| 1.00Stage Contract for Maintenance of 33/11 KV Receiving Stations in respect of STD Ganderbal | |||||
| 2.00 | Supply, Fabrication, testing and Commissioning of PVC insulated Copper Bus Bar including nuts and Bolts.(The job includes necessary modification fabrication of Busbar as per requirement & alignment to existing Panels). | 1 | Kg | 2,200 ₹2,200 | 1,350 ₹1,350 Lowest |
| 3.00Supply installation Testing & Commissioning of 11 KV Vacuum Interrupters (800A/600A as per already installed) for below make.The job includes dismantling of damaged interrupter. | |||||
| 3.10 | Vijai, Easun Reyrolle, Alind, Alind, Electric Field, Pasca, Crompton, ABB, and out door type 11kv Breakers. | 1 | No | 29,000 ₹29,000 | 24,900 ₹24,900 Lowest |
| 3.20 | Sudhir, Schneider | 1 | No | 30,000 ₹30,000 | 26,000 ₹26,000 Lowest |
| 3.30 | Installation/Fixing, Testing & Commissioning of 11 KV Vacuum Interrupters of above makes including dismantling of damaged interrupter. | 1 | Job | 6,000 ₹6,000 | 900 ₹900 Lowest |
| 4.00Supply installation Testing & Commissioning of 11 KV vacuum Interrupters Housing of below mentioned make. | |||||
| 4.10 | Vijai and Easun Reyrolle (Per Phase) | 1 | No | 12,000 ₹12,000 | 11,000 ₹11,000 Lowest |
| 4.20 | Alind (Assembly upper set/ Lower set). | 1 | No | 16,000 ₹16,000 | 15,000 ₹15,000 Lowest |
| 4.30 | ABB/Electric Field/Crompton/S&S ( per Phase) | 1 | No | 7,500 ₹7,500 | 500 ₹500 Lowest |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
3 Oct 2025, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUTIVE ENGINEER STD GANDERBAL
DIV OFFICE STD GANDERBAL
Stage contract for Maintenance of 33_11 KV Receiving Stations for District Ganderbal - Bandipora in respect of STD Ganderbal for the Year 2025-26 OR till next Stage Contract is finalized.
2025_PDD_287938_1
STDGBL e-NIT NO 19 OF 2025-26 DATED 11-09-25
Open Tender
Electrical and Maintenance Works
Item Wise
7 days
Ganderbal_Bandipora
refer SBD
8 documents required · 8 mandatory
₹1,500
EXECUTIVE ENGINEER STD GBL
₹30,000
9 Oct 2025
11 Sept 2025
4 Oct 2025
13 Sept 2025
3 Oct 2025
15 Sept 2025
13 Sept 2025 - 15 Sept 2025
Amount
Stage Contract for Maintenance of 33/11 KV Receiving Stations in respect of STD Ganderbal
Supply, Fabrication, testing and Commissioning of PVC insulated Copper Bus Bar including nuts and Bolts.(The job includes necessary modification fabrication of Busbar as per requirement & alignment to existing Panels).
Supply installation Testing & Commissioning of 11 KV Vacuum Interrupters (800A/600A as per already installed) for below make.The job includes dismantling of damaged interrupter.
Vijai, Easun Reyrolle, Alind, Alind, Electric Field, Pasca, Crompton, ABB, and out door type 11kv Breakers.
Sudhir, Schneider
Installation/Fixing, Testing & Commissioning of 11 KV Vacuum Interrupters of above makes including dismantling of damaged interrupter.
Supply installation Testing & Commissioning of 11 KV vacuum Interrupters Housing of below mentioned make.
Vijai and Easun Reyrolle (Per Phase)
Alind (Assembly upper set/ Lower set).
ABB/Electric Field/Crompton/S&S ( per Phase)
Sudhir and Schneider (Per phase)
Outdoor type PCVCB upper and lower part(Per phase)
Installation, testing and commissioning of 11KV vacuum Interrupters Housing of above mentioned make including dismantling of damaged assembly.
Supply Installation, testing and commissioning of of 11 KV CTs indoor type cast resin of following make and ratios including dismantling of damaged CT's and transportaion of Red material back to Divisonal store.
750-375/5-5-5A Metering, Protection and Differential Core
800-400/5-5-5 A Metering, Protection and Differential Core
600-300/5-5-5 A Metering, Protection and Differential Core
600-300/5-5 A Metering and Protection Core.
400-200/5-5 A Metering & Protection Core
300-150/5-5 A Mertering & Protection Core
100-50/5-5 A Metering & Protection Core
40-20/5-5A Metering & Protection Core
Installation, testing and commissioning of 11 KV CTs indoor type cast resin of above makes & Ratios including dismantling of damaged CT's and Transportation of new set from divisional store to site including transportaion of Red material upto Divisonal store. (The job includes identification of damaged part so that exact part can be arranged from OEM)
Supply, Installation, Testing and commissioning of Energy meter of Secure make with latest series premier 5000 of 11kv level and 33kv level with 5A secondary. 11kv/110v-5A / 33kv/110v-5A
SITC of G.I channel iron, angle iron, flat iron etc including necessary fabrication as per requirement including paint job.
Supply, Installation, testing and commissioning of 11 KV CT's outdoor type Dead tank type including dismantling of damaged CT's. (CT set to be provided should be of OEM as per already installed CT set) (The job includes identification of damaged part so that exact part can be arranged from OEM) including transportaion of Red material upto Divisonal store.
600-300/5-5-5 A Metering, Protection and Differential Core
400-200/5-5A Metering, Protection and Differential Core
400-200/5-5A Metering & Protection Core
SITC of 11 KV PT set indoor type (11KV/110V) ER, Electric Field, Alind etc.
SITC of 11 KV PT indoor type (11KV/110V) of Schneider, CG etc.
SITC of 11 KV outdoor Dead tank type PT's ( 11KV/110 V).
Installation, testing and commissioning of 11 KV PT's (11 KV/110 V) indoor type and outdoor type including Transportation of new one from divisional store or otherwise to site including dismantling of existing PTs & transportation of Red Material upto Divisional Store
Supply Installation, testing and commissioning of 33 kV Current Transformer with Metering and Protection core, P S Class (36kV, 70kV (rms), 170kVp, 25 KA for 3 sec, Accuracy 0.5, Burden 30 VA, 1Φ, Outdoor) (1 No per Φ) of following ratios.
400-200/5-5-5 A (Metering, Protection and Differential Core )
250-125/5-5-5 A (Metering, Protection and Differential Core )
Installation, testing and Commissioning of 33 kV Current Transformer including Transportation of new one from divisional store or otherwise and Transportation of Red item back to Divisional store.
Supply Installation, testing and commissioning of 33 kV PT's (33 kV /110 V single Phase outdoor type Potential Transformers
Installation, testing and Commissioning of various 33 KV PT's
Supply Installation, Testing and Commissioning of 11 KV VCB Panel including Transportation from divisional store and supply of all accessories, clamps & Stand for commissioning of panel in (along with GTP and Test Certificate)
Installation, Testing and Commissioning of 11 KV VCB Panel and supply of all accessories, clamps & Stand for commissioning of panel.
Supply, installation, testing and commissioning of items in 33 KV C&R Panel of make OEM (The job includes identification of damaged part so that exact part can be arranged from OEM)
Master Tripping Relay 4NO + 4NC, 36 Volt DC
TNC Switch 25 Amp.
Tripping/Closing coils with housing complete 300 W Burden
Repairing of items in 33 KV C&R Panel.
Master Tripping Relay 4NO + 4NC, 36 Volt DC
TNC Switch 25 Amp.
Supply,Installation, testing and Commissioning of various 33 KV VCB including supply of all accessories, clamps & collars for commissioning of VCB (along with GTP and Test Certificate)
Installation, testing and Commissioning of various 33 KV VCB including supply of all accessories, clamps & collars for commissioning of VCB
Supply,Installation, testing and Commissioning of various 33 KV C&R Panel including supply of all accessories, clamps & Stand for commissioning of C&R panel including Transportation from divisional store including earthing termination complete Job (along with GTP and Test Certificate)
Installation, testing and Commissioning of various 33 KV C&R Panel including supply of all accessories, clamps & Stand for commissioning of C&R panel including Transportation from divisional store including earthing termination complete Job.
Supply installation Testing & Commissioning of G I Pipe 9" Dia, 10 feet Long, 6mm thick along with Top end Base Plate (450mm x 450mm).
Supply installation Testing & Commissioning of G I Pipe 6" Dia, 10 feet Long, 6mm thick along with Top end Base Plate (450mm x 450mm).
Supply, installation, testing and commissioning of items of 33 KV VCB (The job includes identification of damaged part so that exact part can be arranged from OEM)
33 KV Porcelain Post Insulator
Operating Rods
Closing Coils with Housing
Tripping Coils wih Housing
Contactor
Gasket
Operating Shaft
Mechanism Housing
Gear Assembly
vacuum/gas charging valve
Input/Output housing terminal pads
Repairing of items of 33 KV VCB
Operating Rods
Operating Shaft
Gear Assembly
Supply of 33 KV Vacuum Interrupters (1250A as per already installed) for below make.
Vijai, Easun Reyrolle, Alind, Alind, Electric Field, Pasca, Crompton, ABB, and out door type 11kv Breakers.
Sudhir, Schneider
Installation/Fixing, Testing & Commissioning of 33 KV Vacuum Interrupters of above makes including dismantling of damaged interrupter Including transportation of Red Material upto Divisional Store).
Supply of 33 KV vacuum Interrupters Housing of below mentioned make .
Vijai and Easun Reyrolle (Per Phase)
Alind (Assembly upper set/ Lower set).
ABB/Electric Field/Crompton/S&S ( per Phase)
Sudhir and Schneider (Per phase)
Outdoor type PCVCB upper and lower part(Per phase)
Installation, testing and commissioning of 33 KV vacuum Interrupters Housing of above mentioned make including dismantling of damaged assembly including transportation of Red material upto Divisional store.
Supply, installation, testing and commissioning of 33/11 KV Power Tranformer equipments/Items (The job includes identification of damaged part so that exact part can be arranged from OEM) including dismantelling of parts.
Bucholz Relay
33KV Bushing
33KV Bush Rods
11 KV Bushing
11 KV Bush Rods
Tap Changer complete
WTI set with probe
OTI set with probe
Repairing of 33/11 KV Power Tranformer equipments/Items
Bucholz Relay
Tap Changer complete
WTI set with probe
OTI set with probe
Installation, Testing & commissioning of Power Transformer including fixing of radiators (if required), topping up (oil to be provided by department) etc
1 MVA OR of lower capacity
Dehydration/Filteration of Power Transformer Oil including providing of Filtration machine capable of centrifuge, heating, degassing, filtration value upto level load.
Installation, Testing and Commissioning of following MCCB's with copper spreaders ISI Mark.
100A 3-pole 36 KA
125A 4-pole 36 KA
250A 4-pole 36 KA
400A 4-pole 36 KA
630A 4-pole 36 KA
Supply, Installation, Testing and Commissioning of MCCB Enclosure Box
Providing and fixing of Gaskets of 12mm,10mm,6mm including drainage of oil (if reqd.), Dismantling of damaged gaskets/oil sealings and vice-versa of same after completing the job by way of dismantelling of transformer parts and Re-fixing of same.
Radiator valve Gasket (12mm)
Top cover peripheral gasket (12mm)
Oil Sealing of HV-LV Bushings
Tap Changer Body gasket (12mm)
Sight glass (6mm)
Inspection Plate (6mm)
33KV outdoor CT Gaskets (10mm)
Supply , Laying testing & commisioning of 33 KV 3 core XLPE Cable along with suitable heat shrinkable/push on cable termination kits (Make-3M/ Polycab/ Anchor/ Havells/ Gloster)
Supply , fixing, testing & commisioning of 3 Core 33 KV Jointing Cable kits for XLPE cable of sizes
Supply & Fixing of Heat shrinkable/ Push on cable kits with allied accessories Suitable for 33 KV 3-core XLPE cable including dismantling of existing damaged cable kits of following sizes
Supply , Laying testing & commisioning of 11 KV 3 core XLPE Cable along with suitable heat shrinkable/push on cable termination kits (Make-3M/ Polycab/ Anchor/ Havells/ Gloster)
Supply , fixing, testing & commisioning of 3 Core 11 KV Jointing Cable kits for XLPE cable (Make-3M/ Polycab/ Anchor/ Havells/ Gloster)
Fixing of 11 KV Heat shrinkable cable kits with allied accessories Suitable for 3-core XLPE cable including dismantling of existing damaged cable kits of following sizes
Providing and fixing of 1'x1'Junction box of 14 SWG IP 65 protected as per Bis with inbuilt 36 No's Brass connectors mounted on din rail channels complete.
Oil topping of equipments including Power Transformers, CT's, PT's and auxillary X-mers.
Rectification of minor leaks of Power Transformers, CT's, PT's and auxillary X-mers.
Supply & fixing of following battery charger accessories including dismantling & Modification of damaged accessories/ Items. (The job includes identification of damaged part so that exact part can be arranged from OEM)
Power Diodes P-type/ N-type ( 40 to 100 A)
Charger Coil 240/36V AC
AVR Cord
DC Voltmeter ( 0-60V) Digital
DC Ampere meter (0-50A) Digital
Variac 15/25 Amp, 0-240 A
Repairing of following battery charger accessories
DC Voltmeter ( 0-60V) Digital
DC Ampere meter (0-50A) Digital
Variac 15/25 Amp, 0-240 A
Supply, laying, routing, installation, testing & Commissioning of damaged panel wiring using multistandard wire of sizes 1.5/2.5 sqmm including ferruling, thimbling etc
Installation, testing commissioning of 33/0.433 KV Transformer equipments (if required) fixing of following items
0.433 KV LV Bushing
0.433 KV Bush rods
Supply, Routing, laying, testing and commissioning of 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS , connecting ribs, bunching wire, ferruling, thimbling etc
Supply, Laying, installation, testing and commissioning of Chemical Earthing including digging of pits including connecting with present earthing complete job which includes 3m Copper in GI electrode 43mm diameter and termination using 40*6mm GI strip with mainhole cover
Supply, Fixing, Fabrication, testing, commissioning of mechanical parts for various 11kV VCB's (including dismantling of assembly and damaged parts and refixing as per requirement to existing breakers (Pascal, Electric field, Schneider, ER, Alind, CG etc)
Spring charging mechanism with allied accessories complete set of assembly for different 11kv vcb's
HSS Gears of sorts for different sizes and applications used in VCB's of different make
Close release steel pins of sorts
Trip release steel pins of sorts
locking cam set of sorts
Rack and pinion set
Torsion springs of sorts
operating rod of sorts
operating corn of sorts
Making/Breaking springs of sorts
loading spring of sorts with dampers
epoxy holding insulators
Main Links
copper flexible ribbon/braid connections
Copper finger contact 8mm french curved single type
copper 12 finger contact
Bunched strip copper contact for alind
Spring charging Ratchet gear assesmbly with lever and gear complete
Trippin coil housing with allied accessories of sorts
Closing coil housing with allied accessories of sorts
Expoxy/porcelain spout with copper bus bars of sorts of all kinds of breaker excluding Alind make
Expoxy/porcelain spout with copper bus bars with inbuild CT Alind make.
Cotter pins of sorts HSS
Cotter spring pins HSS
Dowell Steel pins
Shaft locks/Pin Locks
Trip strike lever of sorts
Close strike lever of sorts
Minor Re-alignment/Readjustment of mechanical parts
Repairing of mechanical parts for various 11kv VCB's (including dismantling of assembly and damaged parts and refixing as per requirement to existing breakers (Pascal, Electric field, Schneider, ER, Alind, CG etc)
Spring charging mechanism with allied accessories complete set of assembly for different 11kv vcb's
Supply, Fixing, Fabrication, testing, commissioning and repairing of Electrical parts/ Circuits for various 11kv/33KV VCB's (including dismantling of damaged Electrical parts/Circuits and refixing by way of re-wiring as per requirement to existing breakers/Pannels (Pascal, Electric field, Schneider, ER, Alind, CG etc)
12 Point Male female control circuit contact
24 Point Male female control circuit contact
36 Point Male female control circuit contact
Auxillary Switch 12 No+12 NC 16-25A with lever
Anti pumping device with allied accessories
Limit switch with 2 No+2Nc 16-25A with accessories
Repairing of Trip circuit super vision circuit
Reparing of Closing circuit
36 VDC Master trip relay with 4 NO+4NC 25A High speed
36VDC Auxilliary relay with 4NO+4NC High speed
Driver relay DPDT 12 vdc with 2 NO+NC High speed
11KV/110v based 4" Voltmeter digital programeable type
CT Ratio Based 4" Amp. Meter digital programeable type
ASS Switchs 25A
VSS Switchs 25A
LED indicators of different colors 36 VDC
Push buttons 25A with 2NO+2NC
MCB's of sorts 6A-25A 10KA c curve type
Repairing of Pannel wiring complete job as per REC Standards.
Installation Testing and commissioning of Tri-vector meters
Supply, Testing and commissioning of Control relays with 3OC+1EF 2 Element based digital including necessary modification and minor wiring works complete job of following make.
MIT- 114/104 (ER) make.
Schneider
Crompton 14C
Ashida ADR241B/242B
Supply, Installation, testing and commissioning of 11KV epoxy compound spouts with required Copper busbar as per requirement and as per the existing pannel requirement of below mentioned make including dismantling of damaged spouts including transportation of Red material upto Divisional store.
Vijai (Per Phase)
Alind (Sput with required CT/phase).
Easun Reyrolle ( per Phase)
ABB ( per Phase)
ABB (Per Set)
S&S ( per Phase)
Electric Field ( Per Phase)
Electric Field ( Per Set)
Crompton ( Per Phase)
Crompton ( Per Set)
Sudhir/Schneider (Per phase)
Sudhir/Schneider (Per Set)
Hartek (Per Phase)
Hartek (Per Set)
Supply installation testing and commisioning of following tripping and closing coils for different types of VCB's including dismantling of existing damaged coils. The Tripping and closing coils must have burden between 250 to 350 watts at 30VDC & must follow the specifications of design of VCB's .
Tripping/Closing coil of 11KV Alind make VCB
Tripping/Closing coil of 11 KV ER/Vijai Make VCB
Tripping/Closing coil of 11KV Electric Field Make VCB
Tripping/Closing coil of 11KV ABB Make VCB
Tripping/Closing coil of 11KV Crompton Make VCB
Tripping/Closing coil of 11KV Stelmac Make VCB
Tripping/Closing coil of 11KV Sudhir/Schneider Make VCB
Tripping/Closing coil of 11KV Pascal Make VCB
Tripping/Closing coil of 33KV ABB Make VCB
Tripping/Closing coil of 33KV Crompton Make VCB
Tripping/Closing coil of 33KV Stelmac Make VCB
Tripping/Closing coil of 33KV Megawin Make VCB
Installation, Testing, and commissioning of tripping and closing coils for different types of VCB's including dismantling of existing damaged coils. The Tripping and closing coils must have burden between 250 to 350 watts at 30VDC & must follow the specifications of design of VCB's .
Supply installation testing and commisioning of
33 KV Lightining Arrestor (33kV , 10KA)
11 KV Gapeless surge arrestor, 9KV , 10KA LA
Installation testing and commisioning of
Providing & Fixing of
3/5 15 AMP socketwith switch
3/5 6 AMP socket
6 Amp switches
Lamp Holders
12 V DC emergency Lamp
Fan dimmer
9/15 W LED Lamps
1400 mm Ceiling Fan
200 mm Exhaust Fan
6-32 Amp MCB
40 Amp MCB
25 Amp Industrial type Plug Socket with MCB in MS box
Providing and laying of Insulating HT Rubber Mats ( 1000x 2500) 12 to 25 mm thick
Providing and laying of 2 core 16 sqmm 1.1 KV PVC cable for AC / DC distribution including Termination
Supply, installation, testing and commissioning of Following items for use in both 11KV VCB Panel & 33KV C&R Panels
BMR mechanism of different makes
Shower contact
Trip circuit supervision Relay
Indication LED's of various colors
Buzzer
Supply, installation, testing and commissioning of OLTC Panel for Power Transformers
Supply, installation, testing and commissioning of XLPE LT Cable 3.5 Core, armoured, Fire resistant of sizes
Loading Transportation and unloading at site of work from Divisional stores
33KV VCB/ 33KV C&R Panel/ 11 KV VCB Panel
33KV CT/PT Set
Transportation of 11KV VCB to the workshop of the contractor and back to the Receiving station in case the repairing of 11KV VCB is not possible at site.
BHAT CONSTRUCTIONS (BID ID -2542612)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .