Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.9 LAccepted-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | ₹17.9 L Quoted ₹18.8 L | L1 | Accepted-AOC Lowest bidder. |
| 2 | L2₹19.9 L+₹1.2 L (6.29%)Rejected-Finance | ₹19.9 L+₹1.2 L (6.29%) | L2 | Rejected-Finance Not Lowest. |
| 3 | L3₹20.0 L+₹1.2 L (6.62%)Rejected-Finance | ₹20.0 L+₹1.2 L (6.62%) | L3 | Rejected-Finance Not Lowest. |
| 4 | L4₹20.7 L+₹1.9 L (10.2%)Rejected-Finance | ₹20.7 L+₹1.9 L (10.2%) | L4 | Rejected-Finance Not Lowest. |
Tender Value
Refer Docs
EMD Value
₹59,880
Closing Date
12 Oct 2020, 6:00 pmClosed
GE Kamptee
Garrison Engineer, Military Engineer Services, Kamptee Cantt - 441001
REPAIR / REPLACEMENT OF UG CABLE, LED LIGHT FITTINGS AND OTHER MISC E/M WORKS AT MSL UNIT AREA UNDER GE KAMPTEE.
2020_MES_378146_1
8200/E8
Open Tender
Civil Works
Item Rate
180 days
Kamptee
Class D, Cat b (i)
7 documents required · 7 mandatory
₹500
Yes
GE Kamptee
₹59,880
Yes
28 Oct 2020
16 Sept 2020
14 Oct 2020
17 Sept 2020
12 Oct 2020
30 Sept 2020
17 Sept 2020 - 29 Sept 2020
Amount
Taking out of old unserviceable LT UG cable of size 70 sqmm 3.5 core complete all as specified and directed.
All as per item No 1 above but size 50 sq mm 3.5 core complete all as specified and directed.
All as per item No 1 above but size 35 sq mm 3.5 core complete all as specified and directed.
All as per item No 1 above but size 25 sq mm 4 core complete all as specified and directed.
All as per item No 1 above but size 16 sq mm 4 core complete all as specified and directed.
All as per item No 1 above but size 10 sq mm 2 core complete all as specified and directed.
Supply and Laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 70 sq mm, 3.5 core including testing after laid and jointed with lugs, nuts, bolts, washers complete all as specified and as directed.
All as per item No 7 above but size 50 sq mm 3.5 core complete all as specified and directed.
All as per item No 7 above but size 35 sq mm 3.5 core complete all as specified and directed.
All as per item No 7 above but size 25 sq mm 4 core complete all as specified and directed.
All as per item No 7 above but size 16 sq mm 4 core complete all as specified and directed.
All as per item No 7 above but size 10 sq mm 2 core complete all as specified and directed.
Excavation in trenches in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5m in depth for laying of cables, poles, stay and getting out of excavated material complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed.
Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc 1.5m above the starting point complete all as specified and directed.
Fabrication, Supplying Installing, Testing & Commissioning of outdoor type feeder pillar box with rain cowl weather / vermin proof, Indoor type, factory made LT panel, from any CPRI approved manufacturer having dismensions of suitable size with sufficient space between MCCB cable coonection place and body of panel for easily working to workers including necessary incoming & outgoing cable connections, cable glands thimbles of required sizes, made out of CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter & outer double door, the cubical shall have a bottom channel of size 75x40x5mm duly coated with zinc metal coating with satinless steel locking handle arrangement both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 300 mm below the ground grouted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing of existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & neutral of capacity 600 Amps alumunium bus bar duly insulated. (b) Multifunctioning meter to measure Voltage, Ampere, KWH, PF - 1 Nos. (c) One set of pilot lamp. (d) Incoming DPX type MCCB 400 amps 4 Pole 415 volts 36 KA thermal magnetic setting type - 1 Nos (Make:- Legrand Cat No. 420057 or equivalent in L&T/Siemens) (e) Outgoing Type DRX MCCB 200 amps 3 pole 415 volts 16 KA thermal magnetic setting - 1 Nos (Make:- Legrand Cat No. 027008 or equivalent in L&T / Siemens) (f) Outgoing Type DRX MCCB 125 amps 3 pole 415 volts 16 KA thermal magnetic setting - 2 Nos (Make:- Legrand Cat No. 027008 or equivalent in L&T / Siemens) (g) Outgoing Type MCB 63 amps 3 Pole 415 volts 10 KA thermal magnetic setting - 2 Nos (Make:- Legrand / L&T / Siemens) (h) Outgoing Type MCB 32 amps 3 Pole 415 volts 10 KA thermal magnetic setting - 7 Nos (Make:- Legrand / L&T / Siemens) Note:- Old panel should be deposited to MES yard.
Fabrication, Supplying Installing, testing & Commissioning outdoor type feeder pillar box with rain cowl weather / vermin proof, Indoor type, factory made LT panel, from any CPRI approved manufacturer having dismensions of Suitable size with sufficient space between MCCB cable coonection place and body of panel for easily working to workers including necessary incoming & outgoing cable connections, cable glands thimbles of required sizes, made out of CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter & outer double door, the cubical shall have a bottom channel of size 75x40x5mm duly coated with zinc metal coating with satinless steel locking handle arrangement both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 300 mm below the ground grouted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & nuetral of capacity 300 Amps alumunium bus bar duly insulated, (b) Multifunctioning meter to measure Voltage, ampere, KWH, PF -1 Nos (c) one set of pilot lamp. (d) Incoming DPX type MCCB 200 amps 4 Pole 415 volts 16 KA thermal magnetic setting type- 1 Nos (Cat No. 420057 Make:- Legrand or equivalent in L&T/Siemens) (e) Outgoing Type MCCB 63 amps 3 Pole 415 volts 10 KA thermal magnetic setting-5 Nos (Make:- Legrand / L&T / Siemens) (f) Outgoing Type MCB 32 amps 3 Pole 415 volts 10 KA thermal magnetic setting-6 Nos (Make:- Legrand / L&T / Siemens) Note:- Old panel should be deposited to MES yard.
Taking down point wiring with aluminium conductor cable of light point fan & socket light & power complete including light fittings any type switches, sockets, ceiling rose, switch boards, bell/buzzer, bell push, tube light fitting, regulator etc, and making good to the disturbed surfaces of walls/ floor etc to macth with existing surfaces including white washing/colour washing/ distempe-ring to match with existing wall/ floor/ ceiling finishes complete all as specified and directed.
Taking down sub main wiring of any size/ capacity complete all as specified and making good disturbed sufaces to match with the existing surfaces complete all as specified and directed.
M&L for point wiring 1100 volt grade single core FRLSH PVC insulated and unsheathed cable with multistranded copper conductor 1.50 sqmm drawn in and including electrical grade PVC conduit not less than 20mm dia with IS 9537 (Part-III) 1983 marking medium grade on surface of wall/ceilling including FRLS PVC insulated unsheathed earth wire with copper conductor of size 1.50 sqmm pressed steel terminal boxes sunk on wall for mounting of switches, switch sockets, fan regulator etc including laminated sheet cover 3mm thick complete all as specified and making good to distrubed surfaces for one light point controlled by one, one way switch.
All as per item No 20 above but one ceiling/ exhaust fan point controlled by one switch and regulator complete all as specified and directed.
All as per item No 20 above but one 3 pin 5 amp socket out point on the same board with other switches complete all as specified and directed.
All as per item No 20 above but one 3 pin 5 amps socket out let point on independent board complete all as specified and directed.
All as per item No 20 above but one bell/buzzer point controlled by one bell push complete all as specified and directed.
All as per item No 20 above but one light point controlled by two - two way switches complete all as specified and directed.
All as per item No 20 above but wiring with 2.5 sqmm multi stranded cable and earth wire with copper conductor of size 2.5 sqmm for 15 amps power point complete all as specified and directed.
M&L for point wiring 1100 volt grade single core FRLSH PVC insulated & unsheathed cable with multistranded copper conductor 1.50 sqmm drawn in existing eletrical grade PVC conduit not less than 20mm dia with IS 9537 (Part-III) 1983 marking medium grade concealed in wall/ceilling including FRLS PVC insulated unsheathed earth wire with copper conductor of size 1.50 sqmm pressed steel terminal boxes sunk or metal flush box on wall for mounting of switches, switch sockets, fan regulator etc including laminated sheet cover 3mm thick complete all as specified and making good to distrubed surfaces for one light point controlled by one, one way switch.
All as per item No 27 above but one ceiling /exhaust fan point controlled by one switch and regulator complete all as specified and directed.
All as per item No 27 above but one 3 pin 5 amp socket out point on the same board with other switches complete all as specified and directed.
All as per item No 27 above but one 3 pin 5 amps socket out let point on independent board complete all as specified and directed.
All as per item No 27 above but one bell/ buzzer point controlled by one bell push complete all as specified and directed.
All as per item No 27 above but one light point controlled by two - two way switches complete all as specified and directed.
All as per item No 27 above but wiring with 2.5 sqmm multi staranded cable and earth wire with copper conductor of size 2.5 sqmm for 15 amps power point complete all as specified and directed.
M&L for circuit /sub main wiring along with earthwire, FRLSH PVC insulated copper conductor single core cable in surface / recessed as required in size 2 x 2.5 Sqmm with earth wire of 1 x 2.5 Sqmm complete all as specified and directed.
All as per item No 34 above but 2 x 4.0 Sqmm with earth wire of 1 x 4.0 Sqmm complete all as specified and directed.
All as per item No 34 above but 2 x 6.0 Sqmm with earth wire of 1 x 6 Sqmm complete all as specified and directed.
All as per item No 34 above but in existing PVC conduit concealed in wall/ceiling for 2.5 Sqmm with earth wire of 2.5 Sqmm complete all as specified and directed.
All as per item No 37 above but 4.0 Sqmm with earth wire of 4.0 Sqmm complete all as specified and directed.
S&F switch piano flush button, single pole, one way, 6 Amp complete all as specified and directed.
S&F switch piano flush button, single pole, two way, 6 Amp complete all as specified and directed.
S&F socket out let flush type, 2 and 3 pin, 5 amps, 250 volts AC multipurpose complete all as specified and directed.
S&F switch socket combination 2 in 1, 3 pin, 5 amp and 15 amps flush type 250 volts AC complete all as specified and directed.
S&F ceiling rose, surface type, three terminal, 5 amps complete all as specified and directed.
S&F electric bell, ding dong, AC 230 volts, single phase complete all as specified and directed.
S&F bell push, flush type, 5amps complete all as specified and directed.
S&F step type (Socket type) 2 module electronic fan regulator, flush type on existing parabolic laminated sheet etc as required complete all as specified and directed.
S&F lamp holder insulated body with back plate for angle/ battern fitting complete all as specified and directed.
S&F in repair single pole and neutral enclosure with a two pin and socket complete with one single pole MCB of 20 Amp complete all as specified and directed.
S&F 20W LED polycarbonate batten having system lumens > 2000 lumens & made up of co-extruded thermally conductive plastic material & high optically efficient plastic diffuser, input woking range 120Vac to 270Vac, CCT 5700 +/-300K , CRI > 75 , THD < 20% , PF > 0.9 , IP20, 2 Nos. clamps provided for mounting in false ceiling with screw complete all as specified and directed. Make:- CG Cat No LCTLN-20-CDL or equivalent in Wipro, Philips, Bajaj.
S&F 10W LED polycarbonate batten having system lumens > 1000 lumens & made up of co-extruded thermally conductive plastic material & high optically efficient plastic diffuser, input woking range 120Vac to 270Vac, CCT 5700 +/-300K , CRI > 75 , THD < 20% , PF > 0.9 , IP20 , 2 Nos. clamps provided for mounting in false ceiling with screw complete all as specified and directed. Make:- CG Cat No.-LCTLN-10-CDL or equivalent in Wipro, Philips, Bajaj.
S&F LED bulk head fittings for interior and exterior applications within car parks, walkways, stairwells, corridors and housing associations as well as commercial buildings complete all as specified and directed. Make:- CG Cat No. LBHP-10-CDL or equivalent in Wipro, Philips, Bajaj.
S&F 36W LED 600mm x 600mm surface panel having system lumen output > 3600 lumen, fixture comprises of CRCA sheet metal body powder coated in white. The LED clusters are assembled in the body & special high translucent frosted diffuser is used for uniform glare-free light distribution. Input Voltage working range is 150Vac to 280Vac, CRI > 80, CCT 5700 +/-300K, PF > 0.95, THD < 15%, IP20 Protection & 4 Nos. clips provided for suspension mounting, 3.5KV Internal surge protection is provided in driver including suitable size bracket 1.2 mtr long complete all as specified and directed. Make:- CG Cat No LCTLSNE-36-FO-CDL or equivalent in Wipro, Philips, Bajaj.
S&F 25W LED street light comprises of pressure die cast aluminium housing with frame and toughned glass cover having system lumen output > 2500 lumens. All LEDs are Tier 1 LEDs with induvial lens, Input voltage working range is 140Vac to 270Vac, Driver is used with 4KV Internal Surge protection, Short Circuit Protection, open Circuit Protection, High & Low voltage protection, Fixture is IP65 Protected & IK05 protected, THD < 10% , CCT 5700 +/-300K , PF > 0.9 , CRI > 75, including suitable size bracket 1.2 mtr long complete all as specified and directed. Make:- CG Cat No. LST-25-CDL-M/NL or equivalent in Wipro, Philips, Bajaj.
S&F 45W LED street light comprises of pressure die cast aluminium housing with frame and toughned glass cover having system lumen output > 4950 lumens, All LEDs are Tier 1 LEDs with induvial lens, Input voltage working range is 140Vac to 270Vac, Driver is used with 4KV Internal Surge protection, Short Circuit Protection, open Circuit Protection, High & Low voltage protection, Fixture is IP65 Protected & IK05 protected, THD < 10% , CCT 5700 +/-300K , PF > 0.9, CRI > 75 complete all as specified and directed. Make:- CG Cat No.LSTS-45-CDL-M or equivalent in Wipro, Philips, Bajaj.
S&F 200W LED flood light made up of pressure dia cast aluminium housing with toughened glass cover having system lumen output > 22000 lumens, All LEDs are Osram LEDs with induvial lens, Input voltage working range is 120Vac to 280Vac with upper limit cut of at 300Vac, Fixture can with stand for 8hr in case of High Voltage fault up to 400Vac, Potted driver is used with 4KV Surge protection, Short Circuit Protection, open Circuit Protection, High & Low voltage protection with one External 5KV Surge protection, Fixture is IP66 Protected & IK08 protected, THD < 10%, CCT 5700 +/-300K, PF > 0.9, Cable entry through PG9 Cable gland including suitable size bracket 1.2 mtr long complete all as specified and directed. Make:- CG Cat No. LFLN-200-CDL/60-M or equivalent in Wipro, Philips, Bajaj.
S&F 40W LED post top luminaire has a single piece construction, comprises of die cast housing and PC diffuser & spun aluminium reflector having system lumens > 4000. The operating voltage 120-277Vac with PF > 0.9. The LED is SMD type only with CCT 5700K CRI >75. The luminaire is IP 65, IK 10 and Electrical protection Class I. Driver should have 4KV Internal & 5KV External surge protection, The life of LEDs > 50000 hours at L70 (Dimension : top : 410mm dia , 395mm height, OD Size : 62 mm) complete all as specified and directed. Make:- Crompton Cat No LPTO-40-CDL or equivalent in Wipro, Philips, Bajaj.
S&F in repairs LED fitting including drivers having energy consumption upto 20 W, 230 V, 50Hz prewired, complete all as specified and directed. Make:- CG Cat No. S0DVES-24-700-20W or equivalent in Wipro, Philips, Bajaj.
S&F in repairs LED fitting including drivers having energy consumption upto 75W, 230 V, 50Hz prewired, complete all as specified and directed. Make:- CG Cat No. X075C070V107FN1BO or equivalent in Wipro, Philips, Bajaj.
S&F in repairs LED fitting including drivers having energy consumption upto 200 W, 230 V, 50Hz prewired, complete all as specified and directed. Make:- CG Cat No. X220C070V315CNV1AO or equivalent in Wipro, Philips, Bajaj.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 complete all as specified and directed. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore, medium grade & copper lug etc. (f) 40mm nominal bore light grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
S&F in replacement of condenser AC 230 Volt 4.0 MFD complete all as specified and directed.
Taking down sheet metal enclosure DB, main switch etc and making good distrubed sufaces to match with exisiting surfaces complete all as specified and directed.
S&F sheet metal enclosure, single pole & neutral for 240 volts 6 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
S&F sheet metal enclosure single pole & neutral for 240 volts 8 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
S&F sheet metal enclosure triple pole & neutral for 415 volts 4 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
S&F in repair MCB single pole 240 volt 6 to 32 amps 10 KA complete all as specified and directed.
S&F in repair MCB single pole and neutral 240 volt 6 to32 amps 10 KA complete all as specified and directed.
S&F in repair MCB triple pole and neutral 415 volt 40 to 63 amps 10 KA complete all as specified and directed.
S&F double wall corrugated high densty polymer ethyl (HDPE) pipe for laying of electric cable of size 50mm outer dia and 38mm inner dia with IS 14930(Part 2) and 6mm thickness laid in trenches, wall, floor, pole including bends, socket and other connected accessories complete all as specified and directed.
S&F double wall corrugated high densty polymer ethyl (HDPE) pipe for laying of electric cable of size 70mm outer dia and 58mm inner dia with IS 14930 (Part 2) and 6mm thickness laid in trenches, wall, floor, pole including bends, socket and other connected accessories complete all as specified and directed
S&F double wall corrugated high densty polymer ethyl (HDPE) pipe for laying of electric cable of size 90mm outer dia and 78mm inner dia with IS 14930 (Part 2) and 6mm thickness laid in trenches, wall, floor, pole including bends, socket and other connected accessories complete all as specified and directed.
Disconnect and insulate electric supply of wire and taking down carefully ceiling/ exhaust/ cabin/ wall fans of any make and sweep, dismantling blades, check for repairs required complete all as specified and directed. Note:- Repairs/ Replacement of spares shall be carried out under appropriate items.
Hanging only ceiling fans of any make and sweep connecting the complete with & including provision of copper conductor cord 3 core PVC insulated and sheathed from ceiling rose to fan connector and testing, marking of MES No, complete all as specified and directed. Note:- The fan shall be fitted with new set of clamps, rubber shackle, split pins and top and bottom nut bolts etc.
Hanging only exhaust/ cabin/ wall fans of any make and sweep, connecting lug complete with and including provision of copper conductor cord, three core PVC insulated and sheathed from ceiling rose to fan connector & testing, marking of MES No, complete all as directed and specified. Note:- The fan shall be fitted with new set of washers, nuts, rubber packing etc.
Opening up of fan motor of ceiling/ exhaust/ wall/ cabin fans cleaning starter, rotor, cleaning of all parts greasing oiling of bush and bearing re-assembling and testing for smooth functioning complete all as specified and directed.
M&L for taken down burnt/ damaged winding, cleaning stator and rotor including slots etc, rewinding with suitable gauge of super enameled copper insulated wire for ceiling fan 1200mm sweep complete all as specified and directed.
All as per item No 76 above but exhaust fan of 230mm sweep complete all as specified and directed.
All as per item No 76 above but exhaust fan 300mm sweep complete all as specified and directed.
All as per item No 76 above but exhaust fan 450mm sweep complete all as specified and directed.
S&F in replacement bearing for ceiling fan of 1200mm sweep complete all as specified and directed.
All as per item No 80 but exhaust fan 230mm sweep complete all as specified and directed.
All as per item No 80 but exhaust fan 300mm sweep complete all as specified and directed.
All as per item No 80 but exhaust fan 450mm sweep complete all as specified and directed.
S&F gun metal bush for ceiling fan of 1200mm sweep complete all as specified and directed.
S&F in replacement of condenser, AC 230 Volt 2.5 MFD complete all as specified and directed.
S&F in replacement of condenser AC 230 Volt 4.0 MFD complete all as specified and directed.
S&F blades for ceiling fan of 1200mm sweep complete with nuts and bolts as per sample (set of three) complete all as specified and directed.
M&L for shaft work of ceiling fan of any make and sweep complete including filling metal and lathe machining complete all as specified and directed.
M&L for down rod for ceiling fan of any make and sweep made out of medium grade GI tubing, 15mm dia, duly painted with two coats of synthetic enamel paint and provision of holes for electric wire at top and bottom, also arrangement for fitment of ceiling fans complete all as specified and directed.
M&L for MS work such as fan hook angle / FI clamp, MS pipe nuts, bolts, washers welding, bending cold or hot drilling holes for bolts in any shape and size etc including two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
M&L for earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases as required with 25 x 4mm galvanised strip complete all as specified and directed.
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs.70,715.00]
Chinmaya Enteprises
Sharma Electrical and Services
Vaidehi E Link
Bidder Name
Sharma Electrical and Services
Paragon Electrotechnics
Chinmaya Enteprises
Vaidehi E Link
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .