Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.6 LAccepted-AOC N A | NA | NA | 121004 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹35.9 L+₹20,221 (0.57%)Rejected-Finance JAIN SADAN MAHAL ROAD SHIVPURI DISTT SHIVPURI MP | SHIVPURI | SHIVPURI | MADHYA PRADESH | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹37.8 L+₹2.0 L (5.63%)Rejected-Finance FLAT NO A 15 ARCHANA GREEN SOCIETY NIBM ROAD KONDHWA PUNE 411048 | PUNE | MAHARASHTRA | 411048 | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹40.5 L+₹4.8 L (13.4%)Rejected-Finance | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹40.6 L+₹4.8 L (13.5%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
9 Nov 2023, 6:00 pmClosed
GE NORTH PUNE
Garrison Engineer North General Cariappa Marg Camp Pune 411001
GE (N) P/TOKEN - 62 OF 2023-2024 ADDN /ALTN TO BUILDING NO P-14 (COMD LIB - READING AND CHILDREN SECTION) AND SPECIAL REPAIR TO EXTERNAL ELECTRIFICATION NEAR RS ROAD IN THE AREA OF AGE E/M (NORTH) UNDER GE (NORTH) PUNE
2023_MES_617259_2
GE (N) P/TOKEN- 62 OF 2023-2024
Open Tender
Civil Works
Item Rate
240 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE NORTH PUNE
₹98,000
Yes
30 Dec 2023
11 Oct 2023
16 Nov 2023
11 Oct 2023
9 Nov 2023
25 Oct 2023
12 Oct 2023 - 19 Oct 2023
Amount
Taking out/removal of existing PVC/Linoleum floor and removiong the debris out side the premises where directed.
Dismantling synthetic wood or wooden tile flooring of any description at any position including bedding layer and PVC sheet fixed on top od wooden floor and removiong the dismantled debris out side the premises where directed.
M & L for Double charged vitrified Ceramic tiles, light shade 8 to 10 mm thick (square/rectangular), polished, area of each tiles exceeding 0.42 sqm but not exceeding 1.00 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tile including 20 mm thick bedding layer of cement mortar 1:4 all as specified and directed.
M & L for double charged vitrified Ceramic tiles light shade 8 to 10 mm thick (rectangular), polished, in skirting etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tile including 10 mm thick backing coat of cement mortar 1:4 all as specified and directed.
M & L for double charged vitrified ceramic tiles dark shade 8 to 10 mm thick (square/rectangular), polished, area of each tiles exceeding 0.42 sqm but not exceeding 1.00 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tile including 20 mm thick bedding layer of cement mortar 1:4 all as specified and directed.
Material & labour for Mirror polishing on marble/ granite/ Kota stone/ stone work by machine grinding wherever required to give high gloss finish complete.
Supply and fix in repair for aluminium powder coated partition using ‘Jindal’ aluminium SP/ DP section or equivalent make as specified with 5mm thick tinted glass, PVC rubber beading,12mm thick prelaminated particle board fixed with glazing clips etc complete all as specified and as directed. Sections : SP (Single partition) - 20033, DP (Double partition) - 20034,Glazing clips - 4407
M & L for powder coated aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified
M & L for powder coated aluminium door shutters, aluminium section weighing 0.55 kg/ m including necessary joining cleats, glazing clips, ruber neoprene packing, handles two Nos in each shutter, 03 in each shutter hinges, powder coated aluminum snap beading
M & L for preparing surface of old treated wooden surface and applying two or more coats of melamine polish including wood filler and pigment of approved tint etc complete all as specified and dierected.
M & L for 12 mm thick fully Vitrified tile with bullnosing as in treads including 15 mm thick screed bed in cement mortar 1:4 including dismsntling existing treads all as specified and directed.
M & L for 12 mm thick fully Vitrified tile as in risers over and including 10 mm thick backing coat in cement mortar 1:4 including dismantling existing risers all as specified and directed.
M & L for preparation of previously treated wall surface and applying a coat of acrylic oil emulsin distemper all as specified and directed.
M & L for preparation of previously treated ceiling surface and applying a coat of acrylic oil emulsin distemper all as specified and directed.
M & L for preparation of previously treated steel surface and applying a coat of synthetic enanel paint all as specified and directed.
S & F in repair PVC zebra pattern 100 % polyster roller venishing blinds with acrylic acid coating on both sides of the fabric to ensure the normal light penetration all as specified and directed.
Material and labour for point wiring using approved colour coding as per IS ,with multistranded copper conductor 1.5 Sqmm (nominal area), two single core, PVC insulated and unsheathed FRLS cable 1100 Volts grade ISI-694 marked drawn through in and including heavy duty PVC concealed conduit including all accessories, Metal flush box of suitable module, with earth dolly, covered with twin colour (specified by Engr-in- Charge)modular white cover plate & frame after chasing in brick/stone masonry walls etc for accomodating modular switches, sockets, regulators etc including PVC insulated multistranded copper conductor 1.5 Sqmm (nominal area) single core FRLS cable as earth continuity conductor along with wiring and connecting to earth dolly, providing Copper cable sockets plate/ bottle type of adequate size at termination end of cable point wiring in DBs, switch boards, fittings fixtures all as specified and as directed for the following
One light / wall / exhaust fan point controlled by one, one way switch 6 Amps complete all as specified and as directed
One ceiling fan point controlled by one, one way switch 6 Amps and regulator Note : PVC Casing caping / Pipe of size as required at site on surface of ceiling (only for fan point) in lieu of concealed is permitted and is deemed to be included in the unit rate quoated.
One bell point controlled by one, one way switch 6 Amps complete all as specified and as directed
One 5 pin socket outlet plug point, 6 Amps, controlled by one, switch on same board complete all as specified and as directed
One 5 pin socket outlet plug point, 6 Amps, controlled by one, switch on independent board complete all as specified and as directed
Description all as per 1 here-in before but using 2.5 Sqmm single core copper conductor FRLS cable of multistranded PVC insulated unsheathed 1100 Volts grade for one 6 pin socket outlet plug point,16 Amps independent including necessary running of 2.5 Sqmm PVC insulated multistranded copper conductor single core FRLS cable as earth continuity conductor along with wiring and connecting to earth dolly providing Copper cable sockets plate/ bottle type of adequate size at termination end of cable point wiring in DBs, switch boards, fittings fixtures all as specified and as directed
Supply and fixing Modular Switch - 6 Amps, Single pole one way, one module complete all as specified and as directed.
Supply and fixing Modular Bell push - 6 Amps, Single pole one way, one module complete all as specified and as directed.
Supply and fixing Modular Switch - 16 Amps, Single pole one way, one module complete all as specified and as directed.
S & F Modular socket outlet multipurpose 6 Amps, 5 pin, 2 module, complete all as specified and as directed.
S & F Modular socket outlet multipurpose 16 Amps, 6 pin-shuttered type, 2 module, complete all as specified and as directed.
Supply and fixing, Ding Dong bell suitable for operation on AC. 230 volts, single pole complete all as specified and as directed.
Supply and fixing modular fan step regulator, 120W - 2 module suitable for ( 48" & 56" fans) supply complete all as specified and as directed.
S & F Ceiling rose, 3 phase / PVC / polycarbonate, complete all as specified and as directed
Supply and fixing 20/22 Watt Inverter LED Battenaluminium body with Opal Diffuser, IP20, Battery back-up & Functioning as per Product TDS with intregrated electronic driver, connector block, holder, decorative end caps, LED tube light etc complete with all accessories prewired and mounting PVC rectangular block, including provision of flexible copper conductor cable of suitable size from ceiling rose to connector and taking down old unserviceable fitting from existing postion for carrying to store, making good disturbed surfaces complete all as specified and as directed. Make Halonix Cat No LED INVERTER BATTEN HLB-08-22-CW-INV or equivalent in Havells
Supply and fixing 40 Watt and 4 ft LED Linear Light Alumina asthetically designed rectangular pendant luminare including hanging arrangement by suspension wire not less than 1 meter from both end, duly power coated housing made of AL extrusion section and opal diffuser, IP 20with intregrated electronic driver etc complete with all accessories prewired including provision of flexible copper conductor cable of suitable size from ceiling rose to connector and taking down old unserviceable fitting from existing postion for carrying to store, making good disturbed surfaces complete all as specified and as directed. Make Halonix Cat No HLLL-P04-40-CW-AL or equivalent in Havells and Wipro.
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp connecting up with three core flexible copper conductor cable of suitable size from ceiling rose to connector, making good disturbed surfaces complete all as specified and as directed. Make Jaquar cat No -LGLZ01X010XW , Orient Cat No- LBLN-10-C-SQ
S & F for recess mounted 2' x 2' square LED panel 36 watts, 596 x 596 x 9mm size, sleek design aluminium housing, polycarbibate diffuser white powder coated finish operating voltage 140 volts - 270 volts, AC, 50 Hz complete all as specified and as directed. Make- Halonix HLFPR22-11-36-CW-37mm, Philips RC383B LED 4000 PSU ODWH PIR, Jaquar LULTU1S036XC.
S & F for LED down light recess mounted luminare, round/square type 15 watts as per site requirement with efficiency of 1500 lumens per watt, Series of downlighters with low depth round & larger dia, powder coated white finish with drop down PC diffuser to deliver low glare illumination with optimized heat sink for efficient heat dissipation and separate replaceable electronic driver suitable for office spaces sleek design white finish operating voltage 150 V-270 V AC, 50 Hz all as specified. Make- JAQUAR Cat part No. LNEP01S015XN/LLCN01R01SXN, Halonix HLDLR31-15CW/ HLDLR-S27-15-CW,Philips DN296B LED 15S-6500 PSU WH.
S & F for LED spot light suitable for operation on 230 volt 50 Hz AC supply Recess-mounted, COB-based, round xed LED downlight with 60 beam angle 08/09 watts or above including driver as per sample including removal of old unserviceable one complete all as specified and as directed. Make Halonix Cat No. HLDLR-31-09-CW, Havells LHEBMKPFIHIW008, Driver LSSCRX1252, Jaquar LETSO1R010XC.
S & F in Repair for Decorative wall mounted luminaire with opal glass with nickle finishing wall lamp with E27 lamp holder with and including LED bulb 10/11 watts complete all as specified and as directed. Make- Jaquar Cat part No - JNL-NKL-WLSL-55004E27 , HALONIX HHW048 08 CF RF or its equivalent in Philips.
S & F for wall mounted LED 06 watts (WW) or more, 3000K with good color rendering (CRI>70) picture light fitting, 230 volts with durable aluminium housing and intregrated electronic driver connector block etc complete with all accessories internally pre wired and necessary mounting arrangements, including taking down old unsv fitting complete all as specified and as directed. Make :-Shakti cat part no SZWPFPX003 or Luker I-3, LIMR6 or Halonix
Supply & fix in replacent decorative wall mounted energy saving 03 watt or above LED bedside light fitting flexible and adjustable to any direction with integeral electronic driver complete with all accessories. Cat Part No 48042 of philips black & metallic , Havells model Uneco or equivalent in Jaquar.
Taking down fan, Sealing cable end, dismantling blades and removing fan and blades from site and fixing or Hanging in existing position after proper cleaning , replacing unserviceable fan condenser 2.5 MFD and connecting up including provision of cable from ceiling rose or connector to fan after room plaster, colour complete all as specified and as directed.
Supply and fixing ceiling fans working on single phase input voltage 140-285 , Sweep- 1200 mm, Power 32 W, 345 RPM , with 232 Air delivery CMM (m3 /min), complete with compact BLDC Motor, blades, down rods, electronic regulator and accessories, including making connections with provision of flexible wire 23 /0.0076 twin core copper conductor from ceiling rose/connector to fan complete all as specified & as directed.
S & F for plastic body exhaust fan, AC single phase, 240 V of size 250 mm sweep with louvers (as per Cat Part No -698502 of Make Indo Asian or equivalent Make- Bajaj Maxima DX/ Usha Crispair )including necessary connection and replacement of flexible copper cable from ceiling rose and taking down of old unserviceable fan complete all as specified and as directed
Taking down carefully existing unserviceable main switch /cutout /DBs of any type, capacity and description and removing materials from site and making good disturbed surfaces of walls, floors as per the existing finishes all as specified and as directed.
S & F sheet metal enclosure MCB DB SPN 8 way with 100 Amps rated bus bar 240 Volts double door with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/ stone masonary etc and making good of disturbed surface to match the existing colour of wall complete all as specified and as directed
S & F for sheet metal enclosure MCB DB SPN 4 way with 200 Amps rated bus bar 240 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. Make - Schneider/Legrand/L&T/ABB.
S & F Vertical TPN Distribution Board in sheet metal enclosure double door 4 Way, 415 volts, 50 Hz, suitable for Flush Mounting and surface Mounting & provision for FP MCCB as incomer up to 160 Amps as I/C ( Frame1) and SP/TP MCB's as outgoing (Modules Optium F1+12) , With -100 Amps Copper insulated Busbar assembly for each phase, isolated Neutral bar, 2 Earthbar and Cable ties for cable management, IP 43 - #IK 09 with metal door including necessary cement work and electrical connections complete all as specified and as directed.
Supplied and fixed Four pole MCCB, Thermal Release Range 63-100 Amps, rupturing Breaking Capacity Icu at 415V AC 50Hz. 30 (kA) complete all as specified and as directed
Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) SP 5 To 32 AMP and current carrying capacity in the MCB DB complete with connection testing and commissioning
Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) SPN 32 AMP and current carrying capacity in the MCB DB complete with connection testing and commissioning
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc.
Taking down the existing unservicable sub main wiring of any type / description as existing at site including making good the disturbed surfaces by plastering disturbed surface smooth by applying two coats of same colour paint as existing to match with the existing finishes all as specified.
S & F submain wiring with 2 single core (FRLS) PVC insulated unsheathed multistranded flexible copper conductor cable, of 6.0 Sqmm and one single core 6.0 Sqmm flame retardent low smoke (FRLS) PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694/1990 drawn through including concealed in brick/stone masonary PVC conduit and conduit accessories heavy duty ISI marked, providing Copper cable sockets plate/ bottle type of adequate size at termination end of cable point wiring in DBs, switch boards, fittings fixtures all as specified and as directed all as specified and as directed complete all as specified and as directed.. Note :- ( Two runs of main copper wire, one run of earth wire cable & PVC conduit shall be measured together as one length).
S & F submain wiring with 2 single core (FRLS) PVC insulated unsheathed multistranded flexible copper conductor cable, of 4.0 Sqmm and one single core 4.0 Sqmm flame retardent low smoke (FRLS) PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694/1990 drawn through including concealed in brick/stone masonary PVC conduit and conduit accessories heavy duty ISI marked, providing Copper cable sockets plate/ bottle type of adequate size at termination end of cable point wiring in DBs, switch boards, fittings fixtures all as specified and as directed all as specified and as directed complete all as specified and as directed. Note :- ( Two runs of main copper wire, one run of earth wire cable & PVC conduit shall be measured together as one length).
S & F S & F sub main wiring with approved colour coding as per IS with four single core PVC insulated FR-LSH cable with stranded copper conductor of size 10 Sqmm nominal area and drawing into PVC non metallic rigid heavy duty PVC conduit and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc two runs of PVC insulated with 10 Sqmm (nominal area) stranded copper conductor FRLSH cable as earth wire , all as per IS 694/1990 drawn through including concealed in brick/stone masonary PVC conduit and conduit accessories heavy duty ISI marked, providing Copper cable sockets plate/ bottle type of adequate size at termination end of cable point wiring in DBs, switch boards, fittings fixtures all as specified and as directed all as specified and as directed complete all as specified and as directed. Note :- ( Four runs of main copper wire, two run of earth wire cable & PVC conduit shall be measured together as one length).
S & F PVC rigid non-metallic flexible conduit ISI marked of dia 25 mm dia inclusive of all tees, bends, elbows reducers, junction box etc and fixing accessories such as couplers, lock nuts, saddles, etc for telephone cable , TV cable and public address system including where required all as directed by Engineer-in- Charge duly concealed in wall complete all as specified and as directed
S & F PVC rigid non-metallic flexible conduit ISI marked of dia 20 mm dia inclusive of all tees, bends, elbows reducers, junction box etc and fixing accessories such as couplers, lock nuts, saddles, etc for telephone cable , TV cable and public address system including where required all as directed by Engineer-in- Charge duly concealed in wall complete all as specified and as directed
M&L for taking down indoor unit of split AC 1.5 TR/ 2 TR carefully including disconnecting all electrical connections & removal of copper tubing and refixing the same after completetion of painting of walls including topping up F-22 or R-134(a) gas as required quantity all as specified and as directed by Engr-In-Charge.
Supply and fix for sheet metal enclosures single pole and neutral enclosure with a two pin and earth plug and socket complete with one MCB SP 20/ 32Amps including removal of old unserviceable one complete all as specified and as directed.Make - Scheinder/Legrand/L&T/ ABB
Supply,installation,testing and commissioning of ceiling mount auto light occupancy, dual technology sensor,adjustable of delay timer, infra red and ultrasonic detection,Dia 8meters IP 20, 3 wire with neutral optimum distance between 2 sensors should be 6 Mtr, stand by consumption 0.8W, fixed directly to a false ceiling with mounting claws (included) or installed in a battibox depth 50 mm all as specified and directed. Note:- All necessary FRLSH copper wires to connect complete lights of office bldg/OR living/Messes etc are deemed to be included in the rates quoted above for motion sensors. Make : Legrand Cat no 048806, SWG 12582DB12 of Siemens, MTN630919 Schneider.
Supply and fix for wall mounted fan of size 400 mm sweep BEE. Five star rated ISI marked and connecting up including provision of cable from ceiling rose or connector to fan complete all as including removal of old unsv fan and handed over to store yard of AGE E/M (North) complete all as specified and directed. Note : a) Quoted Rate is deemed to inclusive of Stickering/Marking/writing of MES numbers in bottom of ceiling Fan as directed by Engr-in-Charge. Make:- Bajaj MIDEA BW 2200, USHA Pentacool, Havells V3,Atomberg
M & L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLSH cable with multistranded copper conductor of size 4.0 Sq mm nominal area and drawn through PVC non metallic rigid PVC casing caping as per site requirement and its accessories including one run of PVC insulated 4.0 Sq mm (nominal area) multistranded copper conductor FRLSH cable as earth wire and connected from DB to DB/ main board complete all as specified and as directed. Note:- Two runs of 4 sqmm cable,one run of 4.0 sqmm cable and one run of heavy duty conduit/casing caping as per site requirement and accessories will be measured as one unit
M & L for Sub main wiring with approved colour coding as per IS with four single core PVC insulated FRLSH cable with multistranded copper conductor of size 10 Sq. mm nominal area and drawing into PVC non metallic rigid casing caping per directions of EIC and its accessaries ISI marked heavt duty of suitable size including with two runs of PVC insulated 10 Sqmm (nominal area) multistranded copper conductor FRLSH cable as earth wire and connected from DB to DB/ main boardcomplete all as specified and as directed. Note:- four runs of 10 sqmm cable, two runs of 10 sqmm cable and one run of PVC heavy duty conduit/casing caping as per site requirement will be measured as one unit.
S & F for MCB DB VTPN 8 way with provision for FP MCB/Isolator/RCCB etc as incommer and SP/TP MCBs as out going double door IP 54 with 250A copper bus bar complete prewired including Bus Bar including MCCB 160 Amps 4 pole for incoming etc suitable for operation on 415 volt 50 Hz AC supply including necessary provision for inserting the DBs double door with locking arrangement in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall with existing paint colour complete all as specified and as directed .
S & F for sheet metal enclosure MCB DB TPN 4 way with 200 Amps rated bus bar 415 volts suitable for fixing double door with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall with existing paint colour complete all as specified and as directed.
S & F for MCB tripple pole and neutral rated capacity 40 to 100 Amps, 415 volts breaking capacity 10 KA complete all as specified and as directed.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 120 Sq mm. complete all as specified and as directed. Note : Provision of suitable double crimpped lugs and glands deemed to be included in quoted rates.
-Ditto- all as per item No 67 but 3.5 core 70 sqmm
-Ditto- all as per item No 67 but 3.5 core 50 sqmm
Supply and laying 50mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 63mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Material and labour for PCC (1:2:4) type B1 (using 20 mm graded broken stone aggregate) as in stay of pole/ plinths/ path including form work and finished the surfaces even and smooth without using extra cement complete all as specified and as directed.
Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 50mm bore for protection of UG cables complete all as specified and as directed.
'- Ditto- all as per Item No. 76 above but 80 mm
Supply, fixing, testing and commissioning in replacement of LT feeder pillar panel CPRI approved single door floor mounted outdoor type, as per IP-65 grade, made out of MS sheet 3.00 mm thick of size 750x600x250mm with aluminium bus bar 400 Amps, 4 strip (3 phase) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking with 250 Amps 25 KA MCCB four pole for incomer cable, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands etc and providing fixing arrangements including earthing lead fixing arrangement, complete all as specified and directed. Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection to LT feeder pillar panel is deemed to included in the quoted rates.
S&F Energy meter 10-60 Amps three phase 4 wire electronic class-1 energy meter (LCD Display) multi function type ISI certified totally tamper proof with tamper & fraud detection and recording with snapshot high accuracy and operated at low voltage with communication compatible with optical port, IR with KWH, KVARH lead, KW, KVA demand, average voltage & average currents PF, frequency including transparent meter cover box with suitable fixing arrangements for cables and meter complete all as specified and as directed.
Supply and fix in repairs resin casted copper wounded Current transformer having ratio 5/200 and 15 VA burden complying with IEC : 62053-21 / IS: 13779 and accuracy of class I including necessary connection with energy meter.
Note : 1. Performance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.
ANIL CONSTRUCTION CO.
M/S Eknath agencies
Akanksha Enterprises
K.K.Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .