Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.7 LAccepted-AOC 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | L1 | Accepted-AOC L1 | |
| 2 | L2₹38.0 L+₹3.2 L (9.11%)Rejected-Finance NEAR MES FILTER PLANT SANGOOR UDHAMPUR J K 182101 | UDHAMPUR | UDHAMPUR | J K | 182101 | L2 | Rejected-Finance OTHER THAN L1 | |
| 3 | L3₹38.3 L+₹3.4 L (9.88%)Rejected-Finance NEAR INDUSTRIAL ESTATE THANDA PADDAR UDHAMPUR J K 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L3 | Rejected-Finance OTHER THAN L1 | |
| 4 | L4₹38.5 L+₹3.7 L (10.6%)Rejected-Finance 53 HOUSING BOARD COLONY PHASE II UDHAMPUR 182101 J K | UDHAMPUR | UDHAMPUR | J K | 182101 | L4 | Rejected-Finance OTHER THAN L1 | |
| 5 | L5₹38.9 L+₹4.1 L (11.6%)Rejected-Finance | L5 | Rejected-Finance OTHER THAN L1 |
Tender Value
Refer Docs
EMD Value
₹73,800
Closing Date
7 Sept 2023, 6:00 pmClosed
GE (UTILITIES) UDHAMPUR
GE (UTILITIES) UDHAMPUR, PO-GARHI, PIN-182121
Special repairs to LT Network in JCOs/OR Accn at FOD complex under GE (Utilities) Udhampur.
2023_MES_612974_1
GE/U- /2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (UTILITIES) UDHAMPUR
Please refer Tender documents
8 documents required · 8 mandatory
₹500
GE (UTILITIES) UDHAMPUR
₹73,800
3 Nov 2023
9 Aug 2023
9 Sept 2023
9 Aug 2023
7 Sept 2023
24 Aug 2023
Amount
Excavation in trenches not exceeding 1.5 mtr in wide and not exceeding 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge.
Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed by Engr-in-Charge.
Removing of excavted soil to a distance not exceeding 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (a) MCCB 200 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35/36 KA-01 No. (b) Bus bar electrolytic grade copper 300 Amp,4 pole, not less than 1.5 Mtr long SMC insulators mounted on insulators - 01 set.
Outgoing:- (a) MCCB 125 amps,4 pole,25/26 KA , with adjustable thermal over load release 50 Hz, 415 volts grade - 01 Nos. (b) MCCB 100 amps,4 pole, 25/26 KA , with adjustable thermal over load release 50 Hz, 415 volts grade - 01 Nos. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. (v) cable glands for incoming LT cable 120sqmm -02 Nos and out going cables 95 sqmm -02 Nos and 50 Sqmm-2 Nos is including rate quated by vendor.
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (a) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No. (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators mounted on insulators 240 Amp, 4 pole - 01 set.
Outgoing:- (a) MCCB 125 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01No. (b) MCB TPN 63 amps, 4 pole, 50Hz ,415 V with rupturing capacity 10 KA-04 No. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. (v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables. (vi) Cable glands for incoming LT cable 120sqmm -01 Nos and out going cables 95 sqmm -02 Nos, 50 Sqmm-1 Nos and 35 sqmm -5 Nos is including rate quated by vendor.
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (a) MCCB 160 A 4 pole ,Ics=100%Icu- 25 KA, 415 Volts, with thermal adjustable and fixed magnetic setting with extended terminals -01 No. (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set.
Outgoing:- (a) MCB TPN 40 A 4 pole ,Ics=100%Icu- 10 KA, 415 Volts, with thermal adjustable and fixed magnetic setting with extended terminals -04 Nos. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. (v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables. (vi) Cable glands for incoming LT cable95 sqmm -02 Nos, 70 sqmm -2 and 35 sqmm-3 out going cables 25 sqmm -04 Nos is including rate quated by vendor.
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (a) MCCB 63 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25/26 KA-01 No. (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 150 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set.
Outgoing:- Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. (v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables. (vi) Cable glands for incoming LT cable 95 sqmm -01 Nos and out going cables 70 sqmm -02 Nos and 50 sqmm - 01 Nos and 25 sqmm -04 Nos is including rate quated by vendor.
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (a) MCCB 125 amps,4 pole,25/26 KA , with adjustable thermal over load release 50 Hz, 415 volts grade - 01 Nos. (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set.
Outgoing:- Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. (v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables. (vi) Cable glands for incoming LT cable 95 sqmm -01 Nos and out going cables 70 sqmm -01 Nos and 35 sqmm - 04 Nos is including rate quated by vendor.
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (a) MCCB 100 amps, 4 pole, 50Hz ,415 V with rupturing capacity 25/26 KA-01 Nos.
Outgoing:- (a) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp,4 pole - 01 set. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. (v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables. (vi) Cable glands for incoming LT cable 70 sqmm -01 Nos and out going cables 95sqmm -01 Nos ,35 sqmm -01 Nos and 25 sqmm - 3 is including rate quated by vendor.
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (a) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No.
Outgoing:- (a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. (v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables. (vi) Cable glands for incoming LT cable 95 sqmm -01 Nos and out going cables 70 sqmm -02 Nos and 50 sqmm - 01 Nos and 25 sqmm -04 Nos is including rate quated by vendor.
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (a) Change over swutch 160 amps, 4 pole, 50Hz ,415 V with rupturing capacity 35/36 KA-01 Nos.
Outgoing:- (a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole - 01 set. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. (v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables. (vi) Cable glands for incoming LT cable 70 sqmm -01 Nos and out going cables 95sqmm -01 Nos ,35 sqmm -01 Nos and 25 sqmm - 3 is including rate quated by vendor.
S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 200 Amps , with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge.
S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 160 Amps , with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge.
S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 315/320 Amps ,with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge.
S&F in replacement MCCB 4 pole, Ics=100%Icu- 25/26 KA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge.
S&F in LED flood light with lens 150 watt made uppressure diecast aluminium housing with toughned glass and high power leds and secondary lens with IP 66 protection system of efficasy >110/125 LPW including 10 KV SPD including taking down old UNSV Street lights complete all as specified and directed by Engr-in-Charge.
S&F LED Street light 60 watt made uppressure diecast aluminium housing with toughned glass and high power leds and secondary lens with IP 66 protection system of efficasy >110 LPW including 10 KV SPD including taking down old UNSV Street lights complete all as specified and directed by Engr-in-Charge.
S&F thermoplastic, polystyrene unbreakable junction box size 260 x 210 x 116 mm suitable for pole mounted outdoor type IP 65 insulated complete with FI clamp & nut, bolts, washers and including phase seperator between R, Y, B terminals and one MCB SP 6 amp 10 KA, all duly mounted on din cannel, cable glands for cable entry. complete all as specified and directed by Engr-in-Charge.
Material and labour in replacement of PVC insulated multi stranded copper conductor PVC cable sheathed 2.5 sqmm 3 core and making connections of street light fittings and bollards lights complete all as specified and directed by Engr-in-Charge.
GI pipe bracket Suitable size of light single swan neck shape suitable to fix on top of tubular pole complete with clamps, nuts, bolts and washers complete all as specified and directed by Engr-in-Charge.
S&F of Steel tubular swaged poles erected to truly vertical or planted as strut complete with 6 mm thick mild steel base plate, welded to Pole, B-118 finial taper cap, bolts, nuts and screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II type 410-SP-31 (9m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint on the and portion embedded in concrete, making five black and white bands at lower portion of pole above ground level/coping each 300 mm wide alternately and marking pole number. with black paint at suitable height complete all as specified and directed by Engr-in-Charge. Note:- The earthwork, PCC foundation, steel clamps, MS Cross arms & bracing of angle iron etc will be measured and paid separately under relevant items of Sch ‘A’.
S&F of Steel tubular swaged poles erected to truly vertical or planted as strut complete with 6 mm thick mild steel base plate, welded to Pole, B-118 finial taper cap, bolts, nuts and screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II type 410-SP-64 (12 m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint on the and portion embedded in concrete, making five black and white bands at lower portion of pole above ground level/coping each 300 mm wide alternately and marking pole number. with black paint at suitable height including The earthwork, PCC foundation,deemed to be coated rate by contractor complete all as specified and directed by Engr-in-Charge.
S&F in replacement of automatic street light control switch of 8 KW three phase using Infrared sensor based Nature Switch for automatic switching of street light. Nature switch operation should be based on Natural Light Lux*level. Reqd illuminance level also have part night operation facility for min 4 hrs to max 12 hrs. The sensor along with suitabe rating power contractor (s), one Incoming and three Outgoing MCBs rating of 20-32 Amps & main load circuit wiring (copper) of min 10 sqmm should be enclosed in a pole/wall mountable rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure conforming to IP66 protection class-2. The circuit should be also have provision for manual operation (i.e. sensor by pass option) complete all as specified and directed by Engr-in-Charge.
Supply and Laying and fixing in replacement of along the poles or passing through pipes or laid under floor of through walls etc jointing and testing LT Cross Linked Polythene Insulated (XLPE insulated) galvanized steel strip armoured electric cable 1100 volt grade heavy duty ISI marked with aluminium conductor and overall served with an outer sheath of PVC, of cross sectional area of size 185 sqmm 3.5 core including taking out old UNSV LT cables complete all as specified and directed by Engr-in-Charge. Note : Excavation, earthwork, Pipe for cable protection to be measured and paid for separately.
All as per serial item No 24.00 here-in-before but of size 120 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per serial item No 24.00 here-in-before but of size 95 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per serial item No 24.00 here-in-before but of size 70 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per serial item No 24.00 here-in-before but of size 50 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per serial item No 24.00 here-in-before but of size 35 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per serial item No 24.00 here-in-before but of size 25 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per serial item No 24.00 here-in-before but of size 16 Sqmm 4 core complete all as specified and directed by Engr-in-Charge.
Supply & fixing or laying galvanised steel tubing light grade 80 mm dia (ISI marked) for protection of under ground cable on poles / walls under road crossing etc of following sizes including dismantling & taking down existing pipe complete all as specified and directed by Engr-in-Charge.
M&L for boring of existing road/path for laying of GI pipe protection for UG cable including making good distrurbed area/surface complete all as specified and directed by Engr-in-Charge.
M & L for providing earthing with GI earth plate electrode 600 X 600 X 6mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI strip 25 x 4 mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc complete all as specified and directed by Engr-in-Charge. Note:- (i) All the joints shall be made with welding to get proper conductivity. (ii) On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engr-in-Charge.
M & L for providing earthing with Copper earth plate electrode 600 X 600 X 3 mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to Copper strip 20 x 3 mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc complete all as specified and directed by Engr-in-Charge. Note:- (i) All the joints shall be made with welding to get proper conductivity. (ii) On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engr-in-Charge.
Ring suitable for 12 m long pole for semi highmast light and for fixing of six nos flood lights with bolts, nits and screws, ring made out of ERW MS tubing confirming to IS-2713 including drilliing of holes of required size for fixing of brackets, painting the exposed surfaces of ring with coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of silver paint on the surface complete all as specified and directed by Engr-in-Charge.
S&F , install, 150 amp copper bus bar with enclouser wall mounted size 300X250 mm , suitable for 415 volts 3 pnase 4 wire , 50 hz AC supply system, dust and vermin proof made of 1.8 mm CRCA MS sheet for cable entry and locking arrange ment complete all as specified and directed by Engr-in-Charge.
S&F double walled corrugated (DWC) pipe of size 77 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as specified and directed by Engr-in-Charge.
S&F double walled corrugated (DWC) pipe of size 50 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as specified and directed by Engr-in-Charge.
FANGALIA TRADERS
K S BUILDERS
vijay kumar gupta and co
D P ASSOCIATES
shivom builders
PREM NATH KHAJURIA AND SONS
M/S Builders Indias
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .