| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.6 LAccepted-AOC | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹13.2 L+₹60,310 (4.79%)Rejected-AOC WZ 409 0 B 1ST FLOOR PLOT NO 12 JANAK PARK HARI NAGAR NEW DELHI 110064 | NEW DELHI | WEST DELHI | DELHI | 110064 | L2 | Rejected-AOC Not L1 Bidder | |
| 3 | Rejected-Technical | - | Rejected-Technical Not Found in order | |
| 4 | Rejected-Technical 205 PARSHAV VIHAR PLOT NO 50 IP EXTN PARPARGANJ DELHI 110092 | EAST | DELHI | 110092 | - | Rejected-Technical Not Found in order |
Tender Value
Refer Docs
EMD Value
₹29,080
Closing Date
21 Jun 2021, 6:00 pmClosed
GE U WATER SUPPLY DELHI CANTT 10
GE U WATER SUPPLY DELHI CANTT 10
PROVN OF ELECTRONIC SENSOR BASED SYSTEM AND AUTOMATED WATER SUPPLY DISTR INSTALLATION IN THE AREA OF VIKRAM VIHAR UNDER GE U WATER SUPPLY DELHI CANTT 10
2021_MES_446747_1
GE/WS/D-34 of 2021-22
Open Tender
Civil Works
Item Rate
120 days
GE U WATER SUPPLY DELHI CANTT 10
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE U WATER SUPPLY DELHI CANTT 10
₹29,080
Yes
26 Jun 2021
29 May 2021
23 Jun 2021
29 May 2021
21 Jun 2021
9 Jun 2021
Amount
Supply and Fixing of SCADA Controlling Module for Main Pump House Compatible with SCADA RTU With 01 No. Digital Input Card, 01 No. Digital Output Card, 02 Nos. Analog Inputs, 2 Nos. Analog Output Cards, 1 Relay Card and 24 VDC SMPS Power Supply (All Compatible with Remote Terminal Unit) complete all as specified and as directed
Supply & Fixing of Enclosure for SCADA Controller for the system all as specified and as directed. Panel of size 1000mm x 600mm x 300mm (minimum) fabricated from 1.6mm thick CRCA sheet and must be powder coated complete all as specified and as directed
Supply and Fixing of ACTUATOR BUTTERFLY VALVE Suitable for inching duty and on-off duty, Available actuators make Supply 415V AC/ 3Phase/ 50 Hz, Metal to metal seating design, Triple offset and double offset design Soft seating design also available, Zero leakage, Lined valve also available with FEP/PFA/PTFE lining Fabricated butterfly available in Duplex steel, Monel, Inconel & Titanium grade, Hand-wheel – Yes (optional), CPT, Gear box- Yes (optional) Design: As per AWWA, API, BS, IS 13095 std, Testing: As per AWWA, API, BS, IS 13095 std, Ends: As per AWWA, API, BS, IS std Size: DN 50 – DN 3000, Pressure Class: 125 Lb, 150 Lb – 600 Lb, PN6 – PN25, Temperature- 10 Deg C – 400 Deg C, Ends: Double flange, Wafer, Operation- Electric actuator, Application- Hydro power plant/Distillery/Thermal power plant/Chemical plant. Body: Stainless steel (CF8,CF8M, CF3, CF3M, F316L,F304L,F316,F304), Monel, Inconel, DI, CI, WCB Disc: Stainless steel (CF8,CF8M, CF3, CF3M, F316L,F304L,F316,F304), Monel, Inconel, DI, CI, WCB Spindle: , Duplex steel, SS 316, SS304, SS 410 Painting: Epoxy primer + epoxy painting, Power coating, Chromium carbide Line Size: 150 NB complete all as specified and as directed
Supply and Fixing of MOTOR STARTER PANELS - For 15 HP Motors complete all as specified and as directed
Supply and Fixing of electromagnetic type flow meter for 150 mm pipe, with IP 66 protection, 1.4 kV Isolation, accuracy of 0.5 MV, linearity of 0,5% of MV, mounting in horizontal , 10kg/cm2 max pressure local indication through LCD display and RX 485 MODBUS RTU communication protocol, capable of working in ambient temperature of 0 deg C till 75 Deg c and Humidity upto 95% with Response time of less than 1 Sec, working on 90-250 VAC, 50 Hz including dismantling of existing conventional type flow meter of any size, welding work, cutting of existing MS/DI/CI/GI pipe line and inserting new MS pipe 150 mm dia with necessary MS beds and straight pipe upto 6 mtr and connecting with existing pipe line with necessary flanges, nut, bolts, gasket and DI/ CI specials ll complete all as per specified and as directed
MS Powder Coated Enclosure for Remote Display Units of Electromagnetic Flow Meters
ULTRASONIC LEVEL SENSORS S&F of Water Level Sensor for underground tank suitable for up to 6 meter water level depth of U/G sump, with dead band of less than 0.6meter, IP66 protection, accuracy of 0.25% of F.S. and RS485 Modbus RTU communication protocol, Capable for working in ambient temperature of 0 degree Centigrade to 75 degree Centigrade, non-condensing at 25 degree Centigrade and humidity up to 95% with response time of less than 1 sec with 230VAC to 24VDC, 50Hz power supply, LCD display type, vertical type mounting on top of OHTs with all connections and fixing including clamp, nut-bolt etc complete all as specified and as directed
Supply and Fixing of Three Phase CT for Multi Function Meters complete all as specified and as directed
Supply and Fixing of Single Pole 6 A MCB for Multi Function meters complete all as specified and as directed
Supply and Fixing of SITC of Enclosure for Water level Sensor complete all as specified and directed
M&L for SCADA Software for receiving station Software with 2 years subscription, maintenance and support as per specs, Must have user customizable dashboards and SLD (without any coding/ scripting) Reporting must be user-configurable and changeable. Utility like billing reports must be supported. Multi-site data viewing within same interface without any physical cable connection of sites to SCADA room SCADA must be accessible over internet and must have adequate security with dual factor authentication with username/ password along with OTP on email. All device communication with Cloud based SCADA will be secured using TLS/SSL encryption. SCADA will not support non-secure connections. System shall work without any need of static IP. No static IP will be provided for any location. SCADA application shall be hosted in MEITY ( Ministry of Electronics and Information Technology, Govt of india ) empanelled data Centers ( Empanelled under Meghraj Initiative) complete all as specified and as directed
Supply and Fixing of Two 22 AWG pairs stranded (7x32) tinned copper conductors, polyethylene insulation, twisted pairs, tinned copper braid shield (90% coverage), 24 AWG stranded tinned copper drain wire, PVC jacket RS 485 Armoured Cable as per IEC-60332-1-2, Operating Temperature Range: -30° to 80° C for SCADA System complete all as specified and as directed
Supply and Fixing of 2.5 mm 2 Core PVC Insulated multi strand copper cable complete all as specified and as directed
Supply and Fixing of ACTUATOR BUTTERFLY VALVE 150 MM Line complete all as specified and as directed
Flint India
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .