| 1 | L1₹21.3 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Low | |
| 2 | L2₹30.3 L+₹9.0 L (42.1%)Rejected-AOC ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | VISAKHAPATANAM | ANDHRA PRADESH | 530001 | L2 | Rejected-AOC High | |
| 3 | L3₹34.0 L+₹12.7 L (59.4%)Rejected-AOC | L3 | Rejected-AOC High | |
| 4 | L4₹34.7 L+₹13.4 L (62.7%)Rejected-AOC RZ BH 4 STREET NO 5 MAIN SAGARPUR NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | L4 | Rejected-AOC High |
Tender Value
₹24.2 L
EMD Value
₹48,300
Closing Date
23 Nov 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Sh Sachin Jaiswal, IDSE, CWE Chandijmandir
HQ CWE Chandimandir
CA NO. CWE/CHD-44/2022-23 PROVN OF 11 KV VCBS AND CONNECTED ITEMS AT K AREA UNDER GE CHANDIGARH
2022_MES_553956_2
CWE/CHD-44/2022-23
Open Tender
Miscellaneous Works
Item Rate
180 days
HQ CWE Chandimandir
Class E Category b(ii)
8 documents required · 8 mandatory
₹500
Yes
GE Chandigarh
₹48,300
Yes
20 Feb 2023
1 Nov 2022
28 Nov 2022
1 Nov 2022
23 Nov 2022
9 Nov 2022
Amount
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty ) 11000 volts grade with stranded aluminium conductor of size 120 Sqmm 3 core ( Main Cable) complete all as specified and directed.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty ) 11000 volts grade with stranded aluminium conductor of size 95 Sqmm 3 core complete all as specified and directed.
M & L for cable route indicator made of cast iron plate circular type 10 cm dia duly marked Blue colour marked LT cables arrows mark up side duly welded/nut, bolt with angle iron 45/45 equal size and 45 cm long duly grouted on ground with PCC (1:3:6) as in foundation & earth work excavation etc complete all as specified and directed at site.
Excavation in trenches in soft/loose soil not exceeding 1.50 meter wide and not exceeding 1.5 meter in depth and not exceeding 10sqmm on plan and getting out complete all as specified.
Excavation in trenchs .exc. 1.5 mtr in depth but not exceeding 3 mtr in depth and getting out in any type of soil complete all as specified.
Returning,filling in including spreding, levelling, watering and well ramming in layers not exceeding 25 cm thick each excavated soil in trenches after the pipes have been laid and tested completed as in soft/loose soil, complete all as specified and directed.
Removing of surplus soil/excavated material to a distance not exceeding 50meter and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
M & L for Plain cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate as in foundations of PCC poles/struts, stay asembley, filling and mas concrete etc. including necessary fromwork complete all as specified and direted.
M & L for Plain cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate for coping around Poles,including necessary form work finishing even and smooth without using extra cement,all as specified and directed.
M & L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of Synthetic enamel paint complete all as specified and directed.
M & L for Sand filling under floors or in foundations including watering and consolidation complete all as specified and directed.
Supply & install steel tublar swaged pole welded with MS base plate size 30cm x 30cm x 6mm thick final taper plug bolts nuts & washers as per IS: 2713 (part-I) 1980 made out of MS tubing including painting of two coats of aluminium paint of approved quality over one coat of red oxide primer length 11.00 mtr long, type 410 SP -55 complete all as specified and directed. NOTE : (i) Earth work and PCC work will be measured and paid separately under respective item of the schedule. (ii) Material and labour for ACSR conductor, cross arms, insulators will be measured and paid separately under respective item of the schedule.
Supply and laying factory made unreinforced precast concrete cable cover, class HV, type 1 flat size 300mm x 180mm x 40mm for protection of HT cable laid flat length wise prependicular to the axis of cable complete all as specified and directed.
M & L for Galvanised iron strip 32x6 mm burried in ground with saddles and fixing with screw etc.for roof conductors and down conductor above ground for earthing complete all as specified and directed.
Supply, jointing, testing and commissioning cable end termination jointing kit 11 KV (earthed) grade cable for outdoor termination cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured alluminium conductor cbale of size 120 Sqmmm complete all as specified and directed.
Supply, jointing, testing and commissioning cable end termination jointing kit 11 KV (earthed) grade cable for outdoor termination cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured alluminium conductor cbale of size 95 Sqmmm complete all as specified and directed.
Supply & Fixing Steel water tubing, galvanised, light grade, ISI marked, 80 mm bore with and including all fittings fixed to walls and ceilings or laid in floors complete all as specified and directed.
M & L for Air break switch gang operated triple pole, machanically operated, mounted on insulator and steel framewith operating mechanisim worked from ground level, current rating upto 200 amps for 11 KV complete all as specified and directed.
M & L for Lightening arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 KA on 11000 volts complete all as specified and directed.
M & L for Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts,bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed.
M & L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20 cm size complete all as specified and directed.
M & L for Aluminium strip 25x3.15mm with saddles and fixing screw etc.for roof conductors and down conductor above ground or on HT poles for earthing completecomplete all as specified and directed.
M & L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm surrounded by mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less 2.25mtr below ground level with top edge of earth plate at a depth of not less than 1.50mtrs below ground level connected with and including 32x6mm galvanized iron strip as earthing lead by means of bolts, nuts, check nuts and washers made out of galvanized iron, 20mm dia medium grade GI pipes for watering with funnel, wire mesh and 40mm GI light grade protection pipe for GI strip and including necessary excavation, earth work, PCC 1:3:6 type C-2 concrete pit and RCC pit cover charcoal and common salt filling in alternate layers complete all as specified and directed by Engineer-in-Charge on electrical plate no-3 of SSR Par-I of 2009 including testing complete all as specified and directed. Note:(i)After completion if the desired earth resistance is not obtained the earthing will be re done at on extra cost. (ii) The result sheet of earthing may submit to GE duly signed by all concerned.
Supply, installation, testing and commissioning of factory made HT Panel 2mm thick CRCA sheet having following components/Specifications:- Indoor vaccum circuit breaker panel suitable for 11 KV, 630 Amps, 25 KA for 3 Sec for outgoing conforming to IEC 62271-200, front accessed having following specifications and comprising of following items:- (a) 630 Amps continuous rated electrolytic copper bus bars, droppers and bus bars should be insulated with full system voltage sleeves. (b) Trolly mounted vaccum circuit breaker as per IEC-62271-100, Vaccum circuit breaker should have three Nos resin encapsulated vaccum bottles. (c) Motorized spring charging mechanism with integral spring charging handle for manual spring charge. (d) Cast resin current transformer 11 KV, 300-150/5-5A, core 1: Class 1.0, 15VA, Core 2, SP 10, 15 VA. (e) Acessories like local remote switch, breaker control switch (T-N-C), space heater with thermostat, DC and AC control citrcuit through MCB, indicating lamps for RYB, spring charge, DC supply healthy, breaker ON/OFF breaker in SERVICE/TEST as manufacturer. (f) Comprehensive numerical protection relay as per IEC 61850 compatiable for directional and non directional O/C, E/F, U/V, O/V protection. (g) Digital ammeter and digital voltmeter compctiable to the panel. (h) Multifunction meter with RS 485 port model No. EM6400 of CONSERV make or equivalent in L&T make.
(j) The VCB shall be designed to function properly at high altitude of aprox. 321mtr above sea level at Chandigarh. Panel should have following additional facilities:- (i) Trip Ckt supervision (ii) Disturbance recorder (iii) Measurement and control feature (iv) Event log with date and time Panel should also have additional facilities like:- (i) Intermittant rated closing and tripping coil. (ii) Fully internal arc type tested (25 KA for 1 sec) (iii) Vaccum bottles should be epoxy encapsulated (iv) Racking in/out, manual closing/tripping of CB with compartment door closed. (v) Breaker shall be provided with following contacts:- (aa) Auxiliary switch with 7 No + 7 NC mounted on the draw out portion of the switchgear. (ab) Position switches with 3 No + 1 NC contacts for each position in SERVICE and TEST. (vi) Each cubical of VCB shall have adequate space heating arrangement to counter extreme cold condition of Chandigarh (vii) Type test reports for internal arc test to be submitted alongwith submission of drawings.
NOTES :- (a) Make of HT panel : ABB/Siemens/L&T/Schneider (b) Drawing for panel shall be approved from GE before placement of order by contractor (c) CT ratio as given is tentative and is subject to final approval of GE (d) Precommissioning test of panel shall be carried out by EI from HQ CECZ within overall cost quoted by contractor (e) Any modification required to match the system with existing system is deemed to be included in overall cost quoted by contractor. (f) Pre dispatch inspection of panels can be carried out at factory premise by rep of Accepting Officer within overall cost quoted by contractor. Decision of Accepting Officer shall be final in this regards. (g) Power pack duly fitted by firm supplying VCBs should be supplied within overall cost quoted. (h) Necessary foundation bolts to be grouted in PCC foundation as recommended by the manufacturer shall deemend to be included in overall quoted rates. (j) Panels should be suitable for minimum impulse withstand voltage of 75 KV. Nothing extra shall be payable on this account.
GS Engineers
M/S BALWINDER SINGH
M/s ELECTROSHINE ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .