Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.0 LAccepted-Finance | ₹41.0 L | L1 | Accepted-Finance Accept |
| 2 | L2₹41.3 LAccepted-Finance | ₹41.3 L | L2 | Accepted-Finance Accept |
| 3 | L3₹46.9 LAccepted-Finance | ₹46.9 L | L3 | Accepted-Finance Accept |
Updated dates
Tender Value
₹50.9 L
EMD Value
₹61,000
Closing Date
6 Jan 2026, 12:00 pmClosed
SE ETC-I Kanpur
SE ETC-I Kanpur
FOR ERECTION AND COMMISSIONING OF 220/33 KV 60MVA TRANSFORMERAT 220KV S/S PANKI UNDER ELECTY 220 KV S/S DIVISION PANKI KANPUR
2025_UPTCL_1098973_1
Short Term ET No-55/ETC-I(K)/2025-26
Open Tender
Electrical Works
90 days
SE ETC-I Kanpur
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,770
PNB A/C-0727002100004177
₹61,000
3 Feb 2026
13 Dec 2025
7 Jan 2026
13 Dec 2025
6 Jan 2026
13 Dec 2025
Dismentalling of old Panels in control room as per direction of supervising engineer after levelling including shifting the Panels from Control room to store and acessories including the latest cost of labour T&P cranes for proper completion of work
Fabrication of 3 mtr long electrodes with 4omm dia MS Round bar having 150 mm Long conical shape by due cutting straighting etc and then piercing it vertically inside the ground with top 700mm below the ground level including shifting of MS round bar from the storage place at substation to switchyard.
Laying of 40mm Dia MS Round bar, 700mm below the ground level by due cutting straighting welding, painting excavation of trenches , backfilling of trench after laying of earthmat include shifting of MS Round bar from storage place to switchyard.
Making of 150mm long lap joint of above laid 40mm dia round bar to connect with existing earth mat of substation by due cutting straighting welding etc
Making of 150mm long lap joint of above laid 40mm dia round bar by due cutting straighting welding etc
Making of cross joint of above laid 40mm dia round bar 700mm below the ground level by due welding at all four corners including providing and welding of suitable size of 4 No of MS angle pieces on opposite corners of cross joint.
Making of End joint of above laid 40mm dia round bar 700mm below the ground level by due welding at all four corners including providing and welding of suitable size of 4 No of MS angle pieces on opposite corners of cross joint.
Earthmat extension and strenghtening work Laying of earthmat in the extended switchyard of the substation along with connecting the newly laid earthmat with existing earthmat as per details below
Erection and Fabrication (if needed) of Lattice type main gantry and auxiliary structure their respective beams as per drawing/BOM is to be carried out by contractor. All the duly stacked members of structure are to be shifted from store to work site, tightening of nut, bolts washer, fastening of beams applying standard practise. Beams are to be fastened on the proper alighnment with existing column including latest cost of all labour T&P etc.
Laying and stringing of 220 KV 3 Phase Jack Bus bar of single ACSR Moose Conductor ( 1 job for each phase bus bar per section)
Laying and stringing of 33 KV 3 Phase Jack Bus bar of Twin ACSR Moose Conductor ( 1 job for each phase bus bar per section)
Erection of equipments in proper alignment with complete adjustment in switchyard on the erected structure or in control room as per manufacture drawing or as per direction of supervising engineer after levelling including shifting the equipment from store to working site etc along with their junction box, control cubicle and acessories including the latest cost of labour T&P cranes for proper completion of work
220 KV Transformer Control Panel
220 KV Transformer Relay Panel
220 KV Transformer RTCC Panel
245 KV SF6 Type circuit breaker with structure and modification if necessary
220 KV CT with junction box
220 KV Bus Isolator with PI and proper adjustment
220 KV Post Insulator on ALP Structure
198 KV Lighting Arrestor with surge counter
33 KV VCB with structure and modification if necessary
33 KV CT with junction box
30 KV Lighting Arrestor
33 KV Bus Isolator with PI and proper adjustment
Dismentelling of Fire Hut/store and again reerection of Fire hut/store after repairing to other location as per instruction of site engineer
Dismentelling of sand pit and again reerection of Sand pit after repairing to other location as per instruction of site engineer
Opening of trench cover , laying and dressing of following size control cable on the cable racks in the trenches from control and relay panel to various equipments for AC/DC connection of CT,CB,Isolator,junction box include shifting of cable drums from store to erection site & shifting back the balanced material to store again placing back the opened trench cover including latest cost of labour , T&P etc to complete the work satisfactorily
2Cx2.5 Sqmm
4Cx2.5 Sqmm
6Cx2.5 Sqmm
10Cx2.5 Sqmm
Termintion of following sizes of cable as laid above as per cable schedule and connection diagram, extending DC Supply from DCDB and AC Supply from ACDB, Control & Relay panel, Equipment, CT, Breaker, Isolator including making necessary holes in glands plates or box where ever required fixing of cable glands of approximate size and ferruling & crimping type, lugs and Nos. for each core including latest cost of required skilled material, Technician , T&P For proper completion of work
Earthing of Main and auxiliary structure equipment , trench and panels with the help of specified size MS Flat along with cutting,bending and straightining of MS Flat to give it proper shape Two coat if enamel based paint of green colour above red oxide primer layer at joint , riser strips in all sides of surface as per drawing of earthing and standard practise including latest cost of consumable material, T&P, Labour etc
Earthing with 75x10 mm MS Flat
Earthing with 50x6 mm MS Flat
Earthing with 25x6 mm MS Flat
Jumpering of equipment of 220/33 KV 60 MVA Transformer and associated 220KV Bay and 33KV Bay with the help of ACSR Moose to connect main bus bar and Jack bus with equipment and equipment to equipment with help of suitable clamp/connector including cutting,bending, shaping etc of conductor as per site requirement
Making of shielding Mesh for 220 KV LA by fabrication of 06 Nos 3 meter long electrode with 40mm dia MS round bar having 150mm long conical shape and then its piercing vertically in the ground with top 700mm below ground level and casting of MS Rod dia 40mm x 3 meter embedded in 100 mm dia of marconite and installation in soft soil and connection jointing the electrode with 75x10 mm size MS Flat by welding for making mesh, connecting the shielding mesh with main earth mat at 2 places and finally painting the shielding mesh/ earthing strip with anti-corrosive red oxide primer and 2 coats of green paint with digging of earth trench and its back filling. Two No. risers of 75x10 mm MS Flat shall be welded with existing main earth mat to Auxiliary structure, one separate riser will be taken from laid shielding Mesh to corrosponding 3 Nos LA through surge counter for making of proper Mesh. Note:-Each electrode considers as one job from above chemical earthing.
Making of shielding Mesh for 33 KV LA by fabrication of 04 Nos 3 meter long electrode with 40mm dia MS round bar having 150mm long conical shape and then its piercing vertically in the ground with top 700mm below ground level and casting of MS Rod dia 40mm x 3 meter embedded in 100 mm dia of marconite and installation in soft soil and connection jointing the electrode with 75x10 mm size MS Flat by welding for making mesh, connecting the shielding mesh with main earth mat at 2 places and finally painting the shielding mesh/ earthing strip with anti-corrosive red oxide primer and 2 coats of green paint with digging of earth trench and its back filling. Two No. risers of 75x10 mm MS Flat shall be welded with existing main earth mat to Auxiliary structure, one separate riser will be taken from laid shielding Mesh to corrosponding 3 Nos LA for making of proper Mesh. Note:-Each electrode considers as one job from above chemical earthing.
Providing, fixing and installation of Sign Board of 3ftx2 duly made of 2mm thick GI Plate painted with red oxide primer with 2 coating and then yellow bright and shiny yellow paint and painted with black letter as direction of site engineer board shall be provided with black support frame size 35mmx35mmx5mm with provision of 2 leg for grouting duly painted with black enamel paint complete with all respect to be grouted with casting of C.C. Foundation
Work of loading, safe carriage and unloading of any equipment, structure or any other material from any substation of UPPTCL to JE Store of 220 KV S/S Panki. Every to and from carriage from 220 KV S/S Panki will be considered as one job.
Transformer Works
Complete erection of 60 MVA make 220/33 kv capacitytransformer by erection of radiators canservator tanks. All bushing their turrets connecting oil pipe lines, cooling fans (including cable connections on T/F body), motor drive mechanism of tap changer, rtcc panel, oil pumps and associated oil pipe line etc to completion the job satisfactorily including attending the oil leakage, if any and all other associated works for satisfactory completion of all other associated works for satisfactory completion of work. no T&P shall be provided by the deparment
Shifting of main tank of 60 MVA T/F 220/33 KV make at 220 KV S/S Panki Kanpur from unloading point in switchyard to newly constructed plinth of 60 MVA T/F approx 20 mtr distance including all T&P and all other works required to complete the job satisfactory as per technical specification
Additional shifting of 5 mtr or part there of
Shifting of 50 KL oil tank from any substation of UPPTCL to 220 KV S/S Panki Kanpur
Draining out 45 KL oil tank 209 Ltr oil drums to 50 KL tankstanks including shifting of drum within the S/S p r e m i s e s
centrifuging of complete transformer oil approx 45 KL i n 50 KL oil tank by connecting centrifuging pipes etc
Creating vacumm in 60 MVA make Transformer up to level of 760 mm of Hg inside tank
Filling of 45 KL T/F oil from 50 KL tank. To main tank conservator & radiator.
Centrifuging of complete transformer oil in transformer main tank or oil tanker by cennecting centrifuging Machine arranged by contractor and taking the B.D.V values of the oil periodically till the required values is achieved as per direction of supervising engineer
Control cable laying and termination from marshalling box of 60 MVA|Transformer to control panel, relay panel and marshalling box to RTCC panel of different size cables, all cable ferrule,cable gland of various size is to be provided by the contractor as per required complete the job satisfactorily
Chemical Delta earthing constsisting of fabrication of 3 Nos. 3 mtr. Long electrode (40 mm dia MS Bar) its placing 700 mm below ground and casting of MS Rod dia 40mm x 3 meter embedded in 100 mm dia of marconite and installation in soft soil and connection of all 3 electrode with 75X10mm MS Flat and connection the same with main earthmat at two places. MS Bar flat and angle will be provided by the department. Note:-Each electrode considers as one job from above chemical earthing.
Earthing of 60 MVA Transformer body , neutral of T/F motor drive mechanism ,marshalling box. RTCC panel with 75X10mm. 50X6mm, MS flat as per required and its joining with already laid earth mat at 2 places with necessary modification in existing support structure for earthing. of green colour in two coats and all other associated work complete the work satisfactorily . MS Flat and angle will be provided by the department.
Emulsifire supply, erection & commissioning work
Supply, Fabrication and laying of following type MS Pipe line above the ground make with support (support is made on Ground level above 300 mm above and below ground level 200 mm below with Cement coarse,sand and concrete /Bricks balast as per standard specification with saction angle,U clamp suitable size for holding following MS pipe line per drawing and specification complete with associated work like cutting,bending,welding including fixing bend/elbow, tee,socket, flanges etc. and Above work also including crossing of roads and cable trenches underground digging the earth,RCC/PCC road and Finally filling, leveling of earth including concreting of road crossing as per standard ratio of RCC/PCC & Underground pipe line should be anticorrosive treated by bituminous painting and all pipe line with one coat red oxide and two coat synthetic enamled paint of Berger/Assian make. Including hydraulic testing of Pipe line at 15 kg/sqcm.(Jindal,Apollo,Tata make).
Spray Nozzle SD 17-5
QB Detector
Pressure switch/guage as per IS Specification 3624 Accuracy 5%
Supply &instalation testing commisioning of quick opening flood deluge valve with sprinkler alert alram of HD/Mather/Plate of 150 NB as per maximaum working pressure 10KG/cm2
Supply and installation testing of "Y" type strainer (Karter/sir/agra/kalpana) make of dia 150 NB working pressure 10KG/cm2
Supply along with installation, testing & commissioning of gate valve (Sludge Valve/Butterfly Valve) (Kartar/Sir/ Zoloto make) as per IS Specification (is Code: 14846) of
Provide and fixing one coat of 4mm pypwrap/coatax antirust pipe protection including primer and lap of 25mm on external buried pipe including surface preparation complete in all respects .
Supply & instalation of flange as per IS-1538 of different size as per drawing work include proper butt welding with pipe & proper packing and coupling with Nut bolt (1 set = 2 No flange)
Fabrication and erection of MS angle Plyon support for holding the air and water ring including latest cost of all material,cutting ,welsing and clamping with u- Bolt ans all other associated work
Construction of RCC foundation in the ratio of 1:2:4 of cement ,sand ,stone ballast (20 mm) for fixing of interconnecting M.S. pipe line with necessary support base plate with due grouting of 4 Nos foundation eye bolts.
Supply & installation testing commissing of fire hose boxes suitable for 15 mtr long, 63 mm dia reinforced rubber lined fire hose pipe (as per IS-636) with gun metal branch pipe nozzel (As per IS -903) and gunmetal landing valve of 63 mm dia(As per IS code 5290). (1Set =15 meter long RRL hose pipe with gunmetal nozzel+15 meter long gun metal male and female coupling pipe for quick assembling with existing branch pipe+63 mm gun metal hydrant landing valve + box)
Complete integration, reinstalling and recommissioning of master control panel in the pump house room with newly installed mulsifier system at 220/33 KV 60 MVA transformer this include provision of repairing/replacement of battery charger, replacement of malfunction relay alarm system, auto-manual working of pump including all siklled labour, material,commissioning latest cost.Then complete overhauling of75KW electric motor driven main fira pump with end suction type capacity 210 Mtric cube per hour which inclide installation of water gland and seats and 2 coats of paint.after that complete overhauling of 11KW electric motor driven main jockey pump with end suction type capacity 11
Mtric cube per hour which inclide installation of water gland and seats and 2 coats of paint
33 KV PTPS Bay Shifting
Safe Dismantling of 33 KV 1250 Amp Bus Isolator by opening all male, female Jaw blade and shifting it from site to store
Safe Dismantling of 33 KV VCB by opening all Connectors and shifting it from site to store
Connection of 33 KV PTPS Bay to Existing 33 KV NTPC Bay 3x300 mm' size XLPE Power Cables (including 1 No. spare cable) alongwith other associated works
Providing and laying of 33 KV 3x300 sqmm sixe XLPE Cable ( 1 No. Spare cable ) in 33 KV Power evacuation cable Trench
Providing of outdoor end termination jointing kits and making the end termination joints of the above laid 2 Nos. 33 KV 3x300 mm' size XLPE Power Cables (1 No, spare cable)
Switchyard Lighting
Providing & Fixing of 125 Watt L.E.D. Street Light Luminaries Fittings of Philips / ComptonGreaves / Havells make in Single Piece Die Cast Aluminium Alloy Housing with Pot Optics Reflector & Toughened Clear Glass Cover with Frame for Lamp Compartment incuding Cable Terminations.
Providing & Fixing of G.I. Pole Bracket duly made of 40 mm dia. 1.2 Meter Long 'B" Class Pipe and Bent at One End by Quarter Circle in 1.0 Meter at an Angle of 30° for Fixing of 125 Watt LED Street Light Luminaries Fittings on G.I. Column Structures with help of M.S. Clamps.
Providing of Junction Box of size 280 x 225 x 150 mm duly made of 16 SWG Sheet and Painted with Smoke Grey Colour Synthetic Enamel Paint and Fitted with 1 No. 6 Amp. SP MCB on Anodized M.S. Channel, 1 No. Bakelite Fuse Fitting with 6 Amp. NS 6 type HRC Fuse, 1 No. Copper Neutral Link, Bakelite Terminal Block of 4 Terminals, Cable Glands suitable for 2C / 4C x 2.5 mm' size Incoming / Outgoing Control Cables etc., then Installation of Junction Box on G.I. Column Structures at designated Height with the help of suitable M.S. Clamps alongwith Earthing of the Junction Box with 12 SWG G.I: Wire including Cable Terminations with Satisfactory Testing & Commissioning.
Providing of 3 Phase L.T. A.C. Supply Cubical of size 1200 x 600 x 500 mm with Hinged Door and Proper Locking Arrangement duly made of 16 SWG M.S. Sheet and Painted with Grey Colour Synthetic Enamel Paint. The L.T. A.C. Supply Cubical should be Fitted with 3 No. 100 Amp. Copper Neutral Link, 4 No. 100 Amp. Aluminum Bus Bar (3 Phase + Neutral),5 No. 32 Amp. TPN MCB, 6 No. 40 Amp. DP MCB, 40 No. Link type Terminal Bock, Cable Glands etc. with Internal Wiring and then Installation on M.S. Angle Frame Structure duly Grouted in Ground by due Construction of Concrete Plinth
Earthing of L.T. A.C. Supply Cubical with Providing & Fixing of 600 x 800 x 8 mm size G.I. Plate with its Top At Least 3 Meter below the Ground Level with 20 mm dia. G.I. Pipe & Funnel for Watering, 1 No. 8 SWG G.I. Wire Earthing Lead etc. with Alternate Layer of Charcoal / Coke and Salt At Least 150 mm Thick Around it
Laying of Following sizes PVC insulated Copper Control Cables from L.T. A.C.D.B. Cubical to various Junction Boxes & Junction Boxes to Junction Boxes for Switchyard Lighting through Excavated Trench of size 300 x 600 mm, Covering the Cables with River Sand & Brick Lining Along and Over the Cable, then Back Filling & Leveling of the Trench after Laying of Cables :
4Cx2.5 mm2 size Control Cable
2Cx2.5 mm2 size Control Cable
Laying of 2C x 2.5 mm' size Control Cables form Junction Box to LED Street Light Luminaries Fittings through Inside the M.S. Pole / GI Structure including necessary Fixing of Cable on GI Structure.
Laying 3 ½ x 70./ 50 mm. LT Power Cable, 50 cm below the Ground Level after Excavation of Trench, Laying the 1« Class Brick Lining, Filling of River Sand Along & Over the Cable, then Back Filling & Leveling the Trench after Laying of Cable. The Work also includes Termination of Cable on both sides with Crimping of Lugs.
Providing & Fixing of Cable Marker Duly made of cast iron
Other Misc Works
Shifting,Sorting, weighting, Loading, Unloading & Carriage of various type transmission line and substation material by private carrier (Dist Approx 1.5 KM)
Agumentation of 220/33 KV, 60 MVA transformer bay into existing Bus bar protection at 220 KV S/S Panki Kanpur.
Retrofitting of 33 KV Numeric IEC 61850 Compiled overcurrent earthfault and high speed master trip relay of Siemens/ABB/ALSTOM Make on 33 KV NTPC Feeder Panel. The work also includes preparation of interconnection drawing. Modifications in internal wiring on existing panel for the 33 KV Numerical relay, annunciation fascia & high speed master trip relay with all connection and termination with erection testing commissioning and setting of 33 KV Numeric overcurrent earthfault relay & high speed master trip relay
Supply and fixing of 2 Ton Window Type AC with stabalizer in the control room make HITACHI/O-General/Mitishubushi complete will all associated accessories having 2 Year comprehensive and 5 Year compressor warranty due to not availibilty of air conditioning in new extended control room
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.36 MB
Tendernotice_2.pdf
PDF • 1.08 MB
BOQ_2024333.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid