Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹55.3 LAccepted-AOC | ₹55.3 L Quoted ₹55.5 L | L1 | Accepted-AOC Being reasonable and Lowest L1 |
| 2 | L2₹62.1 L+₹6.6 L (11.9%)Rejected-Finance | ₹62.1 L+₹6.6 L (11.9%) | L2 | Rejected-Finance Being other than L1 |
| 3 | L3₹64.5 L+₹9.0 L (16.3%)Rejected-Finance | ₹64.5 L+₹9.0 L (16.3%) | L3 | Rejected-Finance Being other than L1 |
| 4 | L4₹67.4 L+₹11.9 L (21.5%)Rejected-Finance | ₹67.4 L+₹11.9 L (21.5%) | L4 | Rejected-Finance Being other than L1 |
| 5 | L5₹72.8 L+₹17.3 L (31.3%)Rejected-Finance 67 KAILASH VIHAR TIWARIPUR BAGIA JAJMAU KANPUR 208010 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208010 | ₹72.8 L+₹17.3 L (31.3%) | L5 | Rejected-Finance Being other than L1 |
Tender Value
Refer Docs
EMD Value
₹1.3 L
Closing Date
10 Nov 2020, 6:00 pmClosed
Col SS Bose, CWE
HQ CWE (AF) Chakeri, Kanpur 208008
PROVN OF FALSE CEILING AND ALLIED WORKS IN BLDG NO T 48 AT 24 ED AF STN MANAURI
2020_MES_378482_1
82149/E8
Open Tender
Civil Works
Item Rate
183 days
Manauri, Allahabad
Class C act a (i)
8 documents required · 8 mandatory
₹1,000
AGE (I) Manauri
₹1.3 L
24 Dec 2020
17 Sept 2020
17 Nov 2020
17 Sept 2020
10 Nov 2020
27 Oct 2020
Amount
B/R Work Taking down cement plaster on bricks or stone walls etc, including racking out joints, hacking for key scrubing down with water etc complete all as specified and directed.
M&L rendering 15mm thick in cement mortar 1:4 on fair faces of brick work or concrete surfaces finished even and smooth without using extra cement complete all as specified and directed.
M&L preparation of new platered surfaces and applying two coats of cement base paint on walls over a coat of white cement primer, complete all as specified and directed.
M&L rendering 15mm thick in cement mortar 1:6 on fair faces of brick work or concrete surfaces finished even and smooth without using extra cement after complete removal of existing decorative surfaces of wall complete all as specified and directed.
M&L preparation of newly plastered surfaces of walls and applying three coats of white wash complete all as specified and directed.
M&L preparation of old surface of wall after compelte removal of existing treatment by scraping, rubbing down & cleaned with water and applying two coat of cement base paint over a coat of white cement primer complete all as specified and directed.
M&L preparation of old surface of wall after compelte removal of existing treatment by scraping, rubbing down & cleaned with water and applying three coats of white wash complete all as specified and directed.
M&L preparation of new painted steel surfaces of any decription, over 10 cm width or girth not otherwise described and applying two coat of synthetic enamelled paint over a coat of red oxide primer complete all as specified and directed.
All as per item No 8 above but on old painted surface without primer.
M&L applying one coat of syenthetic enamel paint on old painted wooden surfaces of any description over 10cm in width or girth not otherwise described including preparation of surface complete all as specified and directed.
M&L preparation of old surface of wall including cleaning, widening of existing cracks in surfaces by chesiling and filling cracks by applying one coat of oil based crack 'X' adhesive putty of make:- Pidilite or Dr Fixit or equivalent as approved by AGE (I) and after than applying evenly two coats of water proof elostomeric paint in 100mm wide strips on cracked surfaces of make: Pidilite model/brand "Raincoat '601" or Dr Fixit or Asian paint or equivalent as apporved by AGE (I) complete all as specified & directed.
All as per item No 11 but in patches n exc 10Sqm area complete all as specified and directed.
M&L preparation of old treated plastered surfaces of wall and applying 2 mm thick JK / Birla wall care putty and applying two coats of oil bound distemper over a coat of primer complete all as specified and directed.
M&L 12mm thick armstrong or equivalent board flame proof conforming to IS-2095-1982 to fix as suspended ceiling with one step and including powder coated frame consisting of perimeter chanel of size 20x27x30x 0.50mm ( wall thickness not less 1.0mm of sheet ) and intermidiate channel 45mm (WEB) x 15mm (Flange)x 0.90mm (height) (Sheet thickness not less than 1,0mm) @ 1.22 m centre to centre spacing with ceiling angle 25x 10x 0.5mm fixed to soffit with GI cleat and steel expansion fastner, ceiling section 51.1mm (Knurled web) x 26mm (Flange) with lips of 10.5mm x 0.5mm @ 610mm C/C fixed with nec clip, screw, nylon sleeves etc complete all as specified and directed.
M&L brick work with old size sub class 'B' bricks, staright or curved on plan exc. 6.0 mtr mean radius, built in cement mortar 1:6 complete all as specified and directed.
Demolition of cement concrete (unreinforced) in ground floors and paving n.exc 15cm thickness (below or above ground level) including removal of dismantled material beyond MD land complete all as specified and directed
M&L 75mm thick, PCC 1:3:6 type C-1 (using 20mm graded stone aggregate) as in plinth protection with making joints & filled with bitumen & sand as per relevant clauses of SSR part I complete all as specified and directed.
S&F in repair galvanised steel rolling shutters (thickness of lathe not less than 1.00 mm thick) with ISI marked ball bearing as specified including top cover hood ((thickness of lathe not less 1.00mm of hood cover), anchoring rod 40mm dia GI 'medium grade' pipe of required length, hasp & staple and one coat of primer complete and errected in position as indicated complete with gear box operated type (Standard ISI Marked gear box of make: Universal or equivalent as approved by AGE (I) ) with chain wheel and hand chain, key lock both side of guide (minimum of thickness 2mm) and including taking down of old unseviceable rolling shutter and making good dismantled surface of wall with the matching of existing finish complete all as specified and directed. (Note: old rolling shutter with all fittings shall be creditted to contractor).
S&F safety lever locks mild steel with 4 levers for rolling shutter ISI marked complete all as specified and directed.
S&F ball bearing 'ISI Marked' for rolling shutter complete all as specified and directed.
External Elextrification Supply,laying, testing & commissioning of LT XLPE insulated, screened, PVC bedded galvanised steel strip of wire armoured electric power cable (heavy duty) with aluminium conductor 1100 volts grade of cross sectional area 120 Sqmm 3 1/2 core (earhted) laid in trenches/ in ducts/encased GI pipe/fixed on poles etc including necessary lugs, thimbles & glands complete all as specified and directed. (Note:- Excavation & earthwork, sand cusioning, brick protection, GI portection pipe shall be measured and paid seperately under respective items.)
All as per item No 21 above but of size 70 Sqmm 3 1/2 core
All as per item No 21 above but of size 25 Sqmm 4 core
All as per item No 21 above but of size 10 Sqmm 2 core
Excavation in treanches not exceeding 1.5 mtr in depth and not exceeding 1.5 metre wide for taking out old cable and laying of new cable and getting out in soft/loose soil complete all as specified and directed.
Returning, filling in including, spreading, leveling, watering & well ramming in layers not exceeding 25 cm thick after testing of cable complete all as specified and directed.
Removing exacavated material (soil) out side MD land at contractor's own arrangement complete all as specified and directed.
Supply & laying and spreading of dry (Ganga) sand free from organic impurities , unwashed, spread in even thickness in trenches for cushioning around the cable 8 cm before and 15cm after laying of cables complete all as specified & directed. Note :- Punned thickness shall only be considered for measurement and payment.
M&L brick work with old size sub class 'B' bricks, well burnt, laid dry in trenches for portection of cable over LT/HT cable complete all as specified and directed.
M&L boring of holes under road, pavement, hard standing by manual method for inserting 80mm dia light grade GI tube pipe for cable protection complete all as specified and directed. (Note: GI pipe shall be laid minimum 1.0 mtr below the natural GL as per site requirement and to be paid seperately. Quoted rate shall be deemed included the cost of material & labour required for making good as per existing surface).
Supplying & laying in trenches / floor or fixed to pole / wall of GI pipe 40 mm bore 'light grade', (ISI marked) for laying /fixing including fittings at required location complete all as specified and directed.
All as per item No 31 above but 50mm bore
All as per item No 31 above but 80mm bore
Supply, jointing, commissioning and testing cable jointing kit for 1100 volt grade cable for end/straight through joints in/out door type complete with jointing material and accessories suitable for 3.5 core or 4 core XLPE insulated armoured aluminium conductor cable of size 95 to 120 Sqmm complete all as specified and directed.
S&F cutting, welding, jointing etc to cable rout indicator made out by MS angle 60cm long of size 40x40x5mm thick as stand and 150mm dia 5mm thick round plate continous welding on top edge of stand including painting with two coat of synthetic enamel paint over a coat of red oxide primer fixed in PCC (1:2:4) type B-1 using 20mm graded stone aggregate minimum 30cm below GL and taking out the existing route iindicator from site complete all as specified and directed by Engr-in-charge. Note : (a) Quoted unit rate shall be included cost of embosing sign on MS plate fixed on PCC work. (b) Cost of earthwork & PCC shall be included in quoted unit rate.
M&L PCC 1:2:4 type B-1 using 20mm graded stone aggregate for pole coping including form work complete all as specified and directed.
M&L earthing complete with galvanised steet earth electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of earth electrode not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 32 x 6 mm as earth lead by means of bolt, check nuts & washer of GI or steel connected to earth test point including earth strip from earth electrode to test point, Gl pipe 40 mm dia light grade as protection pipe and 20mm dia GI pipe light grade for watering pipe of required length including charcoal dust, common, salt, excavation and earth work, earth pit with PCC 1:3:6 type C 1 using 20mm graded stone aggregate, precast RCC cover 40mm thickness reinforced with 03 Nos TMT bars, 8 mm dia, both ways, funnel with wire mesh, and connecting the earthing to an earting test point of main panel board and testing and rest as shown in electrical plate No 3 of SSR Part -I including taking out old earthing material, complete all as specified and directed. Note: Earthing strip and protection pipe upto 7.5 metre length shall be deemed to be included in the quoted unit rate. Earthing strip beyond 7.5 metre shall be measured and paid for separately.
Supply and fixing of galvanised strip 32x6 mm fixed on wall/batten or recessed or buried in ground complete all as specified and directed.
Supply. Installation, testing and commisioning of LT Panel in cubical housing cabinet, out door type, platform mounted (minium height 45 cm above normal GL and 30 cm below normal GL) , CPRI approved factory made, totally enclosed, dust and vermin proof made out by 3.15 MM thick CRCA MS sheet and full built upon angle iron frame in size 40 x 40 x 6 MM, having front and rear hinged both side openable doors and liffting lugs (02 Nos) , locking arrengement to be connect to earthing strip at rear side, bottom detachable both side openable ,gland plate complete with suitable size zinc plated and passivated nut, bolts, spring and washers sheet steel bus bar chambers having front hinged covers with a set of electrolytic grade high conductivity. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment. The panel shall be epoxy powder coated and the control circuit shall be connected by multi strandered copper conductor flexible wire 1.5 Sqmm in proper colour coading and drawn through in flexible conduit. The panel should be suitable for 415 volts ,50 Hzs, 3 phase,4 wire system ,suitable rating CTs and PTs . internal connection shuold be made by copper strip in suitable rating ,making incoming and outgoing connection using gland in suitable size including grouting KIOSK on floor (60 CM above the ground surface) in floor angel iron 40 x 6 MM imbeded to fixed the KIOSK with nut bolt, floor PCC (1:2:4) type B1 using 20 MM grade stone aggregate ( minium 50 CM above GL and 30CM below GL) complete comprising the following items:- Note : (i) Panel drawing shall be approved by Deptt for size and all Tech specification before placing order (Bldg main Panel) (ii) All MCCB shall be confirming to Icu 100% and IEC 60947 -2 . in compact series (a) 04 Nos bus bars equal size made out of aluminium conductor strip in colour coating 400 Amps rated mounting on both side heat shrinkable insulators and PVC sleeving. -01 Set (b) LED indicating lamps of 'R' 'Y' and 'B' phase. Set of three -03 Nos (c) Digital multi meter to be measured voltage/current rating/frequency and eanergy - 01 No (d) MCCB ,160 Amps rated, 4 pole, 415 volts grade , 36 KA breaking capacity adjutable type - 01 No (As main incommer) (e) MCCB ,125 Amps rated, 4 pole, 415 volts grade , 16 KA breaking capacity adjustable type - 02 Nos (As outgoing ) (f) MCCB ,63 Amps rated, 4 pole, 415 volts grade , 16 KA breaking capacity adjustable type -02 Nos(As outgoing) (g) MCB two pole, 220 volt, 40 Amp, 10KA breaking cpaicty -01 No (h) Off load changover switch, front handle operated, 4 pole, TPN, 415 volts, 160 Amps complete-01 No.
Supply. Install, testing and commissioning of LT feeder pillar box in cubical housing cabinet, out door type, for making connection junction point platform mounted (minimum height 45 cm above normal GL and 30 cm below normal GL) , CPRI approved factory made, totally enclosed, dust and vermin proof made out by 3.15 MM thick CRCA MS sheet and full built upon angle iron frame in size 40 x 40 x 6 MM, having front and rear hinged both side openable doors and liffting lugs (02 Nos) , locking arrangement to be connect to earthing strip at rear side, bottom detachable both side openable ,gland plate complete with suitable size zinc plated and passivated nut, bolts, spring and washers sheet steel bus bar chambers having front hinged covers with a set of electrolytic grade high conductivity. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment. The panel shall be epoxy powder coated and the control circuit shall be connected by multi strandered copper conductor flexible wire 1.5 Sqmm in proper colour coading and drawn through in flexible conduit. The panel should be suitable for 415 volts ,50 Hzs, 3 phase,4 wire system ,suitable rating CTs and PTs making all connection using gland in suitable size including grouting KIOSK on floor (60 CM above the ground surface) in floor angel iron 40 x 6 MM imbeded to fixed the KIOSK with nut bolt, floor PCC (1:2:4) type B1 using 20 MM grade stone aggregate ( minimum 50 CM above GL and 30 CM below GL) complete comprising the following items:- Note : (i) Panel drawing (dimension) shall be approved by Deptt for size and all Tech specification before placing order (with existing TFR for taking up connection) (ii) All MCCBs shall be conforming to ICU 100 % and IEC 60947-2 in compact series. (i) 04 Nos aluminium bus bar in equal size and thick ness for RYB current rating 600 Amp mounting on insulators and covered by colour coading sleeve - 01 set (ii) MCCB 4 pole, 250 Amp capacity, adjustable type with rupturing capacity 36 KA- 01 No. (as incomer) (iii) MCCB 4 pole, 160 Amp capacity, adjustable type with rupturing capacity 16 KA- 02 No. (as out going) (iv) Digital multi meter to be measured current rating/ voltage/ Frequency and energy -01 No (v)) Indicator lamp plate type for RYB - 03 Nos Note for item No 39 &40: MCB/MCB DB of same make and cost of PCC plateform shall be included in quoted unit rate.
Supply and fixing LED street/ Bldg security light fittings 45 watts energy saving incl making all electric connection using three core copper cable drawn through in PVC flexible counduit pipe from ceiling rose to fittings and mounting bracket made out by GI pipe light grade in 25 mm dia of bore in required length bend in 120 degree fixed with clamping of surface of wall using clamp made out by GI strip in size 32 x4 mm using nut bolt and washer etc complete as directed. (Make ; Bajaj (warm white) Cat No BRTFG 45W LED WW or in other equivalent make as lited in Appedix 'B' duly approved by AGE (I).
AIR CONIDTIONING WORK Supply, installation, commissioning and testing ofvertical pack type Air conditioning air cooled package type 4.5 TR (54000 Btu/Hurs), Air Conditioning unit having one evaporator & one scroll hermetically sealed compressor. Complete with refrigerant piping, inbuilt digital Microprocessor controller, Cleanable type synthetic material air filter, with indoor units mounting frame, internal electrical cabling. Copper tubing for hot & cold gas / refrigerant piping from indoor unit to outdoor unit.M S stand for out door unit , Electric control cable from indoor to out door unit with cable tray & condensate drain pipe of suitable size. Unit shall be suitable for. Total static pressure: 35mm WG Power supply: AC, 3 phase with Neutral, 415 Volt ± 10% , 50 Hz. Refrigerant : R-407C or as pr OEM recommondation Specification of unit is as given below Vertical pack type indoor/outdoor unit: Nominal cooling capacity: 4.5 TR. Cooling coil: internally grooved copper tubing. Fins spacing: 1.95 mm (13FPI). Fin type and material: Aluminium/Hydrophilic blue. Number of rows:4 Supply air fan: DIDW, forward curved centrifugal type with belt driver package with fan drive motor. Type of compressor: Scroll hermetically sealed Control panel: Control panel shall have following features. Control panel should have digital microprocessor controller. LCD display. Auto restart power failure. Fault display. Run-Time rqualization. Non-volatile memory. Touch-key on/off switch. Single-phasing and phase reversal protection. Time delay for compressor operation. Accurate temp. control ±1ºC.
Internal refrigerant piping and wiring. Safety devices for compressor protecton. Inbuilt internal thermal protector. Internal pressure relief valve. High pressure cutout. Low pressure cutout. Filter drier. Expansion device: thermostatic expansion valve with sensor.
Service Valve: Filter: Filter should be non-woven polyester media enclosed by HDPE/nylon washable. Thickness: 50mm Efficiency: 85% down to 20 microns Power supply to indoor unit: 3 phase 415 V 50 Hz Vertical pack type outdoor unit: Nominal cooling capacity: 4.5TR Condenser coil: internally grooved copper tubing. Fins spacing: 1.6 mm (16FPI). Fin type and material: Aluminium/Hydrophilic blue. Number of rows:2
Outdoor Fan: Propeller fan with fan drive motor. Note: (1) Ducting shall be measured & paid separately . However other items required for successfully commissioning unit shall deemed to be included in the contract. (2) Quoted unit rate shall be included cost of copper insulated air tube in various sizes, brick work, cement work for foundation & making good and else GI frame factory made brackets for munting of out door units complete. (3) Testing, nitrozen gas, shifting, installtion and running functional test of AC will be carried out by contractor at quoted unit. Nothing extra will be paid layer on by department.
S&F wall mounted metal type sheet metal enclosure, 32 Amp three pole and neutral & earth with a round pin and earth plug and socket complete in metal clad board (Industrial type) with one TPN MCB 32 Amp fixed properly on in concealed position complete all as specified and directed.
M&L sub main wiring with four run PVC-FRLS insulated unsheathed stranded copper conductor cable of size 6.0 sqmm drawn in and including rigid steel conduit medium grade ISI marked of size not less than 32 mm dia concealed position inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, pipe hooks etc fixed properly on as in concealed position including cutting chases & making good the surfaces by cement mortar (1:3) and matching / finishing of new surfaces either by means of plaster of paris/ putty or distemper/ colour wash with same existing colour / shade of surfaces and provision of one run of earthing wire of size 6.00 Sqmm PVC-FRLS insulated unsheathed stranded copper conductor as a continuous earth wire complete all as specified incl. taking down old unserviceable sub main wiring complete all as specified and directed. Note : (a) Four run single core cableof 6.00 sqmm and one run of earth copper conductor of size 6.00 Sqmm and one run of steel conduit shall be measured and paid as one unit length (b) Cost of cutting/cheasling/plastered/coluring etc as per site shall be included to matching to distrurned surface all as per existing
S&F exhust fan AC supply, single phase 230/240 volt of size 450mm sweep energy saving 4 star rating with louvers heavy duty, steel body, copper wounded suitable for industrial duty steeel body with fixing accessories and making all connection using 3 core copper cable drawn through in PVC flexible conduit pipe & clamping etc complete all as specified and directed. Note:- Quoted rates shall be included cost of making holes in suitable size, plastering, colouring etc required material to match with existing.
All as per item No 46 above but 300mm sweep
Supply install commissioning and testing of commercial as new air curtain unit for prevention of dust and conditioned air losses ,three phase 440 volt 50 HZs made out of MS/CRCA sheet of minium thickness 18 gauge finished with two coats of red oxide primer and final coats of synthetic enamel paint (oven baked) with MS -CRCA 18 gauge square perforated suction grills , aluminium alloy fans and single phase electric motor nozzels etc complete with fittings and accessories so as to produce 1-1.5 M/sec air velocity at floor level for door opening in size 7 feet x 4 feet (52" x 90" ) complete all as specified and directed. Note : Quoted unit rate shall be included cost of making a hole in suitable size on surface of wall and carrying out 15mm thick plastering in CM (1:4) & finishing with two coats of distempering etc complete all as sper existing finish at sit.
S&F TPN 4 pole vertical distribution board , IP30 multiphase outgoings for mounting double door with and including incoming MCCB 125 Amp, 16 KA indoor type complete with 300 amps rating 4 Nos bus bar aluminium mounting on heat shrinkable insulators complete all as speciifed and directed.
INTERNAL ELECTRIFICATION Taking down copper/aluminium point wiring (light, fan, socket or power) complete including fixture and fitting such as switches, ceiling rose, pendants,regulators, sockets, lamp holders, light fittings etc removing old unserviceable material from site and serviceable material to site for keeping in safe custody and making good disturbed surfaces of wall, floor etc. all as directed.
Material and labour for point wiring including concealed rigid non-metallic PVC conduit pipe medium grade, ISI marked heavy duty in size 20 mm dia with 1.5 sqmm FRLS insulated unsheathed, multi stranded copper conductor cable, single core 1100 volt grade with flush cast iron/ pressed steel terminal boxes of suitable size for fixing of switches, sockets and fan regulators etc piano / modular type accessories with 3 mm thick plastic laminated sheet cover and fixing with brass screws/cup washer and including FRLS insulated & unsheathed 1100 volts grade cable with multi stranded copper conductor of size 1.5 sqmm as continous earth wire complete including making good the disturbed surfaces for the following:- Note : Quoted rate shall be included cost of cheasesing ,cutting, plastering and colouring etc to surface of wall / beam/ roof etc as site required matching with existed surface. (a) One light/fan point controlled by one way independent switch.
(b) One 3 pin 5 Amps socket out let point on same board controlled by one switch.
(c) One 3 pin 5 Amps socket out let point on independent board controlled by one switch.
(d) All as per above item No-51 here in before point wiring for 15 Amps socket using 2.5 sqmm copper cable for phase and neutral and 1.5 sqmm as earth wire complete.
(e) All as per above item No-51 here in before power point wiring using 4 sqmm copper conductor cable FRLS insulated unsheathed and unsheathed copper conductor of 4.00 sqmm as earth wire complete.
Supply and fix ivory finish switch piano, flush type, single pole, one way 5 Amps 230 Volts complete all as specified.
Supply and fix ivory finish switch piano, flush type, single pole, one way 15 Amps 230 volts complete all as specified and directed.
Supply and fixing modular type power unit single phase 220 volts 32 Amps socket and control switch ISI marked 3 module complete all as specified and directed.
Supply and fix ivory finish switch socket combination 2 in 1, 5 pin 5 Amps flush type complete all as specified and directed.
Supply and fix switch socket combination 2 in 1, 5 pin 16 Amps flush type complete all as specified and directed.
Supply and fixing ceiling rose PVC/polycarbonate, surface type 65 mm x 50 mm, 2 to 3 terminal complete.
Supply and fixing LED tube light fitting with frame, driver etc in 20 W rating , 4 feet long voltage range 90-300 volt white colour mounting on tow Nos of PVC round/ squire block on surface of wall / beam etc incl making all electric connection using three core copper cable drawn through in PVC flexible counduit pipe from ceiling rose to fittings complete as directed. Make ; Bajaj cat No BCLSBAL 20W CW or in other equivalent make as listed in appendix 'B' duly approved by AGE (I) (for non ceiling cover area)
Supply and fixing indrustial reccess LED 36 (NW) watts light fitting (2'x2' Panel), voltage range 90-300 volt energy saving low glare high power incl making all electric connection using three core copper cable drawn through in PVC flexible counduit pipe from ceiling rose to fittings complete as directed. Make ; Bajaj cat No BZRSQL 43 W GZi NW or in other equivalent make as listed in appendix 'B' duly approved by AGE (I) (for office area)
Supply and fixing indrustial LED 80 watts down light fitting energy saving low glare high pressure diecast aluminium 120 lm/w power incl making all electric connection using three core copper cable drawn through in PVC flexible counduit pipe from ceiling rose to fittings and duly hange with steel wire complete as directed. Make ; Bajaj cat No BGHBM80W LED XE (Blaze series) or in other equivalent make as listed in appendix 'B' duly approved by AGE (I) (for replacing to old HPSV fittings in storage area)
Supply and fixing flood light fitting LED 48 Watt high efficency with fixing accessories on surface of wall/ beam/ truss, pressure die cast aluminium with toughned glass cover voltage range 90-300 volt etc as site and making all connection using three core copper flexible cable drawn through in PVC flexible conduit pipe from ceiling rose to light fittings complete all as specified and directed. Make ;- Bajaj Cat No BJFL 30W LED or in other equivalent make as listed in appendix 'B' duly approved by AGE (I)
Labour for re-fixing to serviceable light fittings in all specification/ make/ model/ cap etc required at site incl fixing /connecting accessories and making connection using three core copper flexible cable drawn through in PVC flexible conduit pipe from ceiling rose to light fittings complete all as directed.
Material labour cutting / cheasesing / plastering and colouring etc to surface of existed wall / beam/ roof etc required at site to be lay concealed PVC conduit in any specification all as required at site incl plastering and colour coating to matching with existed surface complete as directed.
Material and labour sub main wiring with two runs of single core PVC FRLS IS-694 cable with unsheathed multi-stranded copper conductor of size 6 sqmm and drawing through in concelead rigid non metallic PVC conduit pipe medium grade heavy duty in suitable size with all necessary fittings including one run of FRLS insulated unsheathed stranded copper conductor cable of size 6 sqmm as earth wire (green in colour) and connected to common earth dolly complete including taking down of old unserviceable sub main wiring complete all as specified and as directed. Note : (i) Two run of 6 sqmm wire and one run of 6 sqmm earth wire and one run of PVC conduit pipe shall be measured agaist one unit. (ii) Cost of cutting /cheasesing / plastering /colouring etc at site shall be included to matching the disturbed surface with existing surface.
Supply and fix sheet metal enclosure for MCB distribution board SPN, double door, 8 way with 200 Amp rated bus bar 230 Volts complete all as specified and directed.
Supply and fix sheet metal enclosure for MCB distribution board TPN, 4 pole double door, 4 way with 200 Amp rated bus bar 440 Volts with common earth bar, vertical type concealed in surface of wall etc complete all as specified and directed.
Supply and fixing MCB , SPN, 2 pole 215 volts , 40 Amps , "C" Curve 10 KA complete all as specified and directed.
Supply and fixing MCB , SP, single pole 215 volts , 32 Amps , "C" Curve 10 KA complete all as specified and directed.
Supply and fixing MCB ,TPN, 4 pole 415 volts , 40 Amps , "C" Curve 10 KA complete all as specified and directed.
Supply and fixing as new ceiling fan in size 1200 MM sweep white colour 5 star rated copper wound energy saving with set of sweep/ extension rod / "U" clamp and other accessories single phase 50 Hzs incl making electric connection using three core copper cable drawn through in PVC flexible conduit pipe complete all as specified and directed. Make : Usha model EX 3 ,1200 MM (white colour) or equivalent in other make as appended in appendix 'B' duly approved by AGE (I).
Supply and fixing of wall mounting fan/ air circulators heavy duty, 450 mm sweep non capacitor, bracket mounted type copper wound motor ISI marked 3 star rated energy saving with fixing accessories complete making necessary electric connection all as specified and directed. Make ;- Usha model MAX Air W/F (white colour) or equivalent model of make as approved by AGE (I) (for Storage Area)
Supply and fixing Air Circulator 230 volts single phase heavy duty copper wounded 5 sater rating energy saving steel body indutrial type oscillating in 600 mm size of sweep fixing with surface of wall/ beam/ guider etc all as site making all connection using 3 core copper cable drawn through in PVC flexible conduit pipe clamping etc complete all as specified and didrected. Make:- Almonard or equivalent in other make as listed in Appendix 'B' duly approved by AGE (I).
M/S MALHOTRA ENGINEERING WORKS
M/s M A Traders
M/S Garg Sons
Ashirwad Contractor and Supplier
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .