Tender Value
₹88.0 L
EMD Value
₹1.2 L
Closing Date
10 Nov 2022, 6:00 pmClosed
SH A K SINGH SE CWE NAVY VASCO
CWE NAVY VASCO VASCO DA GAMA GOA 403802
REPAIR MAINT OF HT DISTRIBUTION NETWORK AND ALLIED WORKS AT SITE A REPAIR/MAINT INCLUDING MANNING OPERATION OF MAIN RECEIVING CUM DISTRIBUTION SUBSTATION MDSS AT NAVAL BASE KARWAR UNDER GE SB KARWAR
2022_MES_557435_1
85597/E8
Open Tender
Civil Works
Item Rate
330 days
CWE NAVY VASCO
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹1,000
Yes
GE (SB) Karwar
₹1.2 L
Yes
17 Nov 2022
13 Oct 2022
12 Nov 2022
13 Oct 2022
10 Nov 2022
27 Oct 2022
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth for laying/taking out cable and getting out in soft/loose soil all as specified and as directed.
Returning,filling in including spreading, levelling, watering and well ramming in layer not exceeding 25 cm in soft/loose soil all as specified and as directed.
Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and as directed.
Taking down carefully old unserviceable UG cable (HT) of any size from the trenches/wall/pole and keeping aside for reuse and remove the unserviceable cable from site after affording credit depending on its serviceability state including removal of brick/PCC cable cover complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for Separately
Supplying & laying in repair including testing of XLPE insulated, Earthed grade armoured, heavy duty, HT UG electric cable in ternches/wall/cable tray/saddling/GI pipe or specified as per site requirement with stranded aluminum conductor 11 KV grade of following sizes:- Note :- Excavation & earth work, sand cushioning and PCC cover for cable protection shall be measured & paid seperately
(a) 3 core 95 Sqmm
(b) 3 core 120 Sqmm
(c) 3 core 185 Sqmm
Laying only in repair including testing of serviceable, HT UG cable of following sizes obtained from item No 4 here in before all as specified and as directed. Notes : 1. Serviceable cable obtained from Sl item No 4 above shall be reused. 2. Excavation and earth work, sand cushioning, PCC cover for cable protection shall be measured and paid separately.
(a) 3 core 95 Sqmm
(b) 3 core 120 Sqmm
(c) 3 core 185 Sqmm
Supply and lay un-reinforced pre-cast concrete cable cover, class HV, type 1, flat, size 300mm x 180mm x 40mm complete all as specified and as directed.
Laying only un-reinforced pre-cast concrete cable cover, class HV, type 1, flat, size 300mm x 180mm x 40mm complete all as specified and as directed.
Supply and spread dry river sand in trenches for cable cushioning all as specified in clause 19.75 of SSR Part-I. Note:- Punned thickness of sand only shall be measured & paid.
Supply & Laying in repair GI tubing light grade of sizes 80mm dia with necessary fittings as in cable protection in trenches/fixed on wall / floor including necessary clamps bolts and nuts complete all as specified and as directed
Supply, jointing & testing in replacement of old unsv indoor end termination type heat shrinkable 11 KV HT joint kit suitable for PVC / XLPE insulated stranded aluminium conductor of size 3 core 120 Sqmm to 185 Sqmm all as specified and as directed.
Supply, jointing & testing in replacement of old unsv Indoor end termination type heat shrinkable 11 KV HT joint kit suitable for PVC / XLPE insulated stranded aluminium conductor of size 3 core 240 sqmm to 300 Sqmm all as specified and as directed.
Supply, jointing & testing in replacement of old unsv straight through type heat shrinkable 11 KV HT joint kit suitable for 3 core 120 Sqmm to 185 Sqmm PVC / XLPE insulated stranded aluminium conductor all as specified and as directed.
Supply, jointing & testing in replacement of old unsv straight through type heat shrinkable 11 KV HT joint kit suitable for 3 core 240 Sqmm to 400 Sqmm PVC / XLPE insulated stranded aluminium conductor all as specified and as directed.
S&F Danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white, with letters, figures & conventional skull & bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size,for HT 25x20 cm size all as specified & as directed.
Testing of HT/LT UG cable upto 240 Sqmm by checking the insulation resistance using 5000v / 10000v fault insulation locator tester, identify any number of cable fault in a single stretch (from source to load) having minimum length of 1500 RM and pin point the fault location complete all as specified & as directed. Note: In single stretch having minimum length 1500 RM whatsoever Nos of fault shall be paid as each job
Testing of HT/LT UG cable upto 240 Sqmm by checking the insulation resistance using 5000v / 10000v fault insulation locator tester, identify any number of cable fault in a single stretch (from source to load) having length more than 1500 RM and pin point the fault location complete all as specified & as directed. Note : In single stretch having length more than 1500 RM whatsoever Nos of fault shall be paid as each job
Supply & fix in repairs Phase indication lamp LED type of colour complete all as specified and as directed.
M&L for testing of resistance of earthpits of transformer,panels etc after testing the report shall be furnished in standard format approved by Engineer-in Charge.
M&L for Servicing /Repair to vaccum circuit breaker 11 KV rating of capacity 250MVA from HT Pannel of having current rating upto 630 Amps to 2000 Amps by replacing defective/ wornout parts, adjustment of gaps for smooth operation all as detailed below:- (a) Cleaning of VCB with air blower and removing dust particles. (b) Cleaning of insulating places of VCB by using CTC/ CRC/ Thinner as required and recommended (c) Checking the arcing contact gap of vaccum interrupter, if gap exceeds the permissible limits, readjust as recommended. (d) Cleaning the main contacts to remove carbon or any other unwanted particals if visible. (e) Dismantling and cleaning the insulated surfaces and arc barrier with CTC and CRC. (f) Checking / repair and replacement of all minor ac/dc electrical wiring for electrical/ mannual operationof HT panel loading and all others function based on the ac/dc operation of HT panel etc complete in all respect as specified (g) Checking of all nuts/ bolts springs, levers, latches, connectors etc and adjustment etc required and recommended.
(h) Recording IR Values of CTs and PTs (j) Cleaning of bus bar spout. (k) Checking of all moving parts for proper functioning of VCB and adjustment as per manufacturer recommendations. (l) Removing all the moisture content inside the VCB panel all as specified by OEM. Note :- (i) The cost of minor parts ie nuts ,bolts,spring washers,dust cover ring of isolarors contacts,clips pins for release prop,Y phase shrouded over side stop pin,and all other minor parts ie packing essentially required to make the panel dust proof shall be deemed to be included in the rate quoted by the contractor . (ii) The servicing will be carried as per norms of OEM.
S & Fixing in replacement & testing and commissioning tripping coil for operated by ac or dc supply complete with electric copper wire of suitable all as specified and directed
S & Fixing in replacement &testing and commissioning closing coil suitable for operated by ac or dc supply complete with electric copper wire of suitable all as specified and directed
S & Fixing in replacement bakelite kitkat complete with HRC fuse 2-20 amps of suitable size for HT panel grey in colour including necessary nuts for fixing in position all as specified and directed
M&L for Strip Opening the busbar of the HT 11 KV VCB panel from 800 Amps to 2000 Amps, removing the old teared/ unsv insulation from the bus bar,checking the IR value before fixing the HT sleeve and refixing the heat shrinkable insulating tape sleeve suitable for 11 kv busbar not less than 3mm thick having dielectric strength not less than 15kv/mm and HT insulation tapefor CT/ PT connection complete with a certificate from NABL lab. and checking the IR value before testing and commissioning the bus bar all as specified . Note :- Test sheet of IR value shall be submitted by the contractor, no cost extra shall be paid by the department and all testing requirement shall be borne by the contractor including transportation and T&P.
M&L for Taking out ACB of Siemens make, of capacity 800A to 2000A Amps, 3pole , 415 volts,125 KA indoor type from its sub cubicle and carrying out routine maintenance as per manufacturer maintenance manual, examine the moving isolating contacts for any discolouration, cluster contacts, remove the arc chutes, check the SMC moulding are intacts, examine the moving contacts main contacts silver tips, spring mechanism, clean all contacts with a suitable solvent and contacts regreased with HP multipurpose grease, all contacts setting checked, readjusted if required, and regreased with HP multipurpose grease, all tripping device like manual trip, under voltage, shunt trip release, over current and earth fault tripping device to be tested, readjusted and confirm all tripping device is in healthy condition, check and record IR value of ACB, with 1.1. KV LT megger calibrating ground fault / short ckt, overload relays for tripping & timing complete and rendering test report all as specified and as directed.
NOTES :- (i) The scope of work includes following :- (a) Inspection & cleaning the mechanism house (b) Operation of door interlock, interlocking plate & shutter operation inside of panel. (c) Check the Mechanical ON-OFF function, electrical & mechanical operation and damage part of VCB/ACB. (d) Re-greasing and oiling of breaker mechanism, adjustment of various mechanism setting as required, checking contact tightness, contact erosion pins, manually vaccum check of VCB/ACB. (e) Racking-Rack out operation in Test & service position of VCB/ACB trolley. (f) Megger test (IR value - 1KV / 2.5KV) E-RYB, RY-YB, BR-R'R, Y'Y, B'B. (g) CRM Test (contact resistance) of Vacuum Interrupter R, Y, B in on condition outside of panel. (h) Time test of contract pole by Test kit (in mile second). (j) Function of closing coil, Trip coil, spring charging motor, auxiliary contact, limit switches etc. (k) Checking & lubrication of various interlocks. (l) Submission of test report in standard format of vacuum circuit breaker.
(ii) Tools and plants and testing instruments required for servicing of VCB/ACB shall be arranged by the contractor. (iii) The unit rate quoted shall be deemed to include the cost of grease, lubricating material, cleaning material etc as required. (iv) After servicing, report shall be furnished in standard format approved by Engineer-in-Charge.
Supplying and laying synthetic Rubber insulated mats 3 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m. complete all as specified and as directed.
M & L for calibration of relays for primary current/voltage injection test complete for 11KV VCB panels complete all as specified and as directed.
S& Fixing in replacement & testing and commissioning of resin current transformer dual core dual ratio for protection and class I accuracy suitable for 11 KV, 100/50/5+5A of primary wound type with adjustable VA bourden and accuracy in clearing the CT wiring with primary and secondary injection kit including identification to the base and connecting links to HT/VCB to match with the existing system complete all as directed
S& Fixing in replacement & testing and commissioning of pottential transformer PT ratio 11000/110 Volts accuracy class 0.5, 50VA , indoor type , epoxy resin cast,strut type single stage suitable for power measurement, connecting to HT/VCB to match with the existing system complete all as directed
S/F in repair of fuse indoor type, 11 KV, type PTAVT, Amps 3.15, 50hz, current ratio 800-400, including removing of old unsv fuse complete all as directed and specified.
S/F in repair of 11 KV bus bar supporting spout / insulators 130 MM LONG 60 MM DIA /as per sample single pole for indoor use 400 to 800 Amp suitable for existing panel complete all as directed and specified.
M&L for repair and servicing of Automatic power factor correction panels of different capacities including complete rewiring of the APFC Panel, replacement of the auxilary contactors, three phase capacitors, indictors, damping resistors and relays and checking the serviceability of the all the components and replacement of the defective parts all as specified and directed. Note: The above quoted rate includes servicing and internal control wiring of the APFC panel and all the connected items to be fixed are to be meausured and paid seperately under relevant items as below
a) 3 Phase cylindrical shape power capacitor of capacity 30 Kvar suitable for APFC Panel all as specified and directed
b) 3 Phase cylindrical shape power capacitor of capacity 40 Kvar suitable for APFC Panel all as specified and directed
c) 3 pole power contactors for capacitor switching of power capacitors from range 30 to 40 Kvar
d) APFC 3 Phase relay suitable for APFC panel of capacity not less than 200 Kvar all as specified and directed
Supply and fixing in repair of old unsv HRC fuse assembly of any type and size all as per existing having capacity 200 Amps-400 Amps all as specified and directed.
M&L for earthing complete in repairs with galvanized steel earth plate electrode 600x600x6mm thick buried in ground vertical to a depth not less than 2.25 mtrs deep below ground level with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanized GI strip of size 32 X 6 mm and 40 mm dia bore 7.5 mtr long light grade GI protection pipe for earth strip and GI watering pipe 40 mm dia medium grade from the top edge of earth plate fixed with deep cut on one end of pipe and fix from earth plate up to one feet above ground level of other end and plugged watering pipe at top with MS cap and grouted in PCC 1:2:4 of size 30 X 30 X 30 CM etc and 15 CM alternate layer of charcoal and salt around all sides of earth plate all as shown in electric plate no 3 of SSR part I of 2009. Note :- All joints either strip to strip of strip to earth plate are fixed with welded joints.
M&L for Servicing of dry cast Transformer upto 1600KVA , 11 KV/433V by disconnecting incoming & outgoing power supply, opening up, cleaning the transformer internally & externally inspecting all the metering equipments, tightening all electrical connections checking & recording insulation resistance on both LT & HT sides, checking & recording earth resistance complete through authorised service engineer of OEM all as specified & as directed. Note:- a) The above quoted rate includes dismantling of the existing HT cable connected with the transformer and carrying out the meggering test on both HT/LT side and reconnecting the existing HT cable with the transformer. b) The above quoted rate includes all the T&P required for testing and servicing work all as specifed and direcetd. c) The above quoted rate includes all the minor parts required for the servicing i.e. Nuts and bolts, washers, cotton waste, grease etc. (d) The test certificate to be produced after carrying out the rquisite tests as specified and directed
M&L for servicing of load break switch suitable for 11KV HT by dismantling the existing cable connections with the LBS and repairing the on/off operating lever alongwith spring mechanism for charging/discharging of the breaker, cleaning of all the HT contacts with the anti corrosive liquid spay, repairing the allignment of the contcats all as specified and directed, scrapping of the old paint and painting the LBS with one coat of primer and two coats of super enamelled aluminium paint complete and writing the LBS no and loaction of the outgoing cable in english alphabetic letters all as specifed and directed by Engr-In-Charge. Note: a) All the mior parts required for the reapir of the LBS are included in the above rate b) The size and no of alphabets to be written on the LBS will be decided by the GE.
S&F DWC high density polyethelene pipes in replacement having outer dia 90/76 mm, inner as per site requirement having corrugation on the wall and plain surface on the inner wall conforming to IS: 14930(Part I & II) for protection of underground cable laid along pole/along wall/in PCC on GL/roof and including all fittings as required at site including aking down the old unserviceable complete all as specified and directed.
M&L for carrying out caliberation of HT VCB panel of capacity 1250 Amps of make: ABB after obtaining shut down from the Engr-In-Charge and disconnecting the existing incomer HT cables connected with the VCB, Caliberation of the earth fault realy and overload realy as per directions of Engr-In-Charge, checking of all alignment of VCB isolating contacts, servicing of operating mechanism including tripping and closing system of the breakers, dehydarting by spraying of anti corrosive and anti moisture liquid, decarbonising of panel by angle grinder/emery paper, bus section and circuit section incl incoming/outgoing cable and necessary HT insulation at joints, removing perished monoplus compound cleaning and reinsulating with HT taps wherever necessary with and incl replacement of worn out/defective spares like tesnion springs, tortion springs, nut bolts, washers of suitable size etc.
Note:- (i) The above quoted rate deemed to include all minor spares etc. (ii) Any burnt out/defective items like movingfixed contacts, tripping coils, earth fault realy etc will be meausured and paid seperately under appropriate items of BOQ. (iii) Spare parts required other than mentioned in here -in-after shall be deemed to be incl in the quoted rate (iv) The caliberation test certificate to be submitted after servicing & testing in presence of Engr-In-Charge.
M&L for maintenance and overhauling of 11 KV VCB including opening, checking, cleaning wih CTC, cleaning wiping of insulating components, primary & secondary circuits, spouts, busbars, supports, CT, PT,check oil for leaking, cleaning contact tips, cover the exposed portion of busbsr with HT tape & heat shrinkable sleeves, cleaning of bushes, spout insulators for visible crack, tightness old fasteners holding moving contacts, check and correct the buffer gap adjustment & mechanism settings, testing, cleaning & overhauling of complete operating mechnism for smooth functioning, checking of control panel wiring for operation and protection for tripping & closing & rectifying the defects including Deoxidizing of all electrical contacts replacement unserviceable wiring with ferrule & lugs, reassembling & testing of complete VCB all as directed. Note: (i) Required part for replacement will be measured and paid under relevant item (ii) Cost of labour & cleaning material like Urethrene, gasket remover, lubricant etc for replacement is deemed to be included in quoted rate
Supply only 24 pin plug assembly suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only cable stem article suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only contact system VD4-1250Amps (12 finger) suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only front cove/shutter assembly suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only spring drum suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only spring v4207 suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only roller chain v4208 suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only torsion spring V4710/4711 suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only Lever assembly V6014 suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only motor cut off switch suitabe for ABB HT Breakers of cap 1250 Amps 11KV
Supply only spring charging motor suitabe for ABB HT Breakers of cap 1250 Amps 11KV
M&L for supply and fixing breaker control switch (Triple-neutral-close) 4 Pole/4 Terminal 660 V AC/DC pistol grip type complete all as specified and directed by Engr-In-charge.
M&L for supply and fixing of vacuum inturupter 1250 Amps, 11 KV rating suitable for HT VCB of make ABB all as specified and directed by Engr-In-Charge.
M&L for replacement of old unsv digital voltmeter, DC, with phase range 200mv to 600V with built in resistance of size 96x96mm, accuracy class 0.5 complete all as specified and directed by Engr-In-charge.
M&L for replacement of old unsv digital ammeter, digital type, of size 96x96mm, accuracy class 0.5 complete all as specified and directed by Engr-In-charge.
M&L for replacement of old unsv earth fault and over load relay suitable for HT VCB of capacity 1250 Amps complete all as specified and directed by Engr-In-charge.
Manning and Operation
Manning and Operation of Main Receiving cum Distribution Sub Station (MDSS), 11 KV HT supply including SCADA power monitoring system for 03 (three) shifts of 8 hours each on all days including Sunday and holiday routine maintenance,checks & attending emergency breakdowns at distribution Sub Stations DSS 6, DSS 4, DSS UC and connected feeder pillars all as specified and directed by Engineer-in-Charge. The installation comprises of following equipments: (a) 11 KV, 1250 Amps,indoor type HT VCBs - 42 Nos (b) SCADA power monitoring system with one industrial PC (c) LT distribution panel board for sub station lighting & CPP motors. (d) Battery bank - 1 No (e) Ventilation system.
NOTES:- (a) Contractor shall employ One No skilled electrician/ operator having minimum ITI qualification in electrician trade from Govt recognized institute with adequate knowledge and minimum 2 years experience in Maintenance & Operation of HT & LT electrical installation in each shift of 8 hrs (total 03 shifts per day). The operator must be competent to carry out the routine maintenance of MDSS , Calibration and setting the IDMT relays and handle the power monitoring SCADA system all as directed by the Engr-in-Charge and One No helper having minimum 10th pass certificate with adequate experience in each shift of 8 hrs (total 03 shifts per day).
(b) The rate is deemed to be inclusive of maintaining necessary records and documents for operation and maint of plant specified.Contractor will maintain proper records of all kinds of daily, weekly, monthly, quarterly, half yearly, yearly or whatsoever maintenance is carried out during contract period as per format issued by Engr-in-Charge in a binded book/register and will obtain the signature of Engineer-in-Charge every fortnightly.
(c) The rate quoted deemed to include for daily routine maintenance like checking and rectification of loose connection, Cleaning of the VCB's, monitoring of the operation of relays,CT's and PT's of the VCB's and switching over of power supply from commercial to stand by DG supply in case of power failure and monitoring of the total load in VCB room. The contractor will ensure general area cleanliness and upkeep of the installation on daily basis. In case of failure, a penalty of Rs 2000/- per installation per month will be levied and recovered from dues.
(d) The Contractor shall not employ same tradesman continuously for more than 11 months.
(e) The contractor shall provide 02 uniforms to each operator & helper and design of uniform shall be got approved from Engineer-in-charge. In case contractor fails to provide the uniform, recovery @ of Rs 1200/- per uniform will be recovered.
(f) The rate quoted shall deemed to be inclusive of safety gear & required tools for minor maintenance. In case of failure to provide tools kit & safety kit (Gum boots- 02 pairs, hand gloves), a penalty of Rs 3000/- will be recovered and levied on the contractor for non compliance.
(g) In case of failure due to absence of operative staff, the contractor shall be liable to pay compensation at twice the cost of a day’s Manning & Operation derived from pro rata rate of Sch ‘A’ quoted rates
(h) The operator must be well converant with functioning of the plant and shall be competent enough to maintain the installation incl main electric panel.
(j) The contractor shall pay the wages to the Skilled operator through e payment i.e Aadhar linked bank accounts(Credit to their bank account). Engr-in-Charge shall ensure that e-payment made to Skilled operator and their wages shall not be less than minimum wages fixed by state Govt or central Govt whichever is more. Monthly e-banking statement shall be furnished by the contractor to the Engineer-in-Charge and the same shall be kept in record duly verified.
(k) It is the responsibility of contractor to deposit the employees provident fund (EPF) to the concerned authority as per the prevailing scales as laid down by the Ministry of labour for all Electrician/ operator/ helper (as applicable) and necessay proof to this regard shall be submitted to Engr-in-charge for verification and records. The quoted rate shall be deemed to be included of above provisions. In case contractor fails to produce the proof of EPF, shall be liable for action as deemed fit. Decision of GE in this regard shall be final and binding.
(l) The contracotr shall maintain all the registers under various labour law rules, 2017 and shall be produced to GE and as well as officers detailed by labour department.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .