Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.0 LAccepted-AOC BIDHANPALLY P O SREEPALLY DIST PURBA BARDHAMAN PIN 713103 | SREEPALLY | PURBA BARDHAMAN | WEST BENGAL | 713103 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹9.0 L+₹6,367 (0.71%)Rejected-AOC NARAN PALLY PURBO BARDHAMAN PIN 713 101 | PURBA BARDHAMAN | WEST BENGAL | 713101 | L2 | Rejected-AOC Being L2 | |
| 3 | L3₹9.1 L+₹13,469 (1.50%)Rejected-Finance 121004 | L3 | Rejected-Finance Being L3 |
Tender Value
Refer Docs
EMD Value
₹18,000
Closing Date
19 Jul 2025, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, Bardhaman Electrical Division,
Purta Bhavan, 1st Floor, Purba Bardhaman
Electrical repairing and renovation of Galsi Fire Station under Burdwan Division West Bengal Fire and Emergency Services Purba Bardhaman
2025_WBPWD_877469_1
WBPWD/EEBED/NIQ-09/2025-26
Open Tender
Electrical Work/ Equipment
Item Rate
Purba Bardhaman
Please refer Tender documents.
3 documents required · 3 mandatory
₹18,000
20 Aug 2025
11 Jul 2025
21 Jul 2025
11 Jul 2025
19 Jul 2025
11 Jul 2025
Amount
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (upto 160A)(Make:Legrand/ABB ITUS/Schneider) 4 way [D-11/15]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment 4 way(Make:Legrand/ABB ITUS/Schneider) (For Compound Light Control) [D-10/14]
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection 80A(Make:Legrand/ABB ITUS/Schneider) [D-8/10]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. 6-32 A SP(Make:Legrand/ABB ITUS/Schneider)[D-6/7]
32A TP(Make:Legrand/ABB ITUS/Schneider)
Supplying and fixing 415V, 32A, TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(L&T / Havells / Siemens )[D-3/4a]
Supplying & Fixing steel sheet waterproof type looping cable box size 200x250x100 mm deep having 18 SWG thick comprising of one 250 V I5 A lat-kat fase unit, one No 4 way bakelite base terminal block , having lined with gasketted top cover with brass machine screws etc, earthing terminal with lug on pole near base, including S&F 40 x 6 min thick. MS clamps with bolts, nuts etc. including painting with anticorrosive paint
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire(Mk. Havells / KEI / Polycab / RR Kable) of the following sizes in rigid conduit pipe as per GS. 2x(1.5 sqmm)+1x(1.5 sqmm) (loop connection & Separate plug) [E-14/1a(i)]
Supply & Delivery of XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make Polycab / RR Kable / Gloster/Havells] 2 core 6 sq.mm (for individual run from DB to individual fittings) ,
4 cor 16 sq.mm (For VTPN & new Pump) ,
4 cor 35 sq.mm (For VTPN & new Pump) ,
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting.[F-1/2b]
Laying of cable upto 3/4 core 35 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting.[F-1/2c]
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed.[F-2/1a]
Supplying and fixing & finishing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below 4 Core 16 sqmm [F-4/7c + F-5/8b]
2 Core 6 sqmm [F-4/7c + F-5/8b]
4 Core 35 sqmm [F-4/7c + F-5/8b]
S & F 1.5 Mtrs. Long 40mm dia G.I detachable pole top arm bracket with sleeves, nuts etc as required with painting by one cote red led and one cote of synthetic enamel paint . i)single arm with 100 mm dia sleeve, set nut bolts
Supply and fixing replace 240 volt 6 A modular type switch on existing modular switch board with cover plate incl. necy connection.(Make-ABB IVIE/Crabtree/ Legrand Myrius) [E-17/3.a]
Supply and fixing 240 volt 20 /16A modular type switch on existing modular switch board with cover plate incl. necy connection.(Make-ABB IVIE/Crabtree/ Legrand Myrius) [E-17/3.b]
Supply and fixing 240 volt 6A modular type 5 pin plug socket on Existing modular Switch board with cover plate incl. necy connection.(Make-ABB IVIE/Crabtree/ Legrand Myrius) [E-17/4.a]
Supply and fixing 240 volt 20A modular type 16 pin plug socket on Existing modular Switch board with cover plate incl. necy connection.(Make-ABB IVIE/Crabtree/ Legrand Myrius) [ [E-17/4.b]
Supply and delivery of LED Tube Twin Fittings Bottom cover of the fittings should be screwed at both ends. with 2 nos. 18/20 Watt LED type tube of Polycarbonate Body with inbuilt driver and Metal Heat Sink having length 1200mm, T8, Iumen Output - Min. 2100 Lumen, Efficacy ≥116 Lumen/watt (Make: Philips / Crompton /Jaquar). [03(Three) years on-site Warranty Certificate & Test Certificate is to be provided from the Manufacturer].
Supply and delivery of LED Tube Single Fittings Bottom cover of the fittings should be screwed at both ends. with 1 no. 18/20 Watt LED type tube of Polycarbonate Body with inbuilt driver and Metal Heat Sink having length 1200mm, T8, Iumen Output - Min. 2100 Lumen, Efficacy ≥116 Lumen/watt (Make: Philips / Crompton /Jaquar). [03(Three) years on-site Warranty Certificate & Test Certificate is to be provided from the Manufacturer].
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length [C-2/17]
S&D LED type tube lamp 18/20 Watt Polycarbonate Body with inbuilt driver and Metal Heat Sink having length 1200mm, T8, Iumen Output - Min. 2100 Lumen (Make: Philips / Crompton /Wipro). [03(Three) years on-site Warranty Certificate & Test Certificate is to be provided from the Manufacturer].
S & F of B22 9 W LED Bulb. (Make:Philips/Crompton/Havells)
Supply of 240V,1-Ph., 48" (1200mm) sweep, high speed AC ceiling fan, the capacitor of fan must be P-2 type brust proof & must have safety wire directly linked from fan hook to stator of fan. including safety wire and complete with all accessories like blades, canopy, fork, rubber bush, downrod etc. [Make :Crompton Aura Prime/Orient Quaser/Usha Striker PWD](3 years warranty)
Fixing ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. (C3/21A)
Supply & Fixing of 240V, 85 W, 4 blade, 1420 rpm, 450mm (18") dia full metal body & blade Wall Bracket Air Circulator fan using Nut & bolts. (Make - EPC or eqv. Crompton / Orient/Usha )
Supply and fixing of LED Street Light fitting (230V AC, 120 Watt, 5500 - 6000K, IP 66, THD<10%, 110 Lumem/Watt, bult in 10KV SPD) Al housing, toughned glass, with all necessary connection to be fitted in the existing pole & new installation pole as per the direction of EIC. [ Make- Crompton, Cat No: TRP -411-120-57-HL2-GL-NSG/ Philips BRP033 LED120S CW MR PSU GR DX,/Jaquar][03(Three) years on-site Warranty Certificate & Test Certificate is to be provided from the Manufacturer].
Supply and fixing 40/45 watt Gate light LED decorative post top for 360 degree indirect light with, Efficacy ≥100 Lumen/watt, 4KV SPD, IP 66 protection . Resistant to impact and corrosion glarr free and better unformity.( Crompton LPTO 40 CDL M/ similar make of Philips BGP 201 LED45 CW PSU GR CPC SPD/ Jaquar) [03(Three) years on-site Warranty Certificate & Test Certificate is to be provided from the Manufacturer].
Supply and fixing of LED Highbay Light fitting (230V AC, 70 - 100Watt, 5500 - 6000K, IP 66, Efficacy ≥120 Lumem/Watt, bult in 4KV SPD) Al housing, toughned glass, with all necessary connection. Fitting must be ensure uniform light distribution. [Make: PHILIPS BY130P LED100S CW PSU GR Wb/Crompton CRP 414 180 57 SL GL NSG/Jaquar - As per choice of EIC).[03(Three) years on-site Warranty Certificate & Test Certificate is to be provided from the Manufacturer]
Supply, installation, testing and commissioning of LED illuminated sign board made of 1” x1” Iron hollow square bar with sufficient support bar in between the structure and fitted in wall with L channel and angle iron at the front side of the building. Thickness of the board in four side including 3’’ back side of the board should be covered with same ACP sheet and back portion of the board should be covered with 20 swg aluminum sheet to resist unwanted water seepage. 3 mm ACP of blue colour in the front of the structure and milky white 2.0” projected laser cut male and female acrylic letter will be fixed at the top of the ACP sheet with dark colour of acrylic sheet in side of male part to resist unwanted illumination from side of the letter. Female letter will consist of 1.5 watt sufficient Nos of water resist outdoor type LED module (make Bajaj / GE/Samsong) including supply and fixing controller in MS box outside of the structure.LED should cool milky white in colour, minimum 10000 burning hours, should have similar intensity at every point on the board, and should operate satisfactory up to 50 degree centigrade. Acrylic letter will be fixed on ACP base with such space so that all letters may read clearly from sufficient distance the four edges of the Boards should be fixed 40mmx40mm angle sheet channel with necessary steel screw .The cost including carrying (from companies work shop to site) and scaffolding charges(for 4 storied building) and painting with 2 coat of RO primer and one coat of synthetic enamel paint. The letter of following inscription below as per direction of EIC:- Tentative matter & final matter willbe approved by authority. Size- (18' x 6' = 108' sqft)
Installation of above glow sign board of size 18' x 6' on roof top by means of 4 nos 100 x 50x6 mm heavy type MS channel (12 ft long each) and a rectangular structure of size 18' x 6' with horizontal and vertical intermediate support by 50 x 50x 5 mm thick MS equal angle properly welded in rectangular manner for holding the sign board vertically and strongly on roof top. The board is supported by angle support from back side of glow sign board by 50 x 50 x 5 mm thick MS equal angle in L shaped manner. The supporting piller 4 Nos holding vertically on roof top by CC foundation structure (1:2:4) of size 3'x3'x2.5' height and back angle support by CC foundation structure (1:2:4) of size 2'x2'x2.5' height. All the CC structure should be plastered and neat finish incl. painting the total structure by two coats of anticorrossive synthetic enamel paint over one coat of red lead primer as per approved.
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe (G1/2a)
Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. (G3/5c)
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages Earth Coninuity conductor No. 8 SWG(G2/5iii)
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. [G-2/4a]
Rates to be quoted will be inclusive of all the taxes incl. GST. No other additional charges will be applicable in addition to the quoted rates.
SREE GURU ENGINEERING (BID ID -6728291)
GHOSH ENTERPRISE (BID ID -6741120)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .