D.G.(S and D)
Office of the D.G (S AND D) SEWARAGE AND DRAINAGE department Kolkata Municipal Corporation 5, S.N. Banerjee Road Kolkata-700 013 West Bengal
Repairing, overhauling with replacement of defective spares for 2 nos H.T VCB (11KV), 1no dry type transformer (1000 KVA ) at Ambedkar Drainage pumping Station.
2025_KMC_977205_1
KMC/S_D/ABK/VCB/25-26
Open Tender
Electrical Work/ Equipment
7 days
DLPS
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹10,000
20 Jan 2026
26 Dec 2025
17 Jan 2026
26 Dec 2025
15 Jan 2026
26 Dec 2025
TOTAL
Item Rate BoQ
BoQ_Ver3.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Racking out & drawing out of VCB from HT panel after tripping the VCB manually & keeping the VCB in a workable position inside the room.
Taking out the P.T. (11 KV/110V) HT VCB Panel and thorough cleaning, washing the interior portion with carbon tetachloride after taking out the from P.T. housing and re-fifling the same after the desired IR. value and re-fixing the P.T. complete and testing and commisining as per direction of E.I.C
Repairing, Srevicing & Overhauling of VCB (mechanism portion).
Removing of pitting from H.T. contacts by filing & dry cotton cloth & cleaning the main V & finger contact with CTC/CRC & hot oil jet & after discharging the store charges using discharg earth rod.
Supply and delivery of resin cast 11 KV 100/50/5/5A dual core dual ratio 15 VA C.T. ISI brand
Supply & fitting fixing with proper connection & testing by suitable instruments of Reputed make triple pole IDMTL type combined Over-current & earth fault Relay type CDG-61 with instantaneous high set setting. Two nos over-current element at the outer poles have O/C setting 50-200% & instantaneous high set setting 250-2000% continuously adjustable. The earth fault element at the centre will have O/C setting range 10-40% or 20-80% & instantaneous high set setting range of 100-800% continuously adjustable. The Relay will be flush/projection mounted on the front side of the panel thereby making suitable arrangement including all necessary materials & will be hosed in horizontal draw out case.
Supply 3- phase 110V power pack unit (ISI brand), 500VA
Supply and fittings of 11KV grade, Busbar insulator(incoming)
Supply and fittings of 11KV grade, Busbar insulator(outgoing)
Supply and fittings of 30V DC grade, shunt trip coil
Supply and fittings of 30V DC grade, closing coil
Supply Delivery & fixing of Control fuse 6 Amps( make G.E / Kaycee)
Supply & Delivery fitting & fixing of indicating lamp (LED type) (make Vishno / L&T).
Supply & fixing digital type Square Voltmeter (AE/ reputed make) as per existing specification and P.T. ratio
supply & fixing auto manual switch for auto spring charge motor
Internal control circuit wiring including necessary connection with sockting & end finishing by 1.1 KV grade 2.5 sq mm PVC insulated single core Cu Flexible wire (make Finolex/ KDK)
Dismantling, Servicing, cleaning, testing, re-fifling and calibration of the Each feeder consist of Relay type- 2nos over current relay and one no earth fault relay 11 KV panel.
Discharging the primary and secondary side of transformer properly by earth rod. Open out all the cables from HT & LT side making proper tag marking of all cables.
Dismantling of top cover, side cover, gourd bar, tap-changing switch handel etc of the transformer.
Thorough cleaning & removing of dust from Core & coil assembly, tap changing switch etc by CTC with the help of soft brush, clean cloth with hot air jet pressure arter dismantling of HV & LV connection from bushing terminal end of inside transformer as per direction of EIC.
Re- insulation all the HT coil lead properly with HT insulating tape, vernish etc, and testing of primary & secondary coil resiatance, IR value with respect to earth & H.V test etc, and after completion of test terminate all the cable leads as per existing way and refixing the top cover, side cover gourd bar, tap changing switch handeletc of the transformer after cleaning properly and as per direction of EIC
Supply of new HT & LT bushing
Spray painting of outside surface of the transformer with one coat red oxide primer & two coat of synthetic enameled make after proper cleaning of the said transformer.
Repairing and calibration of temperature scaner of transformer
Testing Ang Commissioning Of Transformer As Per Direction Of EIC
Please Enable Macros to View BoQ information
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.92 MB
BOQ_2380852.xls
BOQ • 0.38 MB
FORM.pdf
Tender Documents • 0.63 MB
Download all tender documents and submit your bid