Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.7 LAccepted-AOC MOSAT HARIPUR RD VILL P O HARIPUR DIST HOOGHLY PIN 712701 | HARIPUR | HOOGHLY | WEST BENGAL | 712701 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹25.2 L+₹50,162 (2.03%)Rejected-Finance | L2 | Rejected-Finance 2nd lowest bidder | |
| 3 | L3₹25.6 L+₹93,296 (3.78%)Rejected-Finance 90 E BECHARAM CHATTERJEE ROAD KOLKATA 700034 | KOLKATA | KOLKATA | WEST BENGAL | 700034 | L3 | Rejected-Finance 3rd lowest bidder | |
| 4 | Rejected-Technical | - | Rejected-Technical Disqualified |
Tender Value
Refer Docs
EMD Value
₹49,490
Closing Date
5 Aug 2021, 6:00 pmClosed
EE_II, Kol. South Health El. Divn.,P.W.Dte.
75 D H Road Kidderpore Kol_23
Installation Work, SITC of Air-conditioning Machines and FDA system at laboratory and library rooms at the top floor of Birla Block, Chittaranjan Seva Sadan and Sishu Sadan, Kolkata.
2021_WBPWD_336844_1
WBPWD/KSHED/Q23/21-22
Open Tender
A/C ORG
Item Rate
60 days
Kolkata
Please refer Tender documents.
2 documents required · 2 mandatory
₹49,490
O/o Exe.Engr., Kol. South Health El. Divn., PWDte.
12 Nov 2021
16 Jul 2021
9 Aug 2021
16 Jul 2021
5 Aug 2021
27 Jul 2021
26 Jul 2021
Amount
Supply & installation of required size floor-cum-wall mounting LT industrial type electrical panel made with MS structure of (50X50X6)mm MS angle, (25X5)mm MS flat, CRCA 14 SWG sheet, comprising with following electrical accessories, necessary copper wire, connection, socketing of wire/cable ends, cable end boxes (16 SWG CRCA sheet , earthing attachment & painting with powder coated paint over one coat of RO primer duly grouted on wall as per direction of EIC. (A) 415V, 200 A 4 bar BBC of 1200mm X 450mm X 300mm size made out of 14 SWG powder coated CRCA sheet with front covers fixed with 4 nos. fixing bolts in each with electrolytic tinned copper bars 4 X 20 X 5 mm with colour sleeve on bakelite insulator & front transparent fibre glass guard- 1 No. (B) 415V, 160A TPN SFU with 3 nos. 160A DIN type HRC fuses & NL in SS enclosure with suitable cable end box / throat box as incomer - 1 no. (MAKE -LT/Schneider/Legrand ) (C) 415V, 32A TPN SFU with 3 nos. 32A DIN type HRC fuses & NL in SS enclosure with suitable cable end box / throat box as outgoing - 5 Nos. (MAKE -LT/Schneider/Legrand) (D) E.I. Danger board - 1 No. (E) Digital Multifunction Meter (class 0.5) Make: L/T- 1 no (F) CT of ratio 400/5A- 3 nos. (G) R-Y-B LED indicators (Siemens) - 3 Nos.
Distribution wiring in 1.1 KV grade 2x22/0.3(1.5 sq. mm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Make -Havells/Finolex/Polycab/RR Kabel) partly in 20mm size PVC rigid conduit 'FR' (Precision MMS) [for ceiling portion only] and in 19 mm bore 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1 x 22/0.3 (1.5 sq mm) single core stranded FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Make - Legrand- Myrius) fixed on Modular GI switch board complete with 3 nos. suitable size 'Ph, N & E' copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] - Av. Run 8 Mtrs.
Supplying and fixing 2+10 way, 240 V, 10-16A per way double-door SPN MCB Distribution Board with IP-42/43 protection, fixing at flat iron frame on wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment, comprising with 1 no 40 A DP Isolator as incomer & 10 nos. 10 kA, C-curve, 6-16 A SP MCB (Make - Legrand/Schneider/ABB)
Supplying and fixing double door 415V, 16-32A per way 4 way HTPN MCB DB with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment, comprising with 63 A four pole isolator as incomer & 12 nos. 16-32 A (10KA, 'C' curve) SP MCBs as outgoing. (Make - Legrand/Schneider/ABB)
Supply & fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Make-Legrand -Myrius), 20A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & fixing 240 V, 20 A , 3 pin Modular type plug socket (Make -Legrand - Myrius) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & fixing Recessed mounting LED fittings suitable for false ceiling 2' X 2' (Philips Cat. No. RC380B LED36S-6500 G5 L60W60 PSU OD SG / Crompton LED POLARIS-II, Cat no. CCR-126-50-57-SL-NWH / Wipro, Cat no. - CRCO10S036HP57G2) with all other reqd. accessories, recessed in false ceiling and necy connection by 3 X 1.5 sq. mm PVC insulated CU wire.
Supply & fixing of Single LED Tube light fitting [Make - Philips cat no. TMC 501 P 1 x T-LED / Crompton cat no. IGP161 LT8-16] complete with 18/20 Watt LED tube lamp [Make - Philips Master LED tube model no.18W 865 T8 I 2100lm / Crompton cat no. LTT8-20 ] suspended below the ceiling with S & F 2x20mm dia EI conduit up to 25 cm long with 'L' type MS clamp and making connection as to GS.
S & F of 240 V 1200 mm (48") sweep A. C. Ceiling fan having double ball bearing, down rod, canopy, fan blades etc. complete with all accessories (without regulator) and engraving & painting the Departmental Number up to 15 digits on fan body with making necessary interconnection as required. [Make: Crompton HS Plus / USHA Striker Plus, Colour - Brown]
Supply & fixing of 240 V 400 mm (16") sweep wall mounted cabin fan with metal body, metal base & metal blade (Make – EPC Electrical Pvt. Ltd.) on wall/ceiling by S & F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S & F necessary PVC insulated 3 core flexible copper cord.
Supply & fixing 240V 230 mm (9") sweep heavy duty Exhaust Fan (Make - EPC Elect. Pvt. Ltd. / Crompton / Usha / Orient) after making hole in wall and making good damages, smooth cement finish etc. as practicable as possible, providing necessary PVC insulated wire and making connection including supply & fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long).
Distribution wiring in 1.1 KV grade single core stranded 'FR' PVC insulated & unsheathed copper wire (Havells/Finolex/Polycab/RR Kabel) of the following sizes in 20/25/32 mm size PVC rigid conduit 'FR' (Precision MMS) incl. necy. fittings as required -
2 x 22/0.3 (1.5 sq. mm) + 1 x 22/0.3 (1.5 sq. mm) ECC
2 x 36/0.3 (2.5 sq. mm) + 1 x 22/0.3 (1.5 sq. mm) ECC
2 x 84/0.3 (6 sq. mm) + 1 x 56/0.3 (4 sq. mm) ECC
4 x 84/0.3 (6 sq. mm) + 2 x 56/0.3 (4 sq. mm) in 25 mm dia for 8.5 TR AC
4 x 80/0.4 (10 sq. mm) + 2x84/0.3 (6 sq. mm) as ECC in 32 mm dia for 16.5 TR AC
Supply & Laying of 1.1 kV Gr. 4 Core 95 sq.mm XLPE/PVC insulated Ar./ Al. Cable (Make - RR Kabel / Havells / Polycab) with 2 X 10 SWG GI wire through by existing angle on wall as to G. S.
Supply & Laying of 4 core 35 sq. mm. PVC Ar./ Al. Cable (Make - RR Kabel / Havells / Polycab) with 2 X 10 SWG GI wire through by saddling system on wall and mending good the damages to original finish as to G.S.
Supply & fixing of compression type gland for 4 core 95 sq.mm PVC/Ar cable & finishing the ends with dowels solder less socket by crimping method as per GS
Supply & fixing of compression type gland for 4 core 35 sq.mm PVC/Ar cable & finishing the ends with dowells solderless socket by crimping method as per GS
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
2 x 36/0.3 (2.5 sq. mm) + 1 x 22/0.3 (1.5 sq. mm) ECC
2 x 84/0.3 (6 sq. mm) + 1 x 56/0.3 (4 sq. mm) ECC
4 x 84/0.3 (6 sq. mm) + 2 x 56/0.3 (4 sq. mm) in 25 mm dia for 8.5 TR AC
4x80/0.4 (10 sq. mm) + 2x84/0.3 (6 sq. mm) as ECC in 32 mm dia for 16.5 TR AC
Supply, Installation, Testing & Commissioning of Floor Mounted Air Cooled Packaged Unit with Hermetically sealed Twin Rotary Compressor should be present in indoor unit, flow of refrigerant with Scroll Compressor with Accurate temperature control, High reliability, Quick initial cooling, Better humidity control, quiet operation of system. Outdoor Unit will be Air cooled FTHX & Blue fins condenser with Corrosion resistant body, Propeller type Fan with motor. System must be designed to operate under voltage range from 360V to 440V, Auto backup, Conformal coating for PCBs, Eco Friendly R407C/R410A refrigerant. Floor mounted type Indoor unit consists Non woven Aolyester media enclosed by HDPE mesh, DIDW type Centrifugal blowers with forward curved blades and efficient air filter for evaporator, aluminium fins on the evaporator coil have hydrophilic coating, micro processor controller and other standard accessories. (Make - Blue Star / Voltas / Daikin / Mitshubishi Electric)
Supply and charging of Refrigerant Gas R407C/R410A
Lifting, Shifting of above noted AC Indoor & Outdoor of Units on roof of 3rd Floor.
Supply, installation, testing and commissioning of the refrigerant piping (Hard Drawn and minimum thickness 1.15 mm) between each set of outdoor and indoor units. (Make: Rajko/Royku/Mandev)
1 1/8" (Discharge Line)
7/8" (Liquied Line)
Supply & laying of Drain piping of 32mm NB PVC/HDPE hard pipes with insulation, fitting, accessories, bends, elbows, tees, flanges, tapings, wall sleeves, hangers, supports, anchor.
Supplying & laying of 1.1 kV Gr. 4 core 2.5 sq. mm copper Control Cable(Make – Havells / Finolex / Polycab) between ODU and IDU as per direction of EIC.
Supplying, installation, testing & commissioning of GSS ducting of following thickness including necessary supports, adjustable dampers, vanes etc complete as per IS 655. (Make: TATA/SAIL).
24 Gauge(0.63MM) GSS Ducting site fabricated as per IS 655
22 Gauge (0.8MM) GSS Ducting site fabricated as per IS 655
Supplying & fixing of thermal insulation with 19 mm thick nitrile rubber (Make – Armacell / Kflex / Vedio Flex).
Supplying & fixing of 12 mm thick acoustic insulation inside ducting with fibre glass rigid board of density 48 kg/cu.m finished with 28G perforated aluminium sheet with bolts nuts GI washers as per specification & as required.
Supplying, fixing, testing & commissioning of powder coated extruded aluminium section supply air grills with MS volume control dampers as required (Make: Ravi Star / Dynacraft / Carvaire).
Supplying, fixing, testing & commissioning of power coated extruded aluminium section return air grills with louvers but without volume control dampers complete as required (Make: Ravi Star / Dynacraft / Carvaire).
Supply, Installation of Volume Control Damper (Make: Ravi Star / Dynacraft / Premier) for Ducting GI
Supplying, fixing, testing & commissioning of fresh air arrangement with volume control dampers (Make: Ravi Star / Dynacraft / Carvaire), bird screen etc complete as required.
Supplying and fixing fire retardant nonporous double layer flexible connection between each unit and duct.
Supply and Installation of VI Pad for ODU Unit with fitting set
SITC of motorized fire damper incl. Acuator control panel and all other required accessories. Damper should be compatible with existing fire detection panel and should accept potential free contact for operation (Make: Ravi Star / Dynacraft / Carvaire).
Supply & fixing of Underdeck insulation with 50 mm thick TF quality expanded polystyrene slab (Make – Armacell / Kflex / Vedio Flex).
Supplying, fabrication & fixing of M.S. structure with U-channel of 6mm thick of size (75 mm x 40 mm x 40 mm) for making platform for the insulation of outdoor unit of 8.75/16.5 TR Air Cooled Packaged type AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1.1 1/2 3) etc fabricated with horizontal angle 25mm x 25mm x6mm including supporting angle 50mm x 50mm x 6mm in outer edge for transmitting the load centrally through 2 nos (50mm x 50mm x6mm) Angle inserted into the existing wall including gurrding arrangement of 3 side (3' height from platform) for maintenance purpose as well as safety.
Supply, Installation, Testing & Commissioning of Analog Addressable Intelligent multi sensor detector ( VDS / UL / FM / ULC approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photo thermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward / Secutron/ Securiton/ Apollo / Morley / Eaton/GST)
Supplying, installation, testing and commissioning of Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron / Securiton/ Apollo / Morley / System Sensor /Eaton/GST)
Supplying, installation, testing and commissioning of LED type Response Indicator (VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron / Securiton/ Apollo / Morley /Eaton/GST)
Supply, Installation, Testing & Commissioning of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST)
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward / Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Supply, Installation, Testing & commissioning of EN Standard (VDS / UL / FM / ULC approved ) Addressable of Repeater panel (LCD indicator panel) with 2 line x 40 characters alpha numeric LCD display with all commands such as reset, mute, silence with suitable battery backup complete as required (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Supply & Laying of 2 Core 1.5 sq. mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab) with 20 mm NB PVC rigid conduit pipe(Make: Precision /AKG/ATUL /VIP/ Universal /BEC/Polycab) on the surface of the wall.
Testing and commissioning of EN standard, VDS approved microprocessor based 4 loop/2 loop fire alarm panel.
The Agency must procure the materials from the Manufacturer/OEM or from their authorized sales channel so that the standard warranty/supprot of the Manufacturer/OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer/OEM or from their authorized sales channel and standard warranty/support should be sent from the e-mail of the Manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Defect Liability Period - 1 (One) year.
M/S N. C. HORE
SIMPSON AND FERRIS PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .