Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.0 LAccepted-AOC | ₹7.0 L | L1 | Accepted-AOC accepted through transparent lottery system |
| 2 | L1₹7.0 LRejected-AOC | ₹7.0 L | L1 | Rejected-AOC rejected through transparent lottery system |
| 3 | L1₹7.0 LRejected-AOC | ₹7.0 L | L1 | Rejected-AOC rejected through transparent lottery system |
| 4 | L1₹7.0 LRejected-AOC | ₹7.0 L | L1 | Rejected-AOC rejected through transparent lottery system |
Tender Value
₹8.3 L
EMD Value
₹8,257
Closing Date
8 Jan 2026, 5:00 pmClosed
EE RW Electrical Division Sambalpur
RURAL WORKS ELECTRICAL DIVISION, SAMBALPUR
Provision of Transformer for Tahasil office at Kishorenagar for the year 2025-26 Under RWES Angul Non Res Building
2025_CERWI_123882_1
EE/RWELECT/SBP/28/2025-26
Open Tender
Electrical Works
60 days
Angul
Please refer to Tender Documents
2 documents required · 2 mandatory
₹4,000
₹8,257
Yes
2 Mar 2026
27 Dec 2025
9 Jan 2026
27 Dec 2025
8 Jan 2026
27 Dec 2025
WPB (GI) Pole 160x152 (11Mtr. Long, 30.44KG/Mtr.)-DP (Total Pole Weight with Base Plate & Stiffner=334.84 KG+10.74 KG= 345.58 KG)
Top Channel(GI) GI 100 X 50 X 6 MM (3000 mm long) (9.56Kg./Mtr, 2 No's.) (Each 2x3.000x9.56= 57.36 Kg)
Fish Plate(GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 6 no's required = (6x2.36x0.280)
M.U Channel(GI) GI 75x40x4.8 mm (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 42.84 Kg)
AB Switch Mounting Channel(GI) 75x40x4.8 mm GI Channel(GI) (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 42.84 Kg)
AB Switch Side Support Channel(GI) 100X50X6mm,9.56 KG/Mtr., each Channel(GI) length 0.35 mtr., 2 no's Channel(GI) required =( 9.56x2x0.35)
Channel(GI) Support for down Pipe 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI) length 0.8 Mtr., 1 no's Channel(GI) required =( 7.14x0.8x1)
HG/ DO Fuse Mounting Channel(GI) 75x40x4.8 mm GI Channel(GI) (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 42.84 Kg)
Cantilever Support Channel(GI) 75x40x4.8 mm GI Channel(GI) (810 mm long,2 No's.) (7.14Kg./Mtr., 2 No's.) (Each 2x0.810x7.14= 11.57 Kg)
Cantilever Support Angle(GI) 50 X 50 X 6MM GI (1282 mm long) (4.5Kg./Mtr, 2 No's.) (Each 2x1.282x4.5= 11.54Kg)
Transformer Base GI Channel(GI) 100 X 50 X 6 MM (3000 mm long) (9.56Kg./Mtr, 2 No's.) (Each 2x3.000x9.56= 57.36 Kg)
Transformer Base Support GI Channel(GI) 100 X 50 X 6 MM (515 mm long) (9.56Kg./Mtr, 2 No's) (Each 2x0.515x9.56= 9.85Kg)
Transformer Belting Angle(GI) 50 X 50 X 6MM GI (3000 mm long)(4.5Kg./Mtr, 2 No's) (Each 2x3.0x4.5 Kg)
Transformer Belting Support Angle(GI) 50 X 50 X 6MM GI (580 mm long)(4.5Kg./Mtr,2 No's) (Each 2x0.580x4.5= Kg)
LTDB Mounting Angle(GI) 50 X 50 X 6MM GI (1000 mm long)(4.5Kg./Mtr, 2 No's) (Each 2x1x4.5 Kg)
50x6mm Flat(GI) for earthing, 2.36kg/mtr., (2.5x7 mtr. For mesh formation, 12 Mtr. For LA and 2.5 mtr. For raising, 11 mtr for AB switch, 2.8 mtr for HG Fuse, 5x2 mtr. for DTR Nutral, (1.3+4.5) mtr. For DTR Body, 0.500 mtr for LTDB & AB Switch operating handle, 3 mtr. for Fencing) ( Each 65.6x 2.36= 154.81 Kg)
63 KVA , 11/ 0.4 KV (AL) Transformer, BIS Energy Loss level II, Ammendment-4
LT Distribution Box with MCCB, Aluminium Busbar of single Bay with kit kat fuse for 63 KVA S/S
55 SQ.MM. AAAC XLPE Covered Conductor
4 Cx 95 mm2 LT XLPE Cable(Armoured) - FOR 63 KVA Trf.
4 Cx 95 mm2 LT XLPE Cable(Armoured) - From LTDB to Pole
AB Switch(11KV,200A.3pole,50Hz)
H.G.Fuse( 11KV.200A.3Pole)
WEDGE CONNECTOR FOR 55 SQMM.CONDUCTOR
POLYCARBONATE BIRD GUARD
Disc insulator (B&S)70 KN polymer
H W fitting (B&S)70KN(3bolted)
Lightning Arrester(12KV,10KA) Station Class 2
11KV pin insulator polymer
HT stay set complete
HT stay Clamp (1.9Kg/pair)
HT stay insulator TYPE-C
7/10 SWG GI stay wire, Grade -2 (15Kg./ Set)
40 mm Nominal bore GI pipe (medium gauge) earthing device with 3 mtr .Long
GI Nuts & Bolts of Assorted size (25 Kg/ DSS DP)
GI Barbed wire/Anticlimbing device (3Kg /Pole)
Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 8 no's = (8x0.59x0.510)
Danger plate 11kv
Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 2 no's = (2x0.59x0.510)
Name plate
Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
Black Colour Paint(GIS Numbering & Zebra Stripping) for numbering
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1800mm) = 0.450Cu.mtr(Per Pole) (For WPB Pole)
Couping ratio 1:1.5:3(M-20 Grade) (500mmX500mmX450mm) = 0.113Cu.mtr(Per Pole)
PCC ratio 1:3:6(M-10 Grade) For DSS Area (5X3X0.1)= 1.5 Cu. mtr.
Fixing of stay set with 0.5Cum cement concrete foundation 1:3:6(M-10 Grade) size ( 900mmx600mmx900mm) using 40mm BHG metal with all labor and material except stay set , stay wire , stay insulator .
Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI) around pipe .
Laying of 4 Cx 95 mm2 LT XLPE Cable
SITC and Erection of GI Fencing with Gate
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1500mm) = 0.375Cu.mtr(Per Pole) (For PSC Pole)
Supply of AL Lugs suitable for 95 sq mm cable/conductor, Crimping with cable and Fixing/connecting include supply and erection of PVC Tape as per voltage requirement.
Supply and erection of double Compression Flameproof Type Glanding for armored Cable 3.5/4C 50-95sqmm including making hole in Base plate and dressing of cable along with vermin proofing properly .Supply to be done as per TPCODL Spec and approved make dowells.
PSC POLE 10 METER LONG 330 KG.
PSC Pole Clamp(GI)
Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 1.2 mtr., 2 no's Channel(GI) required =( 2x9.56x1.2)
Fish Plate(GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 8 no's required = (8x2.36x0.280)
Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 0.306 mtr., 2 no's Channel(GI) required =(2x9.56x0.306)
Danger Plate, 1 no's.
Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 1 no's = (1x0.59x0.510)
GI barbed wire anticlimbing device 3 Kg. Per support
Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 4 no's = (4x0.59x0.510)
11 KV pin insulator polymer
H W fitting(B&S) 70KN, 3Bolt
Disc insulator (B&S) 70 KN polymer
Earthing of Support ( Coil Type )
No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing
NON METALLIC TIES -11KV 55SQMM CVRD AAAC
IPC for 55 sq.mm AAA conductor (For covered conductor)-11kV
Spike (GI ) (using 50x6mm Flat(GI) welded with 8 mm square bar) ( 2 Nos of spike per Set in each Pole )
GI Nut , Bolt & Washer of different sizes (7.433 Kg each Cut Pole)
Black Paint(GIS Numbering & Zebra Stripping)
Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1667mm) = 0.42Cu.mtr(Per Pole)
9 Mtr. long 300 Kg. PSC Pole
LT Stay set Complete
7/12 SWG GI stay wire, Grade -2
LT stay Clamp ( 1.40Kg/pair)
LT Stay insulator
Pole clamp for EYE hook for (XLPE Aerial bunched Cable)
EYE hook for XLPE Aerial bunched Cable
Dead End Clamp suitable for messenger XLPE Aerial bunched Cable
Suspension Clamp with EYE hook for ABC
4C×35 mm² (P)+1C×35 mm²(M)+1CX16 mm²(Street Light) (LT AB Cable)
Insulated piercing connector.Type-A-main 50 to 150 sq.mm & Tap-50 to 150 sq.mm
Coil Earthing
No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing
Danger plate (LT)
Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 1 no's = (1x0.59x0.510)
GI barbed wire anticlimbing device 3 Kg. Per support
Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 4 no's = (4x0.59x0.510)
GI Nut , Bolt & Washer of different sizes (0.5 Kg/ Pole)
Black Paint(GIS Numbering & Zebra Stripping)
Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
Fixing of LT Complete stay set includes 1) Turn Buckle Assembly 2) Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire. 5)Stay clamps with Nuts & bolts, including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size (500mmx500mmx800mm) using 20mm BHG metal with all labour and material (Excavation of earth will be done of size 500X500X1500 mm.)
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1500mm) = 0.375Cu.mtr(Per Pole)
S/F of 1.5 Ton 5 star Inverter type split A.C. M/C with 4 KVA Voltage Stabilizer(110V-300V) (Make - Microtek, V-Guard) and AC stand with all accessories and connections and installation (Make - HITACHI/ Bluestar/ Carrier)
Laying of 4 Cx 95 mm2 LT XLPE Cable
Laying of 4 Cx 95 mm2 LT XLPE Cable
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_573490.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.78 MB
Tendernotice_2.pdf
PDF • 0.70 MB
BOQ_573490.xls
BOQ • 0.43 MB
Download all tender documents and submit your bid