EXECUTIVE ENGINEER (E)
ELECTRICAL DIVISION-3 SIRI FORT, BEHIND GARGI COLLEGE NEW DELHI-110049
SITC of 2 X 1000 KVA Transformer Substation, DG set, Cabling and allied works at Qutub Golf Course.
2025_DDA_886171_1
50/EE/ELD-3/DDA/2025-26
Open Tender
Electrical Works
Percentage
180 days
As per Tender Document
Please refer Tender documents.
16 documents required · 16 mandatory
₹0
₹5.0 L
SE (E)/East and Sports Vikas minar ITO
5 Jan 2026
28 Nov 2025
12 Dec 2025
28 Nov 2025
11 Dec 2025
2 Dec 2025
2 Dec 2025
Supplying, installation, testing and commissioning of following capacity (continuous loading) BEE 3 Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for out door/indoor applications with On Load Tap Changer (OLTC) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x300 sqmm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 and as per CPWD specifications complete in all respects etc as required at site. The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with + 12.5 percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 35 0C for oil and 400C up to 200 KVA and 40 0C for oil and 45 0C for above 200 KVA for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. For
highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. Design ambient condition: a) air temperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible, as per IS: 1180 Part-3. The entries on the rating plate shall be indelibly marked. Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal size thread) with cover (for sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent above 200 kVA; k) One filter valve on the upper side of the tank (for transformers above 200 kVA); l) Unidirectional flat rollers (for transformers above 200 kVA); m) Inspection hole (for transformers above 200 kVA); n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); o) Buchholz relay for transformers above 800 kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oil temperature indicator and winding temperature indicators for transformers above 200 kVA with suitable tripping mechanism above permissible limit s) Jacking pads (for transformer above 1 600 kVA); t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge (for transformer above 1600 kVA) with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug for all transformers of capacity 50 KVA and above. bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. a) 1000KVA
Main LT Planel Supply, Installation, testing & commissioning of LT panel suitable for 415 V, 3 Phase, 4 wire 50 Hz. AC supply system fabricated in complartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, doors of 2mm thick sheet & 3mm thick for glands plates having 4B segregation and IP 42 protection i/c cleaning and finishing complete with 9 tank process for powder coating of approved shade & colour, short circuit withstand capacity of 31 MVA for 1 Sec. bottom base channel of MS Section not less than 75mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common aluminium earth bar of size 50mm x 6mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5 Sqmm. FRLS PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half having knock outs for cable glands of required size, .Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply system and with 20% spare space, lifting hooks shall also be provided in case of large panels. (Panel shall be as per IS/ IEC 61439 part 1 & 2, type tested from CPRI/ ERDA/ ASTA/ DEKRA i/c. Seismic Compliance Zone-IV and should be internal are tested at 50KA for 0.1-0.5 sec. as per IS/IEC 62271-200. Panel should also have minimum mechanical impact strength of IK09 as per IS/IEC 62262) with following incomer, outgoing metering arrangment and accessories as given below. 1600A, FP, MDO ACB WITH M.P RELEASE LSIG, 50 KA, O/L+S/C+E/F (T/F I/C): Qty = 2 1600A,FP, MDO ACB WITHOUT RELEASE LSIG, 50 KA (B/C): Qty = 1 630A,FP, MDO ACB WITH M.P RELEASE LSIG, 50 KA, O/L+S/C+E/ (DG I/C): Qty = 1 800A,FP, MDO ACB WITH M.P RELEASE LSIG, 50 KA, O/L+S/C+E/ (APFC): Qty = 2 800A,FP, MDO ACB WITH M.P RELEASE LSIG, 50 KA, O/L+S/C+E/ (O/G): Qty = 1 ACB CONVERSION FROM MDO TO EDO:Qty = 7 ACB CONVERSION TO MTX 3.5:Qty = 6 REDUCTION FOR MTX 1.0 RELEASE:Qty = 1 ACB UVR:Qty = 4 400A FP MCCB,Ics=50 KA WITH M.P RLS FOR O/L+S/C+E/F (DG2 I/C): Qty = 1 630A FP MCCB,Ics=36 KA WITH T.M RLS FOR O/L+S/C: Qty = 3 400A FP MCCB,Ics=36 KA WITH T.M RLS FOR O/L+S/C: Qty = 3 250A FP MCCB,Ics=36 KA WITH T.M RLS FOR O/L+S/C: Qty = 4
125A FP MCCB,Ics=36 KA WITH T.M RLS FOR O/L+S/C: Qty = 6 63A FP MCCB,Ics=36 KA WITH T.M RLS FOR O/L+S/C: Qty = 3 ROTARY HANDLE- DN3-3B MCCB: Qty = 7 ROTARY HANDLE- DN2 MCCB: Qt
y = 4 ROTARY HANDLE- DZ1 MCCB: Qty = 9 SPREADER TERMINALS- 630A FP: Qty = 3 SPREADER TERMINALS- 320-400A FP: Qty = 4 SPREADER TERMINALS- 200-250A FP: Qty = 4 SPREADER TERMINALS- 160A FP: Qty = 6 400A FP CONTACTOR,AC-1 DUTY (DG2 I/C): Qty = 1 6A,SP MCB, 10 KA: Qty = 5 2A,SP MCB, 10 KA: Qty = 15 EXHAUST FAN WITH VENTILATION LOUVERS:Qty = 3 3P DIGITL MFM,96 MM, CL-1.0, SUITABLE RANGE, RS-485: Qty = 5 BCS:Qty = 7 AUTO MANUAL/LOCAL REMOTE S.S:Qty = 1 PUSH BUTTONS(RED+1 NC): Qty = 1 PUSH BUTTONS(GREEN + 1 NO): Qty = 1 METERING CTs.,CL-1.0, TAPE INS., SUITABLE VA (1600/5A, 15 VA): Qty = 6 METERING CTs.,CL-1.0, TAPE INS., SUITABLE VA (800/5A, 15 VA): Qty = 3 METERING CTs.,CL-1.0, TAPE INS., SUITABLE VA (400/5A, 15 VA): Qty = 3 IND.LIGHT 220V, LED TYPE.22.5mm DIA. (RED): Qty = 10 IND.LIGHT 220V, LED TYPE.22.5mm DIA. (YELLOW): Qty = 4 IND.LIGHT 220V, LED TYPE.22.5mm DIA. (BLUE): Qty = 4 IND.LIGHT 220V, LED TYPE.22.5mm DIA. (GREEN): Qty = 6 IND.LIGHT 220V, LED TYPE.22.5mm DIA. (AMBER): Qty =5
Outgoings: 1 No. 400 amp FP MCCB, Ics=36 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection 2 No. 250 amp FP MCCB, Ics=36 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection 1 No. 200 amp FP MCCB, Ics=36 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection 2 No. 63 amp FP MCCB, Ics=25 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection Metering: CTs., CL.-1.0. Tape ins., SUITABLE VA 3 No. 630/5A 15VA Rotary Handle 2 No -DN-3B 2 No -DN2 1 No -DN1 1 No -DN0 1 No. AUX. Contact For ON-OFF Indiacation 1 No. 3P digital VAF+PF, 96 MM, CL-10, Suitable Range IND. LIGHT 220V, LD TYPE, 22.5 MM DIA 2 No. Red 1 No. Yellow 1 No. Blue 1 No. Green 1 No. 6A SP MCB, 10KA 3 No. 2A SP MCB, 10KA Complete panel as above
Bus Bars: 400 Amps capacity 4P aluminium extensible type main bus bars & auxillary Bus Bars of suitable capacity with heat shrinkable coured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50 KA capacity. Outgoings: 2 No. 100 amp FP MCCB, Ics=36 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection 6 No. 63 amp FP MCCB, Ics=36 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection Metering: CTs., CL.-1.0. Tape ins., SUITABLE VA 3 No. 400/5A 15VA Rotary Handle 1 No -DN-3B 8 No -DN0 1 No. AUX. Contact For ON-OFF Indiacation 1 No. 3P digital VAF+PF, 96 MM, CL-10, Suitable Range IND. LIGHT 220V, LD TYPE, 22.5 MM DIA 2 No. Red 1 No. Yellow 1 No. Blue 1 No. Green 1 No. 6A SP MCB, 10KA 3 No. 2A SP MCB, 10KA Complete panel as above.
Stilt area Panel Supply, Installation, testing & commissioning of LT panel suitable for 415 V, 3 Phase, 4 wire 50 Hz. AC supply system fabricated in complartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, doors of 2mm thick sheet & 3mm thick for glands plates having 4B segregation and IP 42 protection i/c cleaning and finishing complete with 9 tank process for powder coating of approved shade & colour, short circuit withstand capacity of 31 MVA for 1 Sec. bottom base channel of MS Section not less than 75mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common aluminium earth bar of size 50mm x 6mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5 Sqmm. FRLS PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half having knock outs for cable glands of required size, .Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply system and with 20% spare space, lifting hooks shall also be provided in case of large panels. (Panel shall be as per IS/ IEC 61439 part 1 & 2, type tested from CPRI/ ERDA/ ASTA/ DEKRA i/c. Seismic Compliance Zone-IV and should be internal are tested at 50KA for 0.1-0.5 sec. as per IS/IEC 62271-200. Panel should also have minimum mechanical impact strength of IK09 as per IS/IEC
Bus Bars: 250A, 4P aluminium, colour coded bus bars suitable for 415V, 50Hz. (after deration) Outgoings: 2 No. 100 amp FP MCCB, Ics=25 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection 2 No. 63 amp FP MCCB, Ics=25 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection Metering: CTs., CL.-1.0. Tape ins., SUITABLE VA 3 No. 200/5A 10VA Rotary Handle 2 No -DN2 4 No -DN0 1 No. AUX. Contact For ON-OFF Indiacation 1 No. 3P digital VAF+PF, 96 MM, CL-10, Suitable Range IND. LIGHT 220V, LD TYPE, 22.5 MM DIA 2 No. Red 1 No. Yellow 1 No. Blue 1 No. Green 1 No. 6A SP MCB, 10KA 3 No. 2A SP MCB, 10KA Complete panel as above
Bus Bars: 200A, 4P aluminium, colour coded bus bars suitable for 415V, 50Hz. (after deration) Outgoings: 4 No. 63 amp FP MCCB, Ics=25 KA With T.M RKS For O/L+S/C with adjustable thermal and adjustable magnetic release having overcurrent and short circuit protection 2 No. 12-15 H.P S/D STARTER (AS PER TYPE II CO-ORDINATION TABLE WITH MPCB) 2 No. 2-5 H.P DOL STARTER (AS PER TYPE II CO-ORDINATION TABLE WITH MPCB) Metering: CTs., CL.-1.0. Tape ins., SUITABLE VA 3 No. 150/5A, 5VA Rotary Handle 1 No -DN1 3 No -DN0 1 No. AUX. Contact For ON-OFF Indiacation 1 No. 3P digital VAF+PF, 96 MM, CL-10, Suitable Range IND. LIGHT 220V, LD TYPE, 22.5 MM DIA 2 No. Red 1 No. Yellow 1 No. Blue 1 No. Green 1 No. 6A SP MCB, 10KA 3 No. 2A SP MCB, 10KA Complete panel as above.
Supply of PVC Insulated and PVC sheathed, conforming to IS:1554 (Part-1)- 1988 amended upto date. Cross linked polyethylene insulated, PVC sheathed (XLPE), Conforming to IS: 7098 (Part-1)- 1988 amended upto date. Halogen free flame retardant (HFFR) cable confirming to IS: 17048: 2018 amended upto date. 3.5 Core x 300 Sq. mm
Meter
3.5 Core x 240 Sq. mm
3.5 Core x 95 Sq. mm
4 Core x 16 Sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 35 sq. mm and upto 95 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Laying and Fixing of One number PVC Insulated and PVC Sheather/XLPE Power Cable of 1.1 KV Grade of Following size on Cable Tray as Repuired. Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq mm and upto 95 sq mm (clamped wirh 25x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required 3½ X 95 sq. mm (45mm)
3½ X 240 sq. mm (62mm)
3½ X 300 sq. mm (70mm)
4 X 16 sq. mm (28mm)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excludings and cushioning and protective covering etc., complete as required. 90 mm dia (OD-90 mm & ID-76 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required 240 sq mm
Supply of 11 KV 3 core x 240 sq mm Stranded Compact Circular Aluminium Conductor, Conductor Screen With Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with extruded Semi Conducting Compound in combination with Copper Tape, cores laid up, innersheath of PVC tape, galvanised flat steel strip armoured and overall PVC Sheathed Cable conforming to IS: 1554 (Part-2) 1988 amended upto date. Cross linked polyethylene (XLPE) insulated, PVC sheathed conforming to IS: 7098 (Part-2) -1985, 2011 (Reaffirmed 2021) amended upto date.
EARTHING Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and lying 25 mm X 5 mm. copper strip at 0.50 mter below ground as strip earth electrode i/c connections, terminating with nut, bolt, spring, washer etc. as regd. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt and spring washer spaced at 50 mm).
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm x 5 mm G.I strip on surface or in recess for connections etc as required.
Providing and fixing 25 mmx5 mm copper strip on surface or in recess for connections as reqd
CABLE TRAY Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
DG Set Su
pplying, Installation, Testing & Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings: (A) Diesel Engine: Tourbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 0C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications. (B) Engine mounted Instrument Panel fitted with and having digital dis Plate for following: (i) Start-stop switch with key (ii) Water temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication and Voltage indication (vi) RPM indication (vii) Over speed indication (viii) Low lubricantion Oil trip indication (ix) Engine Running Hours indication (x) Fuel Level
Providing and fixing earth bus of 50 mm x 5 mm copper strip on surface for surface for connections etc. as required.
C) Alternator: Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 0C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation. (D) Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. (E) FUEL TANK: Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. (F) Exhaust System: Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor. (G) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. (H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications
(I) AMF Panel: Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers,
11. Restoration timer 12. Control unit with three impulse automatic engine start/stop and failure to start lockout. 13. Impulse counter with locking and reset facility. 14. ON/OFF/Control circuit switch with indicator 15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning 16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories 17. Maintenance notification based on Engine Run Hour & due date. 18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel , interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring. 400KVA
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.37 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 6.74 MB
NIT.pdf
Tender Documents • 9.16 MB
BOQ_931465.xls
BOQ • 0.36 MB
tech_prebid_931465.pdf
Tender Documents • 0.46 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .