Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 3 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
6 Mar 2024, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Project manager
Office of the Project Manager, Unit-43 C and DS, UP Jal Nigam(U), Farrukhabad HQ-Kannauj
As per NIT and Tender Document
2024_UPCDS_907954_1
357/E-NIVIDA/86 Dated 24.02.2024
Open Tender
Construction Works
Item Wise
90 days
Police Line Fatehgarh, U.P
As per NIT and Tender Document
3 documents required · 3 mandatory
₹2,360
As per NIT
₹1 L
6 Mar 2024
29 Feb 2024
6 Mar 2024
29 Feb 2024
6 Mar 2024
29 Feb 2024
Amount
Supply, Installation and commissioning of AMF start silent type 125 KVA DG Set (approved make) comprising of suitable BHP diesel engine directly coupled to 3 phase 50 Hz 415 V alternator of 125 KVA rating at 0.8 power factor mounted on a common base frame, complete in all respects with all required safety devices, fittings, batteries, accessories, filters, residential type silencer, control panel, inbuilt diesel oil MS tank of 230 ltrs capacity made of 2 mm thick MS Sheet complete with MS fuel piping, GM gate valves, supports, control cable between generating set and control panel, exhaust piping with asbestos roping, antivibration mounting pads, first filling of lubricant oil totally enclosed in air tight, dust proof, weather proof, powder coated cubical type, sound prof as per CPCB norms acoustic enclosure made of 2mm thick CRCA sheet with heavy duty doors, lockable arrangements, sound proof insulation with high density rock/ mineral polymer/fibre cloth and perforated CRCA sheet, suitable to reduce the sound level upto 75dba approx. at a distance of 1 mtrs as per CPCB norms
Supply, Installation, testing & commissioning of 500 KVA, 11/0.433 KV, 3 Phase 50 Hz, Oil type copper wound transformer (approved make) with off load tap changing arrangement on HV side in steps of +/- 2.50%, +/- 5% & -7.5%, having cable end boxes on HV side and 800 Amp bus trunking arrangement on LV side complete with all accessories including first filling of filtered dehydrated oil and confirming to IS 2026 and as per specification
A electrical panel with automated changeover system should be provided for smooth operation.
Supply and burying earth electrode for lighting conductor of 600mm*600m*6.0mm G.I plate vertically for earthing with its top at least 3 meters below ground level complete with 20mm dia G.I pipe for watering funnel, 30cm square C.I frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in?charge complete in all respects.
Supply and fixing of horizontal air termination (roof condutor) of 25mm*3mm G.I strip, G.I clamps on surface complete in all respects as approved by Engineer-in-charge
Supply and fixing of vertical air termination final rod comprising of 300mm long x 25 dia. Copper rod with one pointed prong and 100mm dia x 3 mm thick base plate etc. complete in all respects
Supply and fixing of vertical down conductor of 32mm x 6mm G.I. strip etc. on approved clamp on surface for lightning conductor complete in all respect.(for five and above storeyed building)
Supply and fixing of testing joint of G.I. strip 32mm x 6mm and 150mm long with G.I. bolts and nut etc. complete in all respects.
Supply and laying of aluminium conducter, PVC insulated armoured, served, sheeted cable 1000 bolts grade at a depth of 750mm below ground level over a cushion of 75mm thick sand alround and protected with burnt bricks on sides and top on surface 95 sqmm 3.5 core
Supply & fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respects. The armouring of the cable shall be properly connected with the earth. 95 sqmm 3.5 core
Supplying and fixing of Palm / pin type copper tin plated cables sockets (lugs) to the cable leads, insuslating with tape and making of connections etc. complete in all respects as per direction of Engineer-Incharge. 95 sqmm
Supply and burying of 40mm dia x 4.5 metres long G.I. Pipe vertically for earthing having 12mm dia. Holes spaced 75mm apart drilled up to 2 metre from the bottom complete with earthing lead of No. 6 to 8 SWG GI wire in G.I. Pipe up to appron (and from appron to switch board the cost of G.I. wire and pipe will be extra) upto switch board, 30cm square C.I. box with hinged cover masonary enclosure, funnel at top, alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing.
Supply and burying of 600mm x 600 mmx6mm G.I. plate, vertically for earthing with its top atleast 3 mts. below ground level complete with 20mm G.I.pipe and funnel for watering and two earthing leads of No.8to10SWG G.I.wire in 15mm dia G.I. pipe upto switch board (from apron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm. square C.I. frame with hinged cover, masonary housing, alternate layers/of charcoal/ coke and salt at least 150mm thick alround etc. complete in
Supply and burying of 600mm x 600mm x 3mm copper plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and two earthing lead of two no. 8 SWG copper wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipe and copper wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. complete in all respects.
Supplying & Laying of 25mmx3mm G.I. Strip for earthing purpose as required complete in all respects.
Supply and laying of 32 mm x 6 mm G.I. strip from earth electrode directly in the ground as required complete in all respect
Supply and laying of 32mm x 6mm copper strip from earth electrode directly in the ground as required complete in all respect.
Supply & fixing of two number 8 SWG G.I. wire in 15mm dia GI pipe for earthing purpose as required complete in all respects.
A typical mettalic cover shed with gate for DG Set Size (4.25x2.5 SQM)
Proper foundation also to be provided for the protection of DG set.
Proper foundation also to be provided for the Transformer
M/S KHAN CONSTRUCTION
ANUSHKA BUILDERS AND COLONISER
stage.html
html • 0.02 MB
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .