| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 LAccepted-AOC PADAM NAGAR RAMPUR BUSHAHAR | L1 | Accepted-AOC L1 | |
| 2 | L2₹2.0 L+₹8,867.70 (4.52%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹2.3 L+₹30,231.60 (15.4%)Rejected-AOC 284 VEENA NAGAR CAMP DISTT JAGADHARI YAMUNA NAGAR 135001 HARYANA | YAMUNANAGAR | HARYANA | 135001 | L3 | Rejected-AOC L3 |
| Sl No | Description | Qty | Unit | RAJU ENGINEERING WORKS L3 | Susheela krate L2 | Nitin Krate L1 |
|---|---|---|---|---|---|---|
| 1.00Scope of Work | ||||||
| 1.01 | Dismentling of battary bank individual 55 Nos. cell of 2V, 200 AH and replacemnet acid with new acid of specific gravity 1250. | 1 | Nos | 28,000 ₹33,040 | 25,300 ₹29,854 | 24,900 ₹29,382 Lowest |
| 2.01 | Replacement old sulphiric acid of SG 1000 with new acid of SG 1250 in to the 55 Nos. cell. | 385 | Nos | 56,980 ₹67,236.4 | 51,975 ₹61,330.5 Lowest | 52,360 ₹61,784.8 |
| 3.01 | Troubleshooting and servicing of battary charger panel **Charger Details:
* **AC Input:** 415 V, 3 Phase, 4 Wire
* **DC Output Voltage:** 123.75 V (2.75 V/Cell)
* **Output Current:** Float Mode = 20 A, Boost Mode (Start) = 28 A, (Finish) = 14 A
* **Max. Temperature:** 50°C
* **Battery Bank:** 2V, 200 AH, 55 Cells | 1 | Nos | 50,000 ₹59,000 | 45,000 ₹53,100 | 42,000 ₹49,560 Lowest |
| 4.01 | Replacement of damaged auxillary relay 110 V, 3 NO | 5 | Nos | 24,000 ₹28,320 | 23,000 ₹27,140 | 20,500 ₹24,190 Lowest |
| 5.01 | Replacement of damaged DC contactor 20A, 3 Pole, 110 V DC. | 2 | Nos | 9,800 ₹11,564 | 9,200 ₹10,856 | 8,200 ₹9,676 Lowest |
| 6.01 | Replacement of faulty phase failure relay with variable under voltage and over voltage of voltage 430V AC, with 2 NO and 2 NC of make minilec/Schinder, Model No. ALV D2. | 2 | Nos | 14,000 ₹16,520 | 13,200 ₹15,576 | 12,800 ₹15,104 Lowest |
| 7.01 | Replacement of damaged Dropper Diode 40A 800V. | 3 | Nos | 9,000 ₹10,620 | 6,000 ₹7,080 | 5,400 ₹6,372 Lowest |
Tender Value
Refer Docs
EMD Value
₹1,974
Closing Date
24 Sept 2025, 3:00 pmClosed
Sr.ExecutiveEngineer Electrical Mtc. Bhaba Nagar
Sr.ExecutiveEngineer Electrical Mtc. Division HPSEBL Bhaba Nagar
Dismantling of all the cells (2V, 200AH) of Battery bank and replacement all the acid of lower SG with 1250 SG acid, rectification of battery charger electrical fault and replacement of damaged components of battery charger 4x375 KW Rukti Power House
2025_HPSEB_114227_1
No.HPSEBL/EMD/SP-12/2025-26-20
Open Tender
Repair and Maintenance Works
Percentage
15 days
Rukti Power House
Please refer Tender documents.
6 documents required · 6 mandatory
₹590
₹1,974
13 Oct 2025
11 Sept 2025
26 Sept 2025
16 Sept 2025
24 Sept 2025
16 Sept 2025
Scope of Work
Dismentling of battary bank individual 55 Nos. cell of 2V, 200 AH and replacemnet acid with new acid of specific gravity 1250.
Replacement old sulphiric acid of SG 1000 with new acid of SG 1250 in to the 55 Nos. cell.
Troubleshooting and servicing of battary charger panel **Charger Details: * **AC Input:** 415 V, 3 Phase, 4 Wire * **DC Output Voltage:** 123.75 V (2.75 V/Cell) * **Output Current:** Float Mode = 20 A, Boost Mode (Start) = 28 A, (Finish) = 14 A * **Max. Temperature:** 50°C * **Battery Bank:** 2V, 200 AH, 55 Cells
Replacement of damaged auxillary relay 110 V, 3 NO
Replacement of damaged DC contactor 20A, 3 Pole, 110 V DC.
Replacement of faulty phase failure relay with variable under voltage and over voltage of voltage 430V AC, with 2 NO and 2 NC of make minilec/Schinder, Model No. ALV D2.
Replacement of damaged Dropper Diode 40A 800V.
Susheela krate (BID ID -559114)
RAJU ENGINEERING WORKS (BID ID -559360)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .