Charging Voltage ≥13.5 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±18mV/battery/°C, Cyclic use (27°C) : Charging Voltage ≥13.8 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±30mV/battery/°C. Design Float life of upto 10 years. The entire battery unit should have minimum of 2 year Warranty. Schedule of Batteries: 1. VVF Block(88 nos), 2. Admin Block(88 nos) Buyback of old used 12V 120 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries. | |||||
| 1.03 | 12 V 120 AH | 176 | No | 8,340 ₹14,67,840 | 7,500 ₹13,20,000 Lowest |
| 1.04Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 100Ah Sealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT, • Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities. Each module shall have a rated capacity of 100Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applications Installation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices. Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA) Nominal Voltage : 12V Battery Rating / Capacity : 12V-100 AH to 1.75 ECV @ C20 at 27°C. Float charging voltage : ≥13.5 volts per module @ 27°C. Boost charging voltage : ≥13.8 volts per module @ 27°C Current limit : 12 Amps Minimum to 6.5 Amps Maximum. Voltage ripple allowable : < 2% of the RMS. Value AH efficiency : Above 95% WH efficiency : Above 85% Operating Temperature Range of Battery : -20°C to +60°C Self-Discharge/Week : < 1% of rated capacity. | |||||
| 1.05Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C : Life of battery at 27 deg c: 1150 to 1300 cycles at 30 % DOD (OR) 550 to 650 cycles at 50 % DOD (OR) 370 to 450 cycles at 80 % DOD.Batteries generally conform to : JIS 8702C international standard.Internal Resistance (IR) : Approx. 9.8 mΩ for a fully charged battery (27°C). Short Circuit Current (As per IEC) : 1278A,Operating Temp. range : -20°C to +60°C (50 to 60°C for shorter duration),Nominal Operating Temp. range : 27°C ±3°C, Standby use (27°C) : Charging Voltage ≥13.5 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±18mV/battery/°C, Cyclic use (27°C) : Charging Voltage ≥13.8 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±30mV/battery/°C. Design Float life of upto 10 years. The entire battery unit should have minimum of 2 year Warranty. Schedule of Batteries: 1. RABIES Block(44 nos) 2. ANIMAL HOUSE (32 nos) 3. BCG BLOCK (44 nos) Buyback of old used 12V 100 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries. | |||||
| 1.06 | 12 V 100 AH | 120 | No | 6,625 ₹7,95,000 | 5,800 ₹6,96,000 Lowest |
| 1.07Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 26Ah Sealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT, • Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities. Each module shall have a rated capacity of 26Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applications Installation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices. Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA) Nominal Voltage : 12V Battery Rating / Capacity : 12V-26 AH to 1.75 ECV @ C20 at 27°C. Float charging voltage : ≥13.5 volts per module @ 27°C. Boost charging voltage : ≥13.8 volts per module @ 27°C Current limit : 2.6 Amps Minimum to 6.5 Amps Maximum. Voltage ripple allowable : < 2% of the RMS. Value AH efficiency : Above 95% WH efficiency : Above 85% Operating Temperature Range of Battery : -20°C to +60°C Self-Discharge/Week : < 1% of rated capacity. | |||||
| 1.08Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C .Cycle Life of battery at 27°C : 4000 cycles at 20% Depth of Discharge(DOD) (or)2000 cycles at 50% DOD (or)1200 cycles at 80% DOD. Design Float life of upto 20 years The entire battery unit should have minimum of 2 year Warranty. Schedule of Batteries: 1. UTILITY Block(34 nos) 2. MRS SUBSTATION (34 nos) 3. CENTRAL LAUNDRY(34 nos) ; 4 Secondary packing(34 nos) Buyback of old used 12V 26 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries. | |||||
| 1.09 | 12 V, 26 AH | 136 | No | 2,150 ₹2,92,400 | 1,975 ₹2,68,600 Lowest |
Tender Value
₹41.8 L
EMD Value
₹1.0 L
Closing Date
4 Feb 2026, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
DEPUTY GENERAL MANAGER
Integrated vaccine complex, Survey no 192 and 195, Meleripakkam village, Chengalpattu - 603003
Supply, Installation, Testing and Commissioning of Batteries and UPS Service at HLL Biotech Limited, Chengalpattu, Tamil Nadu
2026_HBL_261748_2
HBL/BTY/UPS/SER/CPT/25-26
Open Tender
Electrical Works
Item Rate
25 days
HBL Chengalpattu
Please refer Tender documents.
18 documents required · 18 mandatory
₹2,950
Yes
HLL Biotech Limited
₹1.0 L
Yes
ONLINE
17 Feb 2026
23 Jan 2026
5 Feb 2026
23 Jan 2026
4 Feb 2026
23 Jan 2026
30 Jan 2026
BATTERIES
Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 120Ah Sealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT, • Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities. Each module shall have a rated capacity of 120Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applications Installation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices. Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA) Nominal Voltage : 12V Battery Rating / Capacity : 12V-120 AH to 1.75 ECV @ C20 at 27°C. Float charging voltage : ≥13.5 volts per module @ 27°C. Boost charging voltage : ≥13.8 volts per module @ 27°C Current limit : 12 Amps Minimum to 6.5 Amps Maximum. Voltage ripple allowable : < 2% of the RMS. Value AH efficiency : Above 95% WH efficiency : Above 85% Operating Temperature Range of Battery : -20°C to +60°C Self-Discharge/Week : < 1% of rated capacity.
Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C : Life of battery at 27 deg c1150 to 1300 cycles at 30 % DOD (OR) 550 to 650 cycles at 50 % DOD (OR) 370 to 450 cycles at 80 % DOD.Batteries generally conform to : JIS 8702C international standard.Internal Resistance (IR) : Approx. 9.8 mΩ for a fully charged battery (27°C). Short Circuit Current (As per IEC) : 1278A,Operating Temp. range : -20°C to +60°C (50 to 60°C for shorter duration),Nominal Operating Temp. range : 27°C ±3°C, Standby use (27°C) : Charging Voltage ≥13.5 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±18mV/battery/°C, Cyclic use (27°C) : Charging Voltage ≥13.8 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±30mV/battery/°C. Design Float life of upto 10 years. The entire battery unit should have minimum of 2 year Warranty. Schedule of Batteries: 1. VVF Block(88 nos), 2. Admin Block(88 nos) Buyback of old used 12V 120 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries.
Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 100Ah Sealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT, • Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities. Each module shall have a rated capacity of 100Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applications Installation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices. Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA) Nominal Voltage : 12V Battery Rating / Capacity : 12V-100 AH to 1.75 ECV @ C20 at 27°C. Float charging voltage : ≥13.5 volts per module @ 27°C. Boost charging voltage : ≥13.8 volts per module @ 27°C Current limit : 12 Amps Minimum to 6.5 Amps Maximum. Voltage ripple allowable : < 2% of the RMS. Value AH efficiency : Above 95% WH efficiency : Above 85% Operating Temperature Range of Battery : -20°C to +60°C Self-Discharge/Week : < 1% of rated capacity.
Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C : Life of battery at 27 deg c: 1150 to 1300 cycles at 30 % DOD (OR) 550 to 650 cycles at 50 % DOD (OR) 370 to 450 cycles at 80 % DOD.Batteries generally conform to : JIS 8702C international standard.Internal Resistance (IR) : Approx. 9.8 mΩ for a fully charged battery (27°C). Short Circuit Current (As per IEC) : 1278A,Operating Temp. range : -20°C to +60°C (50 to 60°C for shorter duration),Nominal Operating Temp. range : 27°C ±3°C, Standby use (27°C) : Charging Voltage ≥13.5 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±18mV/battery/°C, Cyclic use (27°C) : Charging Voltage ≥13.8 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±30mV/battery/°C. Design Float life of upto 10 years. The entire battery unit should have minimum of 2 year Warranty. Schedule of Batteries: 1. RABIES Block(44 nos) 2. ANIMAL HOUSE (32 nos) 3. BCG BLOCK (44 nos) Buyback of old used 12V 100 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries.
Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 26Ah Sealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT, • Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities. Each module shall have a rated capacity of 26Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applications Installation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices. Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA) Nominal Voltage : 12V Battery Rating / Capacity : 12V-26 AH to 1.75 ECV @ C20 at 27°C. Float charging voltage : ≥13.5 volts per module @ 27°C. Boost charging voltage : ≥13.8 volts per module @ 27°C Current limit : 2.6 Amps Minimum to 6.5 Amps Maximum. Voltage ripple allowable : < 2% of the RMS. Value AH efficiency : Above 95% WH efficiency : Above 85% Operating Temperature Range of Battery : -20°C to +60°C Self-Discharge/Week : < 1% of rated capacity.
Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C .Cycle Life of battery at 27°C : 4000 cycles at 20% Depth of Discharge(DOD) (or)2000 cycles at 50% DOD (or)1200 cycles at 80% DOD. Design Float life of upto 20 years The entire battery unit should have minimum of 2 year Warranty. Schedule of Batteries: 1. UTILITY Block(34 nos) 2. MRS SUBSTATION (34 nos) 3. CENTRAL LAUNDRY(34 nos) ; 4 Secondary packing(34 nos) Buyback of old used 12V 26 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries.
Supply, Transportation, Unloading , installation, testing & Commissioning of 2 Volt, 100Ah Sealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for 110 V DC Battery Charger, conforming to relevant international standards including rack and Connectors.. • IS15549:2005 • IEEE1188 & 1189 • BS-6290, Part-IV • IEC 60896 -21 & 22 :2004, Part – II. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities. Each module shall have a rated capacity of 100Ah to 1.75 ECV @ C10 at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applications. Installation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices. Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA) Nominal Voltage : 2V Battery Rating / Capacity : 110V / 100 AH to 1.75 ECV @ C10 at 27°C. Float charging voltage : ≥2.23 - 2.25 Volts per Cell @ 27°C. Boost charging voltage : ≥2.30 - 2.32 Volts per Cell @ 27°C Current limit : 10 Amps Minimum to 20 Amps Maximum. AH efficiency : Above 95% WH efficiency : Above 85% Operating Temperature Range of Battery : -20°C to +60°C Self-Discharge/Week : < 1% of rated capacity.
Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Voltage ripple allowable : <2% of the RMS. Value. Life of battery at 27°C :Life of battery at 27 deg c Cycle Life of battery at 27°C : 4000 cycles at 20% Depth of Discharge(DOD) 80% DOD(OR) 370 to 450 cycles at 80 % DOD.Batteries generally conform to : JIS 8702C international standard.Internal Resistance (IR) : Approx. 9.8 mΩ for a fully charged battery (27°C). Short Circuit Current (As per IEC) : 1278A,Operating Temp. range : -20°C to +60°C (50 to 60°C for shorter duration),Nominal Operating Temp. range : 27°C ±3°C, Standby use (27°C) : Charging Voltage ≥13.5 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±18mV/battery/°C, Cyclic use (27°C) : Charging Voltage ≥ 13.8 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±30mV/battery/°C. Design Float life of upto 10 years. The entire battery unit should have minimum of 2 year Warranty. Schedule of Batteries: 1. Utility Substation (55 nos) with rack 2. Rabies Substation (55 nos) with rack 3. VVF Substation (55 nos) with rack 4. BCG Substation (55 nos) with rack Buyback of old used 2V 100 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries.
Comphrensive, Service, Repair and Maintenance of 10 KVA Emerson make UPS system including required parts, not limited to (DC TO DC PCB, SCR DRIVE PCB-3NOS, IGBT-3NOS, SCR-3NOS, MICRON PCB-1NO, DC CAPACITOR-2NOS, COMMUNICATION PCB-1NO & CONTROL, COMMUNICATION PCB-1NO & CONTROL BOARD-1NO ETC. REPLACEMENT CHARGES for complete functioning of the unit as per manufacturer's specifications and site requirements.The supplied Parts should have minimum one year warranty.Block:MAin Receiving station
Comphrensive, Service, Repair and Maintenance of 160 KVA Emerson make UPS system including required parts, not limited to, (IGBT -12NOS, FUSE-6NOS, DC CAPACITOR-10NOS, IGBT DRIVE PCB-6 nos, COMMUNICATION PCB-1NO, CONTROL BOARD-1NO & SCR-6NOS ETC. REPLACEMENT CHARGES for complete functioning of the unit as per manufacturer's specifications and site requirements.The supplied Parts should have minimum one year warranty.Block : QC Block
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.54 MB
TEDOUPS.pdf
Tender Documents • 0.53 MB
BOQ_306621.xls
BOQ • 0.46 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .