GARRISION ENGINEER (AF) THOISE
GARRISON ENGINEER (AF) THOISE 19 FBSU, c/o 56 APO, PIN 937219
PROVN OF LT CABLES,PANELS AT CERTAIN LOCATION AT AF STN THOISE
2023_MES_624799_1
GEAF/T-43/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
THOISE
As per tender document
7 documents required · 7 mandatory
₹500
GARRISON ENGINEER (AF) THOISE
₹38,760
Yes
11 Jan 2024
25 Oct 2023
25 Nov 2023
25 Oct 2023
21 Nov 2023
2 Nov 2023
Amount
Excavating in trenches, n exc1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits,manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in hard and dense Soil complete all as specified and directed by Engineer-In-Charge.
Returning filling in including spreading levelling, watering and well ramming in layer each not exc. 25 cm thick in a soft/loose soil complete all as specified and directed by Enginer-in-Charge.
Removing surplus soil to a distance not exc. 50 mtr and depositing where directed at a level n.exc. 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
M&L for PCC cable cover Class LV, Type I, flat, size 250 mm x 150mm x 40mm laid Flat in trenches over the cable with length 250mm perpendicular to the direction of cable, adjacent/ abutting each other. complete all as specified and directed by Engineer-In-Charge. Note:-Excavation and earth work to be measured and paid for separately
M &L for Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cm thick, complete all as specified and directed by Engineer-In-Charge. Note: Punned thickness shall be measured.
M &L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 95.0 Sqmm, 3.5-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and directed by Engineer-In-Charge.
M &L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 70.0 Sqmm, 3.5-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and directed by Engineer-In-Charge.
M &L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 16.0 Sqmm, 4-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and directed by Engineer-In-Charge.
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium M conductor, 1100 Volts grade, cross-sectional area 16.0 Sqmm,2-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and directed by Engineer-In-Charge.
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 10.0 Sqmm, 2-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends,d.complete all as specified and directed by Engineer-In-Charge.
M&L Earthing complete with steel plate elecrode of size 60 cm x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 2.5 mtr below the ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level. Earth plate surrounded by 15mm thick packed alternative layers of charcoal dust and comman salt and connected to galvanised iron strip 32x6mm by means of bolts , nuts, check nuts and washers of galvanised iron or steel with thimbles.The other end of galvanised iron strip is connected to main switch board and protected by light grade GI pipe of 40 mm bore. Provision of 20 mm bore light grade GI pipe for watering including GI funnel and wire mesh. Pipe shall be provided vertically upto top level of earth pit and then taken horrizontally to the earth pit. Cement concrete chamber of PCC ( 1:3:6 ) type C-2using 40 mm graded stone aggregate.The chamber shall be constructed one metre away from edge of earth pit. 50 mm thick pre cast cover of cement conrete (1:2:4) type B-1 using 20 mm graded stone aggregate and MS angle iron 50 x 50 x 6 mm frame including two coats of painting over a red oxide to expoxsed steel surfaces. excavation in soft / loose soil or hard rock, returning filling and removal of surplus soil to a distance of 50 mm and complete all as directed and shown in Electrical Plate No- 3 of SSR Part-1 (2009). complete all as specified and directed by Engineer-In-Charge.
Supply, installation, testing and commissioning of electric LT Feeder Pillar Box, outdoor, cubical type, floor mounted, factory made, CPRI approved, size 1000x1200x450mm, Al Bus Bar 800 Amps fabricated out of 3.4mm thick mild steel sheet mounted on frame of mild steel angle iron 40x40x6mm also comprising of following Inccoming:- (a) MCCB four pole ,100Amp 415 volts , adjustable type with breaking capacity 25 KA (b) Multifunction meter V,A,F -01 No Make L&T , Equivelent in Seimns and Schinider -01 Nos Outgoing (i) MCCB 4 pole 415 Volts of capacity 63 amps thermal magnetic release adjustable type of breaking capacity 10 KA-01 No (incoming) With addition to Amp meter-01 (ii) MCBTPN 415 Volts of capacity 40 amps thermal magnetic release adjustable type of breaking capacity 16 KA-02 Nos (outgoing) With addition to Amp meter-01 ii) MCB SPN 415 Volts of capacity 32 amps of breaking capacity 10 KA-02 Nos (outgoing) With addition to Amp meter-02 complete all as specified and directed by Engineer-In-Charge.
M/S NINDI BUILDERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .