Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 29 31 32 NEW INDUSTRIAL AREA MANDIDEEP 462046 MP INDIA | MANDIDEEP | RAISEN | MADHYA PRADESH | 462046 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
15 Apr 2021, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, TLMD-IV, Jammu
Office of Executive Engineer, TLMD-IV, Ambedkar Road, Jammu
Capital Maintenance of 2 no 160MVA, 220 BY 132KV BHEL Make Transformer under Supervision of BHEL S Service Engineer at Grid Substation Barn, Jammu
2021_PDD_118986_1
TLMD-IV/J/17 of 2020-2021 Dated 03/03/2021
Open Tender
Electrical Works
Turn-key
90 days
GSS BARN
AS PER NIT, SBD AND SCOPE OF PROJECT
4 documents required · 4 mandatory
₹2,000
Yes
Convener, purchase committee, Directorate of ISM
Exempted
Executive Engineer, TLMD-IV, Jammu
16 Aug 2021
3 Mar 2021
17 Apr 2021
3 Mar 2021
15 Apr 2021
13 Mar 2021
5 Mar 2021 - 13 Mar 2021
10 Mar 2021
180 days
SUPPLY OF MATERIAL, ERECTION, TESTING, COMMISSIONING, STORAGE, HANDLING, PRESERVATION AND ALL OTHER ALLIED WORKS
Plugging leakage from all points by way of replacing gaskets/replacement of all gaskets after dismantling of bushings/turrets/main tank covers/inspection covers or by other procedures where gaskets are not used after approval from JKPTCL, internal inspection of Transformer for root cause analysis of fluctuation in fault gases and there of submission of detailed report for 160MVA, 220/132kV BHEL make Transformer bearing S.No: 2021879. After internal inspection minor corrective measures if required has to be taken at site and its cost shall be included in the bid.
Plugging leakage from all points by way of replacing gaskets/replacement of all gaskets/replacement of all gaskets after dismantling of bushings/turrets/main tank covers/inspection covers or by other procedures where gaskets are not used after approval from JKPTCL, internal inspection of Transformer for root cause analysis of increase in oil level of OLTC conservator tank and there of submission of detailed report for 160MVA, 220/132kV BHEL make Transformer bearing S.No: 2021292. After internal inspection corrective measures if required has to be taken at site and its cost shall be included in the bid.
Filteration of oil of 160MVA, 220/132KV Transformers approximate oilquantity in Transformer is 50.92KL
Painting of 160MVA, 220/132 KV Transformers with non-inflammable paint as per the procedure detailed by the OEM
Testing of Transformer after carrying out all the works
Total Amount FOR MATERIAL REQUIRED FOR PLUGGING OIL LEAKAGE AND OTHER PROBLEMS IN 02 NO. 160MVA, 220/132KV BHEL MAKE TRANSFORMER(Individually to be quoted in relevant Schedule in Financial Bid Packet i.e Schedule-A)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .