Superintending Engineer Electricity Distribution Circle-Unnao
Quantum of works involved for minor maintenance and replacement of old and damaged Gaskets from top cover, Bushing, Radiators and other of 05 MVA power transformer No.-2 at 33/11 KV S/S Industrial Area and 05 MVA Power Transformer No.-2 at 33/11 KV
2024_MVVNL_892695_1
309/E.D.C./Unnao/2023-24
Open Tender
Electrical Works
Fixed-rate
180 days
Unnao
AS PER TENDER DOCUMENT
2 documents required · 2 mandatory
₹1,180
A/C-No.3355002101008374,IFSC-Code-PUNB0335500
₹2,000
17 Feb 2024
8 Feb 2024
15 Feb 2024
8 Feb 2024
14 Feb 2024
8 Feb 2024
Amount
Opening of H.V. side bushing connection of 05 M.V.A. transformer.
Opening of L.V. side bushing/Neutral bushing connection of 05 M.V.A. transformer.
Removing of damaged packing of H.V./L.V. & neutral side bushing and replacement with new gaskets, its fixing after proper cleaning.
Opening of radiators and repairing, fixing its with new gaskets, packing.
Replacement of complete Top cover gasket by opening of all accessories, nuts & bolts and other required to complete the work satisfactory.
Body earthing of 05 M.V.A. transformer (33 KV/11KV) by making bores including providing of 1.5"dia "A Class" Pipe and G.I. strip 50x6 mm and other required materials and works to complete the work satisfactory.
Neutral earthing of 05 M.V.A. transformer (33 KV/11KV) by making bores including providing of 1.5"dia "A Class" Pipe and G.I. strip 50x6 mm and other required materials and works to complete the work satisfactory.
Spary painting of 05 M.V.A. (33/11 KV) T/F with one coat of red oxide primer and then two coat of synthetic enemal smag gray paint of A&M/Berger/Nerolex first grade after cleaning of rust/dust and only surface including cost of all material labour and T&P.
Note:- 1. All the material provided by contractor shall be as per norms of UPPCL/RESPO. 2. One carriage including loading/unloading from dump site to pit site is included in scope of work. 3. During execution of work al risk will be of the contractor. 4. Contractor will provide al T & P, vechile and man power. 5. All the old and used material should be taken on book. 6.The quantity may be vary ± 20%.
M/S RATHORE ELECTRICALS
M/s PRAMENDRA SINGH
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .