Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.5 LAccepted-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | ₹24.5 L Quoted ₹25.3 L | L1 | Accepted-AOC Lowest bidder. |
| 2 | L2₹27.3 L+₹2.0 L (7.79%)Rejected-Finance | ₹27.3 L+₹2.0 L (7.79%) | L2 | Rejected-Finance Not Lowest. |
| 3 | L3₹30.0 L+₹4.7 L (18.6%)Rejected-Finance 58 CHANDRALOK BUILDING MAYO HOSPITAL ROAD NAGPUR 440 018 | NAGPUR | MAHARASHTRA | 440018 | ₹30.0 L+₹4.7 L (18.6%) | L3 | Rejected-Finance Not Lowest. |
| 4 | L4₹31.3 L+₹6.0 L (23.5%)Rejected-Finance | ₹31.3 L+₹6.0 L (23.5%) | L4 | Rejected-Finance Not Lowest. |
| 5 | L5₹37.6 L+₹12.3 L (48.5%)Rejected-Finance | ₹37.6 L+₹12.3 L (48.5%) | L5 | Rejected-Finance Not Lowest. |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
21 Sept 2022, 6:00 pmClosed
GE Kamptee
Garrison Engineer Cantt Area Kamptee - 441001
REPAIR REPLACEMENT OT UG CABLE, MAINT AND REPLACEMENT OF LT PANEL CAPACITOR BANK AND CONNECTED ITEMS OF DISTRIBUTION SYSTEM IN GRC, NCC, APS, MH AND SUPPLY DEPOT AREA UNDER GE KMPTEE
2022_MES_547869_1
8431/E8
Open Tender
Civil Works
Item Rate
180 days
Kamptee
Class D, Cate b (i)
7 documents required · 7 mandatory
₹500
Yes
GE Kamptee
₹70,000
Yes
14 Oct 2022
26 Aug 2022
23 Sept 2022
26 Aug 2022
21 Sept 2022
9 Sept 2022
Amount
Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed . Note :- laying of cable route is same as old cable route .
Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened,PVC bedded, galvanised steel strip, electric power cables ( heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 120 sq mm, 3.5 core including testing after laid and jointed all as specified and as directed Make :- Gloster/ Polycab/Havells Note:- Excavation and earth work,cable protection shall be measured and paid separetely.
All as per item No. 2 but cable size 95 sq mm 3.5 core all as specified and as directed.
All as per item No.2 but cable size 50 sq mm 3.5 core all as specified and as directed.
All as per item No. 2 but cable size 35 sq mm 3.5 core all as specified and as directed.
All as per item No.2 but cable size 25 sq mm 3.5 core all as specified and as directed.
All as per item No. 2 but cable size 16 sq mm 4 core all as specified and as directed.
Excavation in trenches in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables,poles, stay and getting out of excavated material complete all as specified and directed
Excavation in trenches in any type of hard/dense soil/hard standing not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables,poles, stay and getting out of excavated material complete all as specified and directed
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed
Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed .
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 50mm outer diameter and 38 mm inner Diameter with IS 14930 (part 2):2001 or as latest amendment laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed Make:- Dura. Line/Tijaria/REX/Ketron
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 63 mm outer diameter and 51 mm inner Diameter with IS 14930 (part 2):2001or as latest amendment laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed Make:- Dura. Line/Tijaria/REX/Ketron
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 90 mm outer diameter and 76 mm inner Diameter with IS 14930 (part 2):2001 or as latest amendment laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed Make:- Dura. Line/Tijaria/REX/Ketron
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 120 mm outer diameter and 103.5 mm inner Diameter with IS 16285(part 2):2001 or as latest amendment laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed . Make:- Dura. Line/Tijaria/REX.
M&L for RCC Slab Type B0 (1:2:4) for cable route indicators of size Length 0.9 mtrx0.3mtrx0.065 mtr duly writing"MES LT/HT Cabe" duly painted with Weather coat paint embeded in PCC (1:4:8) under ground at depth 0.45 mtr all as directed.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 30 x 5 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40mm bore, light grade 7.5m long as applicable and as per plate No. 5 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f). 40mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
Taking out old/broken any steel/RCC pole any size and remove from site
Supply, erecting & fixing steel tubular swaged pole complete with base plate, pole cap, nut bolt washer etc 8.5 meters long type 410 SP-22 swaged poles conforming to IS 2713 (Part-I to III) 1980 all as specified including two coats of black bitumen paint through out internally and externally upto planting depth and applying two coats of aluminum paint over one coat of red oxide primer (externally) and Numbering of poles as directed including excavation /earth work, PCC (1:4:8) type D-2 using 40mm aggregate for pole foundations of size 600x600x1500mm height upto ground level and using PCC (1:2:4) B-1 for coping with size 450x450x300mm including necessary formwork complete with taking down old unserviceable pole all as specified and as directed.
Supply and fix in repairs thermoplastic cable entry junction boxes of size 250 x 220 x 135 mm and IP-65 protection level with metric knock out fixed on poles with MS clamps, nuts, bolts and washers including MCB SPN, 5-32 amps, 'C' series, breaking capacity 10 KA, 'C' curve 240 volts, 50Hz including necessary incoming and outgoing electric connection with suitable size of copper lugs etc., separate (detachable) gland plate, bakelite connector 4 way 20 amp, dust and vermin proof, front door opening with hinges and locking arrangement, complete all as specified and as directed. Make:- Sintex/Hensel or equivalent
Supply and fix in repair Heat shrinkable straight through cable jointing kit for 1100 Volts grade cable joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 to 185 Sq mm. Note :- Any Excavation and earth work ,Returning and filling, Removing involved shall be measured and paid seperatelay
All as per item No. 21 but cable size 70 - 120 sq mm cable size complete
All as per item No. 21 but cable size 25 - 50 sq mm cable size complete
Supply and fix in repair LED street light luminaires of capcity 60 watts with pressure die cast aluminium housing heat resistance toughened glass, IP 66 protection complete with driver,2.5 sqmm 2 core multistranded Aluminium wire for connection from street light fitting to OH line or junction box,and fixing accessories all as specified and as directed by Engr -In- charge Make :- Cat No. LSTP-60-CDL of CG or equiv.in Philips, Bajaj.
Supply and fix in repair LED street light luminaires of capcity 45 watts with pressure die cast aluminium housing heat resistance toughened glass, IP 66 protection complete with driver,2.5 sqmm 2 core multistranded Aluminium wire for connection from street light fitting to OH line or junction box,and fixing accessories all as specified and as directed Make :- Cat No. LSTS-45-CDL-1 of Crompton or equiv.in Philips, Bajaj.
S&F in repair LED driver for 60W LED street light fittings complete all as specified and as directed.
S&F in repair LED driver for 45W LED street light fittings complete all as specified and as directed.
Supply, install, test and commissioning of LT panel board / feeder pillar box, outdoor cubicle type, vermin proof, dust proof (of CPRI approved manufacturer), fixed on 50x50x5mm MS angle iron frame fixed 300mm above ground level and 450mm below the ground level grouted in and including PCC (1:3:6) type C1 (using 20mm grade stone aggregate) and plane made out of 3.00 mm thick CRCA sheet for both outer shell and 2.00mm hick for inner shell both side open able supported on and including ISMC 75 X 40mm powder coated steel frame and totally powder coated with epoxy siemen grey colour from inside and outside with locking arrangement and fixing arrangement i.e nuts, bolts, washers, clamps etc, with naturally air cooled epoxy insulated aluminium busbar TPN suitable for 300 Amps with detachable gland plate for incoming and outgoing cable including termination of cable ends both incoming and outgoing with sufficient working space inside complete,all control cables shall be of 2.5 Sqmm copper multi stranded conductors and shall be properly bunched with suitable size binding materials , ferruled for proper identification of colour codes and crimped with adequate size of lugs also to accommodate and consisting of the following items, all as specified and as directed . (including taking down old LT Panel) (a) Busbar chamebr for 3 phase & nuetral of capacity 300 Amps (30mm x 10mm) alumunium bus bar duly insulated, (b) Multifunctioning meter to measure Voltage, ampere, KWH, PF -1 Nos (c) one set of pilot lamp. (d) Incoming MCCB 160 amps 4 Pole 415 volts 25 KA thermal magnetic setting type- 1 Nos (e) Outgoing MCCB 63 amps 3 pole 415 volts 10 KA thermal magnetic setting - 5 Nos (f) Outgoing Type MCB 63 amps 3 Pole 415 volts 10 KA - 2 Nos
Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m complete all as specified and as directed.
Dismantling insulators any type, any size complete all as specified and as directed.
Dismantling stay assembly complete. (demolition of concrete, etc. and excavation measured separatel complete all as specified and as directed.
Dismantling of ACSR or AAC conductors complete all as specified and as directed.
S&F in repair MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA complete including enclosure where needed all as specified and as directed.
S&F in repair MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete including enclosure where needed all as specified and as directed.
S&F in repair MCCB 4 Pole, 415 V, Adjustable type, 350 Amps with breaking capacity 50 KA complete including enclosure where needed all as specified and as directed.
M&L PCC (1:2:4) with 20 mm aggregate in lintels upto 1.5m clear span, cills, steps; seismicand other similar bands,plinth courses, string courses,lacing courses, parapets andrailings upto 60 cm in height,copings, complete all as specified and as directed.
M&L PCC (1:2:4) witjh 20 mm aggregate in lintels upto 1.5m clear span, cills, steps; seismicand other similar bands,plinth courses, string courses,lacing courses, parapets andrailings upto 60 cm in height,copings, complete all as specified and as directed.
M&L Rendering 15 mm thick plaster on fair faces of brickwork or concrete sur faces in CM (1:6) all as finishing the surface complete all as specified and as directed.
S&F (in repair) Mild steel fabrication works such as angle / FI clamp, Ms pipe nuts, bolts, washers welding, bending cold or hot drilling holes for bolts in any shape and size etc including two coats of synthetic enamel paint cover a coat of red oxide primer complete all as specified and as directed.
Cleaning of sub station area by uprooting all types vegitation,shrubs,weeds,saplings and creepers of unwanted trees complete with the help of spade,axes,crowbars and other mechanical means after taking necessary electrical shutdown from concerned incharge of various sub stns of Military stn Kamptee. complete all as specified and as directed.
Trimming of tree branches touching of Over head Elecctrical Lines upto 2.5 mtr distance from conductors after taking necessary shutdown from concerned incharge all as directed . (Note : Space between poles will be measured as one unit irrespective of nos of conductors .)
M&L for Loose filling with aggregates of gauge 40 to 80 mm crushed stone back colour suitable for spreading in electrical sub stn after preparation site by removing all type of debris, removing unwanted soil, and spreading lime powdwer beneath the aggregate all as directed.
Supply and fix (in repair) bracket for street light fittings made out of 40 mm dia GI pipe of light grade 1.5 m long each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 30 x 5 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with two coat of aluminium paint over a coat of red oxide primer and fittings bracket to street light fitting including taking down old unserviceable bracket of any shape and size all as complete all as specified and as directed.
M&L for preparing surfaces of electric poles of any type of following sizes including MS cross arms, MS clamps, street light brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of primer and two coat of aluminium paint completely, alternate layer of yellow and black paint of 150 mm strip at the bottom of pole 1.5 mtr above coping with synthetic enamel paint all as specified and as directed. (Note:- Height of HT rail/ tubular poles exceeding 7.5 Mtrs upto 9.5 Mtrs above ground leval complete all as specified and as directed.
All as per item No. 44.00 above Height of steel tubular poles 7.5 Mtrs above ground level complete all as specified and as directed.
M&L for preparing surfaces of electric poles of RCC type of any sizes including MS cross arms, MS clamps, street light brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of primer and two coat of weather proof paint completely and alternate layer of yellow and black synthetic enamelled paint of 150 mm strips at the bottom of pole 1.5 mtr above coping complete all as specified and as directed.
M&L for preparing surfaces of electric TWO pole Structures of any make and height of pole up to 10 Mtrs above ground level including MS cross arms, AB Switch pipe, DO Fuse assembly,MS clamps, brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint complete all as specified and as directed.
M&L for preparing surfaces of electric Four pole Structures of any make and height of pole up to 10 Mtrs above ground level including MS cross arms, AB Switch pipe, DO Fuse assembly,MS clamps, brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint complete all as specified and as directed.
M&L for writing pole No. with letters of size 25 mm height on pole/ plate with Black synthetic enamelled paint complete all as specified and as directed.
S&F (in repair) LED under water fountain light 12 Watt, IP-67 , suitable for water fountain , colour RGBW(3 Wx12) options of remote controlled and fixing accessories complete all as specified and as directed. Make :- Cat No. SZLFFMX012 of Shakti or equiv.in Philips, Bajaj.
M&L for Spray painting to existing LT Panel of any capacity with two coats of approved colour synthetic enamel paint complete including dusting, cleaning of existing dust before applying synthetic enamel paint and writing feeder name with approved colour synthetic enamel paint complete all as specified and directed.
S&F in repair aluminium service cable PVC insulated 4.00 sqmm 2 core complete all as specified and as directed.
S&F in repair aluminium service cable PVC insulated 6.00 sqmm 2 corecomplete all as specified and as directed.
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs.78,655.00] (Note:- for item No 19 to 52) :- Writing of MES No / Pole No is essentitial in MB)
Chinmaya Enteprises
M/S. ELECTROPOWER TECHNOLOGIES
Sharma Electrical and Services
Vaidehi E Link
Bidder Name
Sharma Electrical and Services
Paragon Electrotechnics
Chinmaya Enteprises
Vaidehi E Link
M/S. ELECTROPOWER TECHNOLOGIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .