Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹23.1 LAdmitted-Finance | -12.95% | ₹23.1 L | L1 | Admitted-Finance |
| 2 | L2₹26.0 LAdmitted-Finance | -1.89% | ₹26.0 L | L2 | Admitted-Finance |
Tender Value
₹26.6 L
EMD Value
₹53,100
Closing Date
17 Feb 2026, 6:00 pmClosed
Executive Engineer
PWD Electrical Division I Jaipur
Upgradation of EPABX System at Lok Bhawan, Jaipur.
2026_CEPWD_537394_1
NIT NO 30 of 2025-26 EE PWD E-I Jaipur
Open Tender
Electrical Works
90 days
Lok Bhawan
Please refer tender documents
2 documents required · 2 mandatory
₹500
Through Egras Challan in Office ID 4222
₹53,100
Yes
In the Chamber of Executive Engineer
19 Feb 2026
11 Feb 2026
18 Feb 2026
11 Feb 2026
17 Feb 2026
11 Feb 2026
16 Feb 2026
S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required. 25 mm
Add extra in item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.
P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra).50 mm
Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect.
Supply & Installation of IP-20 & IK-08 , Wall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with 'U'Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19" angles with wall mounting provision on wall. Accessories like: 1 No of 19" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastner etc as required. 12 U Rack with Width 600 mm & Depth 400 mm + 100 mm
Supplying, installation, Testing and commissioning of following capacity 24 port POE Layer 2 indoor Network Switch having features and specifications etc. as mentioned here under: At least 24 X RJ-45 Gigabit Ethernet Ports and additional 2 X 10G Base -T with 4 X SFP Ports with non-blocking architecture by having Switching capacity of min. 168Gbps and packet forwarding rate of 125Mpps or higher, 16K MAC table. Console Port, USB port, Stacking support of min. 8 units per stack. Internal dual AC Power supply, STP, RSTP, MSTP, BPDU Filter, BPDU Restriction, Min. 9K Jumbo Frame, LBD, IGMP Snooping V1/V2/V3, MLD Snooping V1/V2. IGMP /MLD Groups 1K or more, IPv4/IPv6 Loopback Interface, 16 L3 IP Interface, Ipv6 ND, VRRPv3, UDP Helper, ECMP. VLAN: 802.0Ǫ, Port based, Ǫ-in-Ǫ, Multicast VLAN, Protocol VLAN, VLAN Trunking, DHCP Snooping, Server, server Screening. RADIUS , TACACS+ Authentication, ǪoS: 802.0P, 8 queues per port, ǪoS : WRR, Strict+WRR, WRED, 802.0p. ACL: MAC based, IPv4C IPv6, TCP/UDP Port number, time based ACL, TFTP Client, SNMP V1, v2c, v3, SNMP traps, RMON, DHCP server, relay, client, LLDP, LLDP-MED, OAM, Dying Gasp, 802.0ah, sflow, RIP, OSPF v2/v3, policy based route, SSL, SSH. 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45 access ports. Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required.
SITC of IP-PBX which is IP at its core and act as a Unified Communication System with IP switching technology and 100% non-blocking, configured for below mentioned. The system should be IPV6 ready, should have VoIP and Voice mail at its core i.e. these modules should be mountable on the CPU. The system should be Q Sig Ready, inbuilt Auto-attendant facility, Returned Call to Original Caller (RCOC), CLI based DISA (Mobile Extension)System, Should support SNMP manager for managing and monitor network elements, audit network usage and detect network faults, should support SIP over TLS and SRTP, minimum 2 Gigabit Ethernet ports for LAN and WAN, built-in multi-party conferencing facility with 21 party in a single conference, minimum one RS232 ports for SMDR/PMS/CAS Interface. The System have have capability to also act like Universal Media Gateway when required. The System should have facility of Conversation recording on Analog/Digital/IP ports as well as on Mobile SIP Smartphones, UC Client application for Android, iPhone and on Windows PC. Power supply should be inbuilt and SMPS type with input ranges from 100 – 240 V AC, 47-60 Hz OR 48VDC +/- 15%. The system must have Certification: TEC, CE, FCC, ROHS. 96 analogue extensions, 08 PSTN Trunk Port, 30 Channel SIP PRI, 08 Digital Port, 15 IP User License, 5 IP Softphone/mobile user license, 08 VoIP Channel License along with 8 port Voice Mail expandable upto minimum 224 TDM ports and minimum 500 SIP/IP users without any add-on CPU or chassis/hardware platform.
SITC of Line Card for required Analog / Digital / CO Extensions. compatible to the IP PBX as required. 8 CO Extensions
SITC of IP user license for 10 User with required VOIP Channels. compatible to the IP PBX being used.
SITC of following capacity BIS certified 1Phase Input, 1Phase Output advance DSP controlled IGBT based rectifier Online UPS with Inbuilt Isolation Transformer having 0.99 Input power factor & 0.8 Output factor, Input voltage & frequency range of 180-300V on full load/ 110-300V on 50% load & 50 Hz +/- 5% and output voltage & frequency of 230V+/-1% & 50 +/- 0.1 Hz. Overall efficiency of upto 92% (without Transformer Loss), Overloading of 105 - 110% 30 mins, 111 - 130% 5 mins,131 - 150% 10 sec, THDv of < 3% for Linear & < 5% for Non linear load.UPS should have LED Panel with LCD display showing load level, Battery Voltage Level, Input & Output Voltage, Input & Output Frequency. UPS should have protection from Input High / Low;Over Load;Short Circuit; Over Temperature and give audible alarms on Battery Mode;Low Battery;Fault;Over Load & Bypass Mode. SMF Batteries of 12V VRLA for 30 mins with MS Rack and necessary cable for UPS to Batteries Installation. UPS should have valid Certification like Type III environmental declarations from third party renowned agency complying to ISO 14025, CE, ROHS,BIS,EN 62040-1, EN 62040-2, IEC 62040-3 Etc. as required. 5KVA UPS with 4992 VAH Battery
S&F following sizes of ISI marked ( IS:14927 P - II ) uPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners etc. as required. 100 mm x 50 mm
Supplying and Laying PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 & confirming to TEC specification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair for Identification etc. as required.2 pair
Supply and Laying of PE Insulated jelly filled Armoured Telephone Cable. with 0.6 mm thick Solid Annealed Bare Copper Conductor and confirming to TEC specifications confirming. to DOT GR/CUG-01/Aug.2003 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. 5 pair
Supply and Laying of PE Insulated jelly filled Armoured Telephone Cable. with 0.6 mm thick Solid Annealed Bare Copper Conductor and confirming to TEC specifications confirming. to DOT GR/CUG-01/Aug.2003 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. 50 pair
Supply and Laying of PE Insulated jelly filled Armoured Telephone Cable. with 0.6 mm thick Solid Annealed Bare Copper Conductor and confirming to TEC specifications confirming. to DOT GR/CUG-01/Aug.2003 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. 100 pair
P & F Krone module with base frame in the recess / surface made out of 1.2 mm thick sheet steel box, front openable, having locking arrangements duly powder coated ,including dressing, ferruling and punching of telephone cable with krone tool etc. as required. 20 Pairs
P & F Krone module with base frame in the recess / surface made out of 1.2 mm thick sheet steel box, front openable, having locking arrangements duly powder coated ,including dressing, ferruling and punching of telephone cable with krone tool etc. as required. 50 Pairs
P & F Krone module with base frame in the recess / surface made out of 1.2 mm thick sheet steel box, front openable, having locking arrangements duly powder coated ,including dressing, ferruling and punching of telephone cable with krone tool etc. as required. 200 Pairs
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.73 MB
Tendernotice_2.pdf
PDF • 1.90 MB
BOQ_957533.xls
BOQ • 0.36 MB
Cover1.pdf
Tender Documents • 0.35 MB
Download all tender documents and submit your bid