| 1 | L1₹10.9 CrAccepted-AOC 2ND H NO 12 160 19 DIAMOND CHAMBERS 18TH JUNE ROAD OPP EDUCATION DEPT TISWADI PANAJI NORTH GOA GOA 403001 | PANAJI | NORTH GOA | GOA | 403001 | ₹10.9 Cr Quoted ₹9.2 Cr | L1 | Accepted-AOC Letter for commencement of work issued by concerned Divisional Engineer vide order no 3942 dt. 30-3-2026 |
| 2 | L2₹9.2 Cr+₹7.9 L (0.86%)Rejected-Finance H NO 351 F NEAR SHANTADURGA TEMPLE SHANTINAGAR AQUEM BAIXO NAVELIM GOA 403707 | NAVELIM | SOUTH GOA | GOA | 403707 | ₹9.2 Cr+₹7.9 L (0.86%) | L2 | Rejected-Finance 2ND LOWEST |
Tender Value
₹8.7 Cr
EMD Value
₹17.5 L
Closing Date
9 Mar 2026, 5:00 pmClosed
Chief Electrical Engineer
Vidyut Bhavan, Electricity Dept. Panaji
Work of Design, Supply, Erection, Testing and Commissioning of digital panels in replacement of conventional CRP Panels of 40 MVA-II (CGL) Power Transformer and 110KV Line feeders at 220 KV Ponda Substation
2026_ED_27968_1
Tender 37(2025-26)/CSC
Open Tender
Electrical Works
Percentage
365 days
Division III Ponda
Please refer Tender documents.
4 documents required · 4 mandatory
₹1,500
₹17.5 L
5th Floor, Vidyut Bhavan, Electricity Dept. Panaji
8 Apr 2026
2 Mar 2026
10 Mar 2026
2 Mar 2026
9 Mar 2026
4 Mar 2026
3 Mar 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply | - | - | - | - |
| 2 | Supply of Indoor Control & Protection Panel for 110KV Line Bay:
Supply of Control and Protection Panel for 110KV line bay- panel consisting of Simplex swing frame Panel with front glass door having PRP compliant Numerical Protection Relay(Main-I) having Protection Functions of Distance, switch onto fault, A/R,PSB, Directional & non directional overcurrent and earth fault, LBB, over/under voltage, frequency and synch. Numerical Protection Relay (Main-II) of different make having Protection Functions of Distance, switch onto fault, A/R, PSB, Directional & non directional overcurrent and earth fault, LBB, over/under voltage, frequency and synch. with 1 No of Numerical Bay Control Unit along with necessary auxiliary relays for AC/DC Supply Supervision, DC changer over, Breaker contro switch, A/R selection switch and carrier selectio switch and required FO cables, Station & Process bus level ethernet switch line interface Unit to make PRP network at both Station and process bus level. All numerical relays shall be TEC 61850-9-2LE/IEC 61850 Ed2 or IEC 61850Ed2.1 protocol compliant for sampled values streaming, At the process bus level, the PRP protocol according to the IEC 62439-3/4 shall be used, Loss of GPS input to protection system shall not result in blocking of protection functions.
(Preferred Make: Siemens, ABB/Hitachi GE) | 6 | Nos. | 49,68,319.33 | ₹2,98,09,915.98 |
| 3 | Supply of Outdoor Process Bus Interface Panel of line Bay:
Supply of Outdoor Process Bus Intertace panel for 220KV line bay consisting Simplex Panel with canopy having PRP compliant 2 nos. of Switchgear control cum merging Unit (with min. 8 CT, 8 VT, 41DI & 28DO) along with necessary FO cables, Line Interface Unit, test blocks, voltage selection relays, AC Static Tri-vector Energy Meter with DLMS compliance, Media Converter (RS485 to Fiber Optic) for Energy Meter, Auxiliary Relay for AC/DC Supervision and DC change over relay, outdoor pregerminated military grade 6core MM 50/125 um or 62/125 um glass fiber core armoured cable with HDPE pipe as required, IEC 61850 Standard Ed.2. The outdoor panel shall be made of CRCA with 3mm thick sheets for load bearing and 2mm for non-load bearing sides with minimum IP-65 and all required accessories.(Preferred Make: Siemens, ABB/Hitachi, GE) | 6 | Nos. | 20,21,817.33 | ₹1,21,30,903.98 |
| 4 | SETC of Switchgear Control cum Merging Unit ( with min 8 CT, 8VT, 41 DI & 28 DO) along with necessary FO Cables | 1 | Nos. | 6,64,877.33 | ₹6,64,877.33 |
| 5 | SETC of Numerical Distance Protection Main I having protection functions of distance, switch onto fault, A/R, PSB, Directional & Non Directional O/C & E/F, LBB, Over/Under Voltage, Frequency & Sync | 1 | Nos. | 9,83,777.33 | ₹9,83,777.33 |
| 6 | SETC of Numerical Distance Protection Main II of different make having protection functions of distance, switch onto fault, A/R, PSB, Directional & Non Directional O/C & E/F, LBB, Over/Under Voltage, Frequency & Sync | 1 | Nos. | 9,71,959 | ₹9,71,959 |
| 7 | SETC of Numerical Bay Control Unit | 2 | Nos. | 6,25,674 | ₹12,51,348 |
| 8 | SETC of Auxilliary Relay | 2 | Nos. | 59,316.67 | ₹1,18,633.34 |
| 9 | SETC of Control/Selector Switch | 2 | Nos. | 17,673 | ₹35,346 |
| 10 | SETC of Ethernet switch for Process Bus | 2 | Nos. | 6,88,518.67 | ₹13,77,037.34 |
stage.html
html • 0.04 MB
technical_28410.pdf
techsummary_28410.pdf
finance_28410.pdf
BOQ Comparative Chart
xlsx
finsummary_28410.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.22 MB
Tendernotice_2.pdf
PDF • 19.77 MB
Tendernotice_3.pdf
PDF • 4.81 MB
BOQ_28410.xls
BOQ • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .