Executive Engineer PWD Howrah Electrical Division
Office of the Executive Engineer PWD Howrah Electrical Division Onkarmal Jetia Road Howrah 711103
E.I works including air-conditioning, UPS and other utilities associated with the construction of new blood bank with component separation room at Howrah (RN-18000324)---------SITC of UPS.
2018_WBPWD_199697_1
WBPWD/EE/HED/NIQ-71 of 2018-2019
Open Tender
Miscellaneous Works
Item Rate
15 days
Howrah District Hospital
Please refer Tender documents.
11 documents required · 11 mandatory
₹10,551
26 Nov 2021
5 Dec 2018
17 Dec 2018
6 Dec 2018
14 Dec 2018
6 Dec 2018
Amount
Supply,installation, testing and commissioning of 20KVA ( 3 Phase Input & 3 Phase Output - Conventional UPS) with In-built Isolation Transformer & 30 Min Back up each (Total VAH 20160 each) Technology-True O-line Double Convertion(VFI-SS-III) including supply,delivery,installation of battery bank and battery stand (as per battery bank dimension) having base at a height of 2ft raised from the floor level (Make-APC/Numeric/Better Power/ AVO)
Input parameters
Nominal Voltage-380/400/415VAC 3Ph+N+PE
Operating Voltage Range- 323-478VAC
Operating Frequency Range- 45-55Hz.
Power Factor >= 0.99
Bypass Frequency Range- ± 10%
Harmonic Distortion(THDi) ≤ 5% at rated load
Output parameters
Output Voltage-380/400/415VAC, 3Ph+N+PE
Power Factor = 0.9
Voltage Regulation ± 1% (Balanced load)
Frequency(Online Mode)- ± 10%( With Sync Mode & Adjustable)
Frequency(Battery Mode)- ± 0.1 Hz
Harmonic Distortion(THDv) ≤ 2% (linear load) & ≤ 5% at non-linear load
Isolation transformer-Inbuilt
Crest Factor= 3:1
Cold Start = Available
Overload ≤110% for 60 min, ≤125% for 10 min, ≤150% for 60s
Efficiency= 94%
Battery
Battery Voltage- 16/18/20 nos.
Battery Type- VRLA-AGM maintenance free.
Communication
Standard-LCD display,LED indication,RS 232 port, RS 485 port, Dry contact
Environment
Operating Temperature 0 deg C to 40 deg C
Relative Humidity Range- 0-95%(non condensing)
Noise Level- <70db
NOTE: This is an additional work of a installed syatem. All the detector and devices should be configure in the existing Panel.
Note : 1. The Agency must procure the materials from the Manufacturer/OEM or from their authorized sales channel so that the standard warranty/Support of the Manufacturer/OEM becomes applicable to the products to be delivered and installed.
2. Documents that authenticates such procurement from the Manufacturer/OEM and standard warranty/Support should be sent from the e-mail of the Manufacturer/OEM to the e-mail of Engineer-in-Charge and hard copy must be submitted during execution of work/submission of bill with OEM letter head/Signature of authorized person & rubber Stamp.
3. Certification in original from the manufacturer/OEM, as the case may be, regarding originality of the material must be submitted before any payment.
4. Rate should be quoted including all Taxes (if any).
SIMPSON AND FERRIS PVT LTD
MAHESWAR ELECTRICAL INDUSTRIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .