SPL REPAIR/ REPLACEMENT OF ACS, DESERT COOLER, WATER COOLER AGAINST BER UNDER GE NASIRABAD MIL STN AND PROVN OF 02 X HIGH MAST LIGHTS IN SOUTH CAMPUS OF NASIRABAD MIL STN UNDER GE NASIRABAD
2026_MES_784516_1
8764/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Nasirabad
AS PER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹500
Yes
GE NASIRABAD
₹68,000
Yes
14 Aug 2026
14 Aug 2026
4 Sept 2026
14 Aug 2026
2 Sept 2026
28 Aug 2026
14 Aug 2026 - 28 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Material & Labour for Supply, erecting and fixing in true vertical position, 15 Mtr High galvanized mast light system (as per PLG 07 of ILP UK technical report no 7 of ILE UK /IS:875 Part-1 – 2015//BSEN10025/and IS:2062) consisting of totally hot dip galvanised by piece-wise single dipped method high mast, lantern carriage suitable for up to 9 no’s luminaries of 200W each with welded arm (excluding luminaires), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction lights, double drum type self-sustaining winch, integral power tool accessible from door with padlocking arrangement (winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, Stainless steel 6 mm dia. wire ropes (AISI 316, 7 / 19 construction 3 no. rope for lantern carriage & 2 no. rope for winch assembly ) foundation bolt, torque limiter, PR insulated PCP sheathed 5 core x 2.5 Sq.mm trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135.etc. Height of High mast - 15 Mtrs | 2 | EACH | - | - |
| 1.01 | The technical specification for the High Mast Lighting System are here as given under:-
1. Material Construction - IS 2062 grade E350 / BS EN 10025 or
Equivalent having minimum yield strength of 350 N/Sq. mm
2. Top/ Bottom (Diameter of High Mast) - 150/410 MM
3. Nos. of Section of Mast – 2
4. Thickness of Section - 3/4 MM
5. Thickness of Base Plate (Min.) - 25 MM
6. PCD of Foundation - 490 MM
7. No. of Foundation Bolts - 8 Nos.
8. Wire Rope (Nos./Thickness) - 3/6mm, AISI 304
9. Input Supply/Power tool /Torque Limiter - 415V, 3 Phase/ (Reversible
with Plate arrangement for adjusting the tension in the coupling chain
between motor & winch/Mechanical
10. Motor - 1.0 HP
11. Trailing Cable ( Conductor/Type/Size) - Copper/EPR insulated PCP
sheathed cotton braided/5CX4.0 sqmm | - | - | - | - |
| 1.02 | 12. Flood Light 200W should be made of single piece PDC Housing with
lens, & should have inbuilt potted driver with LED Drive current ≤750
MA & should be tested in in-house NABL accredited lab having total
system lumens ≥26000 Lumens with system efficacy ≥130 LPW.
Note :- (a) Complete RCC foundation of specification and size as specified by OEM for High Mast Light Pole is deemed to be included in the unit quoted rate.
(b) High Mast Light technical detail i.e. TDS, Design, Drawings etc. needs to be submitted before make approval. | - | - | - | - |
| 2 | M&L for earthing complete with galvanised steel earth plate electrode 60cm X 60cm X 6mm thick, burried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanized strip 32 X 6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to OH conductor on pole/ Panel/ main switch board etc all as specified or indicated and testing on completion including provision galvanized strip protected by 40 mm bore, light grade pipe and watering pipe shall be 20 mm bore medium grade GI pipe including excavation & earth work, PCC pit with RCC cover, charcoal, salt, funnel, GI strip and protection pipe upto 7.5 mtr complete all as specified and directed. | 4 | EACH JOB | - | - |
| 3 | S & F galvanised iron strip 32 x 6 mm burried in ground /passing through pipe complete all as specified and directed. | 100 | RM | - | - |
| 4 | M & L for test point terminal box made of gunmetal or phosphorus bronze size 75 x 75x 25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hexagonal heads screw complete all as specified and as directed. | 4 | EACH | - | - |
| 5 | Supply, fixing and testing in replacement of energy saving, environmental friendly, long life, exclusive with cast aluminum housing and high power efficient LED flood light 200 watt including driver suitable for working 220-240 volt, AC, 50 HZ with inbuilt power unit, toughened glass cover, IP65/66, 10KV SPD and wired with all accessories complete all as specified and as directed. | 18 | EACH | - | - |
| 6 | Supplying, laying, testing and commissioning of LT UG cable, XLPE insulated heavy duty 16 Sqmm, 4.0 Core armoured cable 1100 V grade, PVC sheathed ,multi stranded aluminium cable fix in pipe /trench /cable duct /fixed on wall by proper size shaped GI clamps with nut bolts etc including aluminium lugs at both ends of cable and making good the disturbed surfaces complete all as specified and as directed. | 160 | RM | - | - |
| 7 | Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m depth for foundation ,laying of cables/pipes/poles etc., and getting out in soft/loose/any type of soil complete all as specified and directed. | 25.92 | CUM | - | - |
| 8 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding of 25 cm thick in soft/loose soil complete all as specified and directed | 25.47 | CUM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.38 MB
GeneralPages8764.pdf
Tender Documents • 0.91 MB
BOQ_879061.xls
BOQ • 3.16 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].