EE I CKHED
P 12 C I T Road 1st floor Kolkata 700014
SITC of Fire Detection System at G PLUS SEVEN storied Boys and Girls hostel of Dr R Ahmed Dental College N Hospital Kolkata
2022_WBPWD_399693_1
WBPWD/EE-I/CKHED/NIT-19/22-23
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Dr R Ahmed Dental College N Hospital
AS PER NIT
4 documents required · 4 mandatory
₹16,000
P 12 C I T Road 1st floor Kolkata 700014
20 Oct 2022
30 Aug 2022
14 Sept 2022
30 Aug 2022
12 Sept 2022
7 Sept 2022
5 Sept 2022
Amount
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable multisensor detector IP 42 (VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator is to be provided extra as per NFPA without extra cost) the detectors should have built in LED response indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Johnson Controls / Edward/ Secutron/ Ravel / Securiton/ Apollo / Morley /Eaton / GST/ Honeywell) [Girls Hostel : 6 nos and Boys Hostel : 6 nos]
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Smoke detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have maximum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator part detector is to be provided extra as per NFPA without extra cost ) the detectors should have built in response LED indicator. (Approved Make: Cerberus Pro /Johnson Controls / Edward/ Secutron/ Ravel / Securiton/ Apollo / Morley / Eaton / GST / Honeywell) [Girls Hostel : 19 nos and Boys Hostel : 22 nos]
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have maximum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator part detector is to be provided extra as per NFPA without extra cost ) the detectors should have built in response LED indicator. (Approved Make: Cerberus Pro /Johnson Controls / Edward/ Secutron/ Ravel / Securiton/ Apollo / Morley / Eaton / GST / Honeywell) [Girls Hostel : 2 nos and Boys Hostel : 2 nos]
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL /ERTL/ LPCB / FM approved) (Approved Make: Cerberus Pro/Johnson Controls / Edward /Secutron/ Ravel / Securiton/ Apollo / Morley / Eaton/ GST/ Honeywell) [Girls Hostel : 8 nos and Boys Hostel : 12 nos]
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL /ERTL/LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Cerberus Pro/ Johnson Controls/Edward/Secutron/ Ravel / Securiton/ Apollo /Morley / Eaton/ GST / Honeywell). [Girls Hostel : 8 nos and Boys Hostel : 12 nos]
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab/KEI/Gloster) with 20mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall. [Girls Hostel : 560 mtr and Boys Hostel : 640 mtr]
Supply, Installation, Testing & Commisioning of Microprocessor based Intelligent, addressable expandable and fully networkable Fire Alarm Control Panel ( VDS / UL / ERTL / LPCB / FM / EN approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make : Cerberus Pro / Johnson Controls / Edward/ Secutron/ Ravel /Securiton/ Apollo / Morley /Eaton / GST/Siemens/Honeywell). [Girls Hostel : 1 no and Boys Hostel : 1 no]
NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm & Signalling Code 5. local Statutory Regulations 6. Manufacturer Recommendation. 7. System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand.
TESTS: 1.The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system under active monitoring of OEM. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done. Before taking up the work necessary building drawing/ floor plan with layout should be prepared and to be approved from the fire safety Cell of PWD according to the prevailing fire safety policy. After commissioning, necessary testing to be done in presence of fire safety cell.
The Agency must procure the materials from the Manufacturer/OEM or from their authorized sales channel so that the standard warranty/supprot of the Manufacturer/OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer/OEM or from their authorized sales channel and standard warranty/support should be sent from the e-mail of the Manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Rate should be quoted incl. of all taxes and cess.
Defect Liability period : 1 year
PERFECT IMAGE SOLUTIONS
ASSOCIATED ELECTRICAL CONST CO. 1963 PVT.LTD
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .