Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.6 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹33.7 L+₹1.2 L (3.79%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹38.7 L+₹6.2 L (19.1%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹45.0 L+₹12.5 L (38.4%)Rejected-Finance PLOT NO 28 SANTOSHIMA COLONY WEST MARREDPALLY SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹45.3 L+₹12.8 L (39.4%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
17 Aug 2022, 6:00 pmClosed
GE I R and D Kanchanbagh
GE I R and D Kanchanbagh Kanchanbagh Post Hyderabad 500058
REPAIR/REPLACEMENT OF UNSV INTERNAL WIRING ELECTRICAL FITTINGS, REPAIRS/ CEILING/ EXHAUST FANS/ SUMMER APPLIANCES AND DAY TO DAY ELECTRICAL COMPLAINTS IN DRDO TOWNSHIP, NAI DSC,CHESS AT KANCHANBAGH HYDERABAD
2022_MES_539868_1
GE I KBAGH TOKEN 27 OF 2022 2023
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Hyderabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanchanbagh
₹94,000
Yes
15 Oct 2022
21 Jul 2022
19 Aug 2022
21 Jul 2022
17 Aug 2022
4 Aug 2022
22 Jul 2022 - 28 Jul 2022
Amount
Material and labour for point wiring complete with ISI marked 1.5 Sqmm PVC insulated multistranded single core cable with copper conductor (FRLS) 1100 volts grade drawn through and including PVC rigid conduit 20 mm or higher dia ISI marked as required at site including conduit accessories such as Junction Boxes, Inspection Covers etc, concealed/surface type on stone/brick masonry walls, roofs, floors etc by means of saddles and clamps etc including PVC gang boxes as required at site for concealed/surface conduit wiring and modular plates & covers as required at site for housing switches sockets, regulators etc. including providing of 1.5 Sqmm PVC insulated multistranded unsheathed FRLS copper conductor as earth continuity conductor and connecting to common earth dolly all as specified for and connecting including taking down old point wiring complete for the following:- One light/ fan point controlled by one, one way switch.
All as per srl Item No. 01 here-in-before but for One ceiling fan/exhaust fan point controlled by one way switch 6 Amps.
All as per srl Item No. 01 here-in-before but for one bell point controlled by one bell push 6 amps.
All as per srl Item No. 01 here-in-before but for Switch Socket outlet 2/3 pins 6 Amps on independent board.
All as per srl Item No. 01 here-in-before but for Switch Socket outlet 2/3 pins 6 Amps on same board.
Material and labour for point wiring complete with ISI marked 4 Sqmm PVC insulated unsheathed multistranded single core cable with copper conductor (FRLS) 1100 volts grade drawn through and including PVC rigid conduit 20 mm or higher dia ISI marked as required at site including conduit accessories such as Junction Boxes, Inspection Covers etc, concealed/surface type on stone/brick masonry walls, roofs, floors etc by means of saddles and clamps etc including PVC gang boxes as required at site for concealed/surface conduit wiring and modular plates & covers as required at site for housing switches sockets, regulators etc. including providing of 4 Sqmm PVC insulated multistranded unsheathed FRLS copper conductor as earth continuity conductor and connecting to common earth dolly all as specified including taking down old point wiring complete as directed.
S&F in repairs switch piano one way 5 Amps 240 Volt complete all as directed.
S&F in repairs switch socket outlet 3 pin,5 Amps 240 Volt complete all as directed.
S&F in repairs switch socket combination 5 pin 15 Amps multipurpose type complete all as directed.
S&F in repairs Bell push flush type 5 Amps complete all as directed.
S&F in repairs lamp holder angle/ batten type complete all as directed.
S&F in repairs fan regulator 240 V AC electronic step type complete all as directed.
S&F in repairs modular fan regulator 120watt 240 V AC two module type complete all as directed.
S&F in replacement for ceiling rose, 3 terminals /PVC/Polycarbonate, isolated body.
S&F in repairs modular Socket 6A-2/3 pin combined two module type complete all as directed.
S&F in repairs modular Socket 6A/16A-2/3 pin combined two module type complete all as directed. :Make: Legrand/Britzy/colours/L&T
S&F in repairs modular 1 way 6Amp switch 1 module complete all as directed.
S&F in repairs 1 way 15 Amp switch 1 module complete all as directed.
S&F in repairs Piano switch 2 way 15 amps1 module complete all as directed.
S&F in repairs bell ding dong, AC, 230V, single pole complete all as directed.
S&F in repairs Buzzer, AC, 230V, single pole complete all as directed.
S&F in repairs bell multi music type complete all as directed. Make: cona/anchor/leader
S&F in repair led luminaire 600 mm x 600 mm 35/36 watt, 220V AC recessed/surface mounted type with high efficiency PMMA diffuser soft glare light with LED efficacy of 120 lm/watt electronic driver,suitable for roof ceiling including connecting up with driver three core copper conductor 1.5 sqmm size complete. Make : Crompton Cat part: LCTRNE-36 FO TL or equivalent in Philips/Wipro/ Shakti
S&F in repairs post top lantern LED type 40 watt 230 watts volts AC outdoor type with decorative post top for 360 degree indirect light IP65 protection with impact and corrosion resistant complete with driver and lamp along with necessary wiring,accessroies complete all as directed. Make : Crompton Cat part: LPTO-40-CDL or equivalent in Philips/Wipro/ Shakti
S&F in replacement retrofit LED polycarbonate tube 18Watt, 6500K CCT,proffesional luminaries single side connection with < 10% THD. Make: Havells Catpart :PHOTONULTRA2.01213T8SSTL18WLED865SPC or equivalent in Philips/Wipro/ Shakti
S&F in replacement LED polycarbonate tube 20Watt, 6500K CCT,proffesional luminaries single side connection with < 10% THD. Make: Havells Catpart :PHOTONULTRA2.01213T8SSTL20WLED865SPC or equivalent in Philips/Wipro/ Shakti
S&F in replacement indoor industrial type surface/wall mounted LED integral batten 18W, 6500K CCT, alluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size all as specified and directed. Make : Havells Cat part: LUMILINE+BS18WLED865SPCSS or equivalent in Philips/Wipro/Shakti
S&F in replacement indoor industrial type surface/wall mounted LED integral batten 20W, 6500K CCT, alluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete removing unserviceable fittings all as specified and directed. . Make : Havells Cat part: LUMILINE+BS20WLED830SPCSS or equivalent in Philips/Wipro/Shakti
S&F in replacement indoor industrial type surface/wall mounted LED integral batten 22W, 6500K CCT, alluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete removing unserviceable fittings all as specified and directed. Make : Havells Cat part: LUMILINEPLUS+BS22WLED865SPCSS or equivalent in Philips/Wipro/Shakti
S&F in replacement indoor industrial type surface/wall mounted LED integral batten 10W, 6500K CCT, alluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete removing unserviceable fittings all as specified and directed. Make : Havells Cat part: LUMILINE+BS10WLED865SPCSS or equivalent in Philips/Wipro/Shakti
S&F in repairs high voltage Neon Transformers 220 to 240 volts, output 750Watts Suitable for energizing the existing neon sign board complete all as directed.
S&F in repairs neon tubing blue colour tube lamp as per existing,operating on 230V, 50Hz, AC single phase including taking down unserviceable tubing complete all as directed.
S&F 320 HT Silicon wiring suitable for connecting existing Neon Transformer to Sign boards including taking down unserviceable wiring complete all as directed.
Dismantling and taking down Geyser of 25/50 litres capacity of any make and pattern from the existing position and removing bolts and nuts, opening and taking out all internal unserviceable parts, leak testing of the inner container, refixing the same in original position after necessary repairs complete all as directed. Note:- Replacement of unserviceable parts will be measured and paid separately under relevant items of this BOQ.
S&F in repairs geyser element of any type and model for 25/50 litres capacity for the 1500 W ISI marked as per site requirement complete all as directed.
All as per srl item No.35 here-in-before but 2000 Watts Make for item No. 35 & 36 :- REMSON/ SEIKO/ POWER PACK/AO SMITH
S&F in repairs thermostat of the geyser, 15 Amps and temperature of 70º C as per site requirement complete all as directed. Make:-REMSON/ POWER PACK/Warmex/AO SMITH
S&F in repairs PVC connection with metal fabricated outer connection for geyser, of best quality 15mm dia, 600mm long with union, brass nuts and washers for hot water pipe for outlet connection complete all as directed. Make : KOHINOOR/ MAHAVIR/ PRAYAG (SYMET)
S&F in repairs PVC connection for geyser, of best quality 15mm dia, 600mm long with union, brass nuts and washers for inlet water pipe complete all as directed. Make : KOHINOOR/ MAHAVIR/ PRAYAG (SYMET)
S&F in repairs copper cable of size 3 core 2.5 Sqmm, PVC insulated sheathed, multistranded copper conductor complete all as directed. Make:-HAVELLS/FINOLEX/ FINECAB/ ANCHOR
Material and Labour for sub main wiring with 2 runs of 2.5 Sqmm single core PVC insulated unsheathed FRLS cable 1100 Volts grade multistranded with copper conductor drawn through and including non metallic rigid PVC conduit ISI marked 25 mm dia including conduit accessories concealed/surface type on walls, roof, floors etc including one run of 2.5 Sqmm PVC copper conductor as earth continuity wire including taking down unserviceable sub main wiring including conduit all as specified and directed. Note : 2 Runs of 2.5 sqmm conductor 1 run of 2.5 sqmm conductor and 1 run of PVC conduit shall be measured as one unit for the purpose of payment.
All as per srl item No. 41 here-in-before but with 2 runs 6 sqmm including 1 run of 6 sqmm PVC copper conductor FRLS cable as earth continuity wire in not less than 25mm dia PVC conduit. Note : 2 Runs of 6 sqmm conductor 1 run of 6 sqmm conductor and 1 run of PVC conduit shall measured as one unit for the purpose of payment.
As per srl item No. 41 here-in-before but 2 runs of 10 Sqmm and 01 run of 10 Sqmm for earth continuity conductor complete all as directed. Note:- 2 runs of 10sqmm copper conductor & 1 run of 10sqmm earth contiunity conductor and one run of PVC conduit shall be measured as one unit length
S&F in repairs non metallic PVC conduit 20 mm dia inclusive of boxes tees, bends, elbows, reducers, tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as directed.
Supply and fix in replacement MCB DB 12 way SPN (double door) sheet metal enclosure factory made suitable for MCB DB's 240 volts with 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed.
Supply and fix in replacement MCB DB 08 way SPN (double door) sheet metal enclosure factory made suitable for MCB DB's 240 volts with 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed .
Supply and fix in replacement MCB TPN DB 04 way (double door) sheet metal enclosure factory made suitable for MCB TPN incomer and MCBs as outgoing with 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed.
Supply and fix in replacement of MCB single pole 6-32 Amps working on 240 volts, 50 HZ AC, 10 KA 'C' curve all as specified and directed.
S&F in replacement of MCB SPN 32-40 Amps working on 240 volts, 50 HZ AC, 10 KA 'C' curve all as specified and directed.
Supply & fixing of MCB TP 40 Amps complete 415 V 50 Hz,10 KA 'C' curve including taking down old un serviceable isolators complete all as directed.
Supply & fixing of MCB 4 pole operating on 415V, AC supply of capacity 63 Amps ,10 KA 'C' curve including taking down old existing un serviceable isolators complete all as directed.
S&F in repairs metallic AC earth plug and socket with sheet metal enclosure with MCB SP 20A complete all as directed.
S&F MCCB 100 Amps, 3/4 pole, 16KA, 415 Volts, 50 HZ, Icu=100%Ics thermal magnetic fixed olc and short circuit rating including necessary fixing arrangement for fixing of MCCB to the existing panel, connecting cable connections including taking down old unserviceable MCCB complete all as directed.
Taking down ceiling fan/exhaust fan/ wall mounted fan / Air circulator fan of any sweep for servicing / repairing / maintenance, opening up, identifying and replacing the defective parts, cleaning, greasing,etc, reassembling and hanging up/fixing back at its original position, connecting up and testing complete all as directed. Note : 1. Cost of spares such as capacitors, bearings, Shaft etc will be measured and paid for separately under respective Item of sch A as supply only.
Supply only capacitor 2.5 mfd suitable for ceiling fan and testing complete all as directed. Make:Epcos/Havells/Tibcon
Supply only capacitor 3.5/ 4.0 mfd suitable for Exhaust fan/Wall mounted fan/Air Circulator Fan . Make:Epcos/Havells/Tibcon
Disconnecting electric connection and taking down carefully fan of any type and size/sweep as described below, removing the burnt winding of fan motor and cleaning the stator completly removing the burnt sludges from the slots and rewinding with super enameled copper winding wire of suitable gauge or of matching size to the exisiting wires with same turns ratio including all insulating material such as insulation paper sleeve, tape, varnishing etc and reassembling, testing, transporting back to site and refixing to original position all as directed:
Celling fan of size 1200/1400mm sweep.
Wall mounted/Pedstal fans size 350/450 mm sweep Oscillating.
Exhaust fan of 350/450 mm sweep.
Supply only bearing No.6201/6202/6203/6204 or any other No matching to the existing size and suitable for ceiling fan/exhaust fan/wall mounted fan. Make: SKF/TATA/ARB
Preparation of old surface of exhaust fan of any sweep by removing old paint using paint remover or by burning off using blow lamp and cleaning with cloth and Spray painting complete exhaust fan with superior quality synthetic enamel paint (Smoke grey) after applying a single coat of primer complete all as directed.
All as per sl item no 58.00 here-in-before but Ceiling fan of size 1200/1400 mm sweep with superior quality enamel paint ( Half White) complete all as directed.
S&F in repairs PVC rectangular block of size 100mmX100mmX50mm for mounting, switches, sockets,PVC sockets,fan regulator
All as per srl item No. 60 here-in-before but of 175mm x 100mm size
All as per srl item No. 60 here-in-before but of 250mm x 300 mm size
Supply and fixing 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections, one twin core cable of size 6 sqmm flat or circular complete all as specified and directed. Make : Havells/Finolex/Plaza
Supply and fixing 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections, one twin core cable of size 10 sqmm flat or circular complete all as specified and directed. Make : Havells/Finolex/Plaza
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0 mm dia of minimum 15m length by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 in SSR PART-I connected to earthing test point all as specified or indicated including provision of earthing lead GI protection pipe light grade of 15mm dia, PCC earth pit with cover, excavation & earth work, testing on completion incl taking out old earthing etc all as specified and as directed by Engr-in-Charge.
S&F/lay in repairs GI earth wire 4 mm dia on walls/floor as earth continuity conductor connected to DBs/ panels etc.
Supply and Fix in repairs GI tubing 15mm dia light grade for protection of GI earth wire complete all as specified and directed.
S&F GI Pipe med grade of size 40mm dia for housing security light/ protection of cables directed including 40 x 5mm MS clamp with nuts, bolts, washers as required after taking down old unserviceable one complete all as specified and directed.
Taking down the evaporative Desert cooler of any size/capacity by disconnecting all the electric connections, cleaning all the components, removing the front panel and painting with two coats of synthetic enamel paint with spray painting complete body and refixing back the front panel and reconnecting with the elctrical connections complete alll as directed.
S&F submersible cooler water pump working on 230 volts, 50 Hz and reconnecting the cfm including taking out the old unserviceable water pump by disconnecting all the water & electrical connection complete all as directed. MAKE : Crompton/Khaitan or any ISI marked.
S&F in repairs fan motor 100% copper wound, ISI marked, three speed working on 230 Volts 50 Hz and reconnecting the same with electrical connections for the evaporative Desert Cooler of capacity 3000/4000 cfm including taking out the old unserviceable fan motor complete all as directed. MAKE : Crompton/Khaitan or as approved by GE.
Supply and fix khus khus pads for the evaporative Desert Cooler of capacity 3000/4000 cfm including taking out the damaged Khus khus pads complete all as directed.
S & F in repairs PVC water tube and distribution with 3 way PVC connection, PVC bends assembly complete, for desert coolers of any make complete for capacity 3000/4000 CUM complete all as directed
S & F in repairs Caster wheels (Set of Four) complete, for desert coolers of any make complete for capacity 3000/4000 CUM complete all as directed
S&F in repairs front grill of desert cooler of capacity 3000/4000 Cum of any make complete all as directed
S&F in repairs rotory switch assembly for desert coolers of capacity 3000/4000 Cum of any make complete all as directed.
S&F in repairs Capacitor of 4/5 MFD capacity suitable for fan motor of desert coolers of capacity 3000/4000 CFM of any make complete all as directed.
M&L for wiring to desert coolers with PVC insulated multistranded, copper conductor single core of size 1.5 Sqmm including PVC clamps, brackets as required and connection, water pump, control switches including taking down old wiring complete all as directed.
M&L for spray painting with synthetic enamel paint of approved tint for water cooler of 40/80 ltrs capacity, any make, after scraping, old damaged paint & making good the disturbed surface to match with the existing surface and shade complete all as directed.
Supply and fix in repairs connection wire of 3 core copper wire PVC insulated of size 4 Sqmm for any capacity window type/Split type AC, water coolers/desert coolers complete all as directed. Make- KEI/ RPG/ INDOASIAN/ FINOLEX/ GLOSTER/ HAVELLS
Taking down carefully existing serviceable split type AC unit of 1.5/2.0 TR capacity and refixing in another location in any position and height complete with all connected work like making opening, fixing mounting brackets and all other required accessories including making good the distrubed surfaces complete all as direcrted
S&F in repairs fan motor bearing and bush for water cooler complete all as directed
S&F in repairs capillary tube including strainer suitable for split type AC 1.5/2.0 TR capacity with necessary brazing, leak testing complete all as directed.
S&F in repairs voltage stabilizer single phase, 230 Volts, AC, 50 Hz of capacity 5 KVA wall mounting type suitable for 1.5 TR split type AC/ window type AC with low and high cut off and intelligent delay input voltage 160 Volts to 260 Volts complete all as directed. Make: V GUARD/ ITL/ BLUE BIRD
Repairing of stabilizer of 4KVA/5KVA capacity including rewiring of Transformer including major/minor spare parts complete all as directed.
Taking out unserviceable 1 Pole contactor from the split type AC and replacing the same with new contactor suitable for 240V, 50Hz coil complete all as directed.
Taking out unserviceable 2 Pole contactor from the split type AC and replacing the same with new contactor suitable for 240V, 50Hz coil complete all as directed.
S&F in repairs drain pipe for rectifying water leakage from AC units complete all as directed.
S&F Brass Valves (set of 2 Nos) suitable for split type AC of capacity 1.5/2TR as per existing type including necessary brazing and sealing the leakage, Leak testing , charging the Refrigerant gas up to required pressure including taking down the unserviceable brass valves complete all as directed. Note :- Gas charging will be measured and paid under relevant item of this schedule.
S&F in repairs wall mounting brackets made out of mild steel (set of 02Nos) coated with anti corrosive paint suitable for mounting outdoor unit of Split AC up to 2.0 TR capacity including all provisions and making good to disturbed surface of wall complete all as directed.
Servicing of Split type Air conditioner of 1.5 TR capacity by disconnecting all the electrical connections, servicing and cleaning the indoor unit & outdoor unit using power jet spray only (external) with suitable foam type cleaning agent duly securing the indoor unit with waste water collecting bag to avoid the spread of water in the working area and out door unit complete to the entire satisfaction of Engr-in-Charge. Note : (i) Servcing should be done using power jet water spray only. (ii) Power jet water spray machine should be provided by contractor. (iii) All included deemed in the quoted rate considered as complete 01 Job.
All as per srl item No. 91 here-in-before but of capacity 2.00 TR.
All as per srl item No. 91 here-in-before but of capacity 3 TR (2 x 1.5 TR multi split)
Leak testing the complete with dry nitrogen, including, cutting, brazing and testing the refrigerant flow system for detecting the leaks and damages with suitable pressuriesed dry nitrogen and brazing to arrest the leaks in any type of air conditioners including testing the system after rectification, etc for the split/window/package type air conditioners of 1.5/2 TR capacity complete all as directed. Note : Refeigerant charging will be measured & Paid Separetly.
S&F fibre/ metallic fan blade for the condensing blower motor of any type/ model/ make for split type AC of 1.5/2.0 TR capacity including removing the unserviceable fan blade complete all as directed.
Taking down the window type Air conditioner of 1.5/2.0 TR capacity by disconnecting all electric connections, oiling, greasing of fan motor replacement of synthetic filter & checking of electric circuit for smooth functioning of AC cleaning, ,condenser coil and evaporating coil with caustic soda and refixing back to its original position and reconnecting the A/C unit with the electrical connections including leak testing complete all as directed.
Taking down the old unserviceable compressor of refrigerator of 165/ 280 litres capacities by disconnecting the electric connections and Supply and fixing compressor including mounting assembly such as rubbers, springs complete all as directed Make : LG/Tecumsha/Voltas
Taking out the unserviceable over load protector for Refrigerator's of capacity 160/200 & 180/220 ltrs. by disconnecting all the electrical connections and supply and fix new over load protector and reconnecting the same with electrical connections including testing of complete all as directed.
Supply only remote cell of size AAA, 1.5V, suitable for split type AC of capacity 1.5/2.0 TR, complete all as directed Make : Eveready/Nippo/Duracell or its equivallent.
Supply & charging / top up of refrigerant R-22 complete all as directed. Make : Mefron/Floron
Supply & charging / top up of refrigerant R-32 complete all as directed. Make : Mefron/Floron
S & F in repairs evaporating coil made out 100% copper tubing having 30/34G aluminium finsanti rust coated for window /split type AC's of 1.5 Ton capacity complete all as directed
All as per srl item No.102.00 but for 2.0 Ton Capacity
Supply and Fix starting capacitor 80 to 100 Mfd for compressor and reconnecting the same with electrical connections for the Split type AC of capacity 1.5/2.0 TR including testing and removing unserviceable starting capacitor complete all as directed.
All as per srl item No. 104.00 here-in-before but for Widow type AC's of capacity 1.5/2.0 TR.
All as per srl item No. 104.00 here-in-before but of Water cooler's of capacity 40/80 & 60/120 ltrs.. Make for item No. 104.00 to 106.00 : Havells/Jaivic/Epcos/Tibcon
S&F in repairs Running Capacitor of 50+2 Mfd for compressor and reconnecting the same with electrical connections complete all as directed.
All as per srl item No. 107.00 here-in-before but of 45 to 50 Mfd for Widow type AC's of capacity 1.5/2.0 TR.
All as per srl item No. 107.00 here-in-before but of 36 Mfd for Water cooler's of capacity 40/80 & 60/120 ltrs..
Supply and fix in repairs fan motor capacitors for split type AC of 1.5/2.0 TR capacity complete all as directed.
All as per srl item No. 110.00 here-in-before but for window type AC's of capacity 1.5/2.0 TR
All as per srl item No. 110.00 here-in-before but for Water cooler's of capacity 40/80 & 60/120 ltrs..
S&F in repairs remote circuit PCB board for 1.5/2.0/3.0 TR capacity split/window type AC as per existing model and capacity, testing for its working including taking down old unserviceable remote circuit PCB board complete all as directed. Make : As per OEM or as per site requirement.
Taking out carefully by disconnecting all connections unserviceable remote circuit PCB Board of 1.5/2.0/3.0 TR capacity split/window type air conditioners and taking to a reputed workshop & replacing all faulty components, making complete functional testing all functions of remote control complete to the entire satisfaction of Engr-in-Charge.
S&F in repairs cooling coil with 100% copper tubing and aluminium fins, anti corrosion coated suitable for 1.5/2TR capacity window type AC/Split type AC of refrigerant (R-22/410/32) compatble complete all as directed. Note : Supply & filling up of refrigerant gas shall be measured and paid separtely under respective item of this schedule.
Repair / maintenance of split/Window type AC, water cooler and desert cooler in its position, testing all the compenents / parts, wiring lidentifying the defective parts & reporting the JE E/M or supervisor for immediate replacement including refixing the appliances after necessary repairs , job includes replacing of any minor spares like wires, bolts, nuts pads and checking all the like air flow, temperature, smooth functioning of applianaces & sealing the pipes hole, checking the drain pipe complete all as directed by Engr-in-charge.
Supply and fix in repairs outdoor split unit assembly with 100% copper condensor coil suitable for capacity 1.5 TR with all spares complete all as directed. Note : Compressor condenser motor assembly will be measured & paid seperately.
All as per srl item No.117.00 here-in-before but suitable for 2 Ton capacity complete all as directed. Make for item No's 117.00 & 118.00 : Carrier Media Ltd or as approved by GE.
Supply and fixing in replacement of hanging clamp of required size with rubber real nuts, bolts including spring washers and locking of splite pin of suitable size for 1200/1400 sweep ceiling fan complete all as specified.
S&F in replacement of down rod 30cm long suitable for ceiling fan complete all as specified and directed.
Supply only PVC electrical insulation tape of size 3/4" x 8 yards x 0.125mm, 40mtr long.
M&L for securing loose wiring and repair to point wiring with necessary rigid non metalic PVC conduit 20mm ISI marked inclusive all accessories complete as specified and directed.
S&F in repairs indicating lamps with holders,connecting up with existing wire of any make,model and capacity of geyser complete all as directed.
S&F in repairs fan blade of set desert cooler mettalic/PVC as per existing model complete for desert coolers of any make complete for capacity 3000/4000 CUM complete all as directed.
Supply only cordless remote suitable for split type AC of capacity 1.5/2.0 TR, 230V, 50Hz complete all as specified and directed Make : As per OEM
S&F in repairs switch socket outlet 3 pin,5 Amps 240 Volt gangbox type complete all as directed. Make: cona/anchor/GM
M&L for point wiring for one light/fan/bell /5amp socket outlet same board/5amp socket outlet independant board point, controlled by one, one way switch with 1.5 sqmm size, PVC insulated and 1100 volts grade, single core (multistrand) copper conductor (FRLS) cable drawn into & including existing conduit and terminal boxes and matching the same with existing surface for mounting fittings like switches, sockets & fan regulators etc with 3mm thick plastic laminated sheet covers fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 1.5 sqmm multistranded FRLS copper conductor cable earth wire and connected to earth dolly complete all as specified and directed, are as follows :-
One light /one fan/one bell point controlled by one switch.
One socket outlet 5 pin 5 amps controlled by one switch on same board.
One socket outlet 5 pins 5 amps controlled by one switch on independent board.
All as per item No. 127 here-in-before but wiring with 4.00 Sqmm for 15 Amps switch socket combination on independent board/two pin earth plug and socket including providing 4 Sqmm PVC insulated multi stranded copper earth continuity conductor and connected to common earth dolly.
S& F in replacement surface mounting Plastic gang boxes suitable for modular switches 3/4 module.Make: GM/Anchor/PressFit
Supply only alluminium fan blade for exhuast fan as per the sample given by the site-in-charge.
S&F in replacement copper wire in wiring circuits as per site requirements PVC insulated single core 2.5 Sqmm FRLS 1100 volts grade multi stranded conductor complete all as directed.
S&F in replacement copper wire in wiring circuits as per site requirements PVC insulated single core 1.5 Sqmm FRLS 1100 volts grade multi stranded conductor complete all as directed .
S&F in replacement of PVC insulated copper conductor of flexible wire of size 40/76 twin core for connecting from fan to electric system complete all as directed.
Supply and fix in replacement VTPN DB 04 way (double door) sheet metal enclosure factory made suitable for MCCB 415 volts incomer and MCBs as outgoing with 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed.
S&F in replacement LED security light fiitting of luminous capacity 2500lumens,IP-66 protection, 5700K CCT, inbuilt electronic driver with <10%THD made up of die cast alluminium housing with high power LED as lighting source and lens embeded toughned glass cover ,seperate driver compartment complete fixing with GI bracket made out of 40mm bore GI pipe light grade 1.5Mtr long bend to shape and fixed to pole/wall with necessary MS clamp accessories complete all as specified and directed by Engr-in-charge. Make:Havells Cat Part:ENDURASUNDOWNSL25WLED765PASYBOPCIHD or equivalent in Jaquar/Crompton/ Shakti
M&L labour for in replacement of earth pit chambers as per SSR Part-I required site complete all as specified and directed.
S&F in replacement for white cover plate with frame 8 module.
S&F in replacement for white cover plate with frame 6 module.
S&F in replacement for white cover plate with frame 4 module.
S&F in replacement for white cover plate with frame 3 module.
S&F in repairs switch socket combination 5 pin 15 Amps multipurpose gangbox type complete all as directed. Make: cona/anchor/GM
S&F in repairs cable lugs of size 16 to 25 sqmm complete all as specified and directed
S&F in repairs cable lugs of size 35 to 50 sqmm complete all as specified and directed
S&F in replacment indoor industrial type surface/wall mounted LED integral batten 10W, 6500K CCT, alluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete removing unserviceable fittings all as specified and directed. Make : Havells Cat part: ENDURALINEARNEOBS10WLED865SPCWH or equivalent in Philips/Wipro/Shakti
S&F geyser assembly 6hole/9hole/12 hole of capacity 25/50ltr capacity as per site requirement.
S&Fin replacement of louver iron shutter for exhaust fan,230mm 12 inch, complete all as directed.
S&F in replacement canopy (set of two) for ceilng fan 1200/1400 mm sweep complete all as directed.
Taking down carefully old burnt/unserviceable compressor unit of 1.5 ton capacity window type AC and replacing the same with factory reconditioned compressor including necessary accessories i e capillary tube including strainer and mounting materials,etc, welding, brazing, leak testing, vaccumissing and charging the refrigerant gas to the required pressure and weight, reinstalling the AC unit on the same place including testing and commissioning complete to any make of AC all as directed by Engr-in-charge.
All as per Item No 147 here-in-before but of 1.5 Ton capacity Split type AC complete all as directed
All as per Item No 147 here-in-before but of 2.0 Ton Split type AC complete all as directed
SRI SAI ENTERPRISES
CHITRA ENGINEERING CORPORATION
Universal refrigeration and Engineering Company
M/s K Venkateswara Rao
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .