| 1 | L1₹18.3 LAccepted-AOC 37 TILAK NAGAR MATHURA 281001 | MATHURA | MATHURA | UTTAR PRADESH | 281001 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹21.6 L+₹1.7 L (8.30%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹23.2 L+₹3.2 L (16.1%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | Rejected-Technical 37 222 BUNDU KATRA AGRA UP | AGRA | UP | - | Rejected-Technical Rejected due to not enlisted in desired category |
| Sl No | Description | Qty | Unit | Vijay Electricals L3 | M/s A.K. ENGINEERS L1 | DEMROT ELECTRICAL WORKS L2 |
|---|---|---|---|---|---|---|
| 1.00 | Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed. | 224.4 | Cum | 300 ₹67,320 | 90 ₹20,196 Lowest | 150 ₹33,660 |
| 2.00 | All as per serial item No. 2.00 here-in-before but depth exc 1.5 metre and not exc 3 metre complete all as specified and as directed. | 1 | Cum | 600 ₹600 | 150 ₹150 Lowest | 300 ₹300 |
| 3.00 | Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed. | 143.1 | Cum | 40 ₹5,724 | 30 ₹4,293 Lowest | 50 ₹7,155 |
| 4.00 | Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed. | 81.3 | Cum | 90 ₹7,317 | 30 ₹2,439 Lowest | 50 ₹4,065 |
| 5.00 | Supply and erecting of steel tubular swaged pole with cast iron base plate, finial taper plug, bolts, nuts & washers as per IS 2713 (Part-II) 1980 made out of mild steel tubing, type 410 SP-55 (11 metre long) including painting of poles with one coat of red oxide primer and two coat of aluminum paint (one coat before fixing and one coat of aluminum paint after fixing) over exposed surface and two coats of bituminous paint over embedded portion & the portion above coping shall be painted in alternative bands of black and yellow colour starting with white colour (each band of 30cm wide) by two coats of super enameled paint upto 1.5m height including taking out old unserviceable HT PCC Pole complete all as specified and directed.
Note :- Excavation, earthwork, PCC in foundation & coping shall be measured and paid for separately. | 2 | Each Job | 20,000 ₹40,000 | 18,000 ₹36,000 Lowest | 18,000 ₹36,000 Lowest |
| 6.00 | M&L for PCC (1:3:6) type C-2 using 40mm graded crushed stone aggregate as in foundation for stays & filling, mass concrete and similar works including necessary form work as required and fair finishing complete all as specified and directed.
Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment. | 5.5 | Cum | 4,500 ₹24,750 | 2,200 ₹12,100 Lowest | 3,000 ₹16,500 |
| 7.00 | M&L for cement concrete 1:2:4 type B1 using 20mm graded crushed stone aggregate as in copings, pedestal of poles and the like including use and waste of form work (straight or curved), all exposed surface of concrete finished even & smooth without using extra cement, complete all as specified & as directed.
Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment. | 2 | Cum | 4,500 ₹9,000 | 3,000 ₹6,000 Lowest | 4,000 ₹8,000 |
| 8.00 | M&L for sand cushioning using clean local unwashed river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of under ground electric cable complete all as specified and as directed.
Notes:-(i) Approved local river sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured. | 53 | Cum | 300 ₹15,900 Lowest | 450 ₹23,850 | 400 ₹21,200 |
| 9.00 | Supplying and laying factory made, un-reinforced precast concrete cable cover, ISI marked, Class HV, Type 1, flat, size 300mm x 180mm x 40mm, laid as cable protection cover in trenches, complete all as specified & as directed. | 2,700 | Each | 25 ₹67,500 | 12 ₹32,400 Lowest | 20 ₹54,000 |
| 10.00 | Supply, laying, jointing and testing HT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium stranded conductor 11000 Volt (Earthed) grade of cross sectional area 95 Sqmm, 3 Core (ISI marked) laid in trenches/ducts, through pipe, under floors or roads/ along poles etc, including dismantling & taking out old unserviceable HT cable, complete all as specified & as directed.
Notes :- (i) Sand cushioning, cable protection, GI protection pipe, jointing kits and excavation & earth work shall be measured & paid for separately.
(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions. | 400 | RM | 900 ₹3,60,000 | 890 ₹3,56,000 | 780 ₹3,12,000 Lowest |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
11 Nov 2025, 6:00 pmClosed
CWE Mathura
HQ CWE Mathura
As per Tender documents
2025_MES_736167_1
CWE/MTR/BPR/ of 2025-26
Open Tender
Civil Works
Item Rate
180 days
GE Bharatpur
As per NIT documents
7 documents required · 7 mandatory
₹500
GE Bharatpur
₹50,000
Yes
7 Jan 2026
21 Oct 2025
18 Nov 2025
21 Oct 2025
11 Nov 2025
4 Nov 2025
Amount
Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
All as per serial item No. 2.00 here-in-before but depth exc 1.5 metre and not exc 3 metre complete all as specified and as directed.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.
Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed.
Supply and erecting of steel tubular swaged pole with cast iron base plate, finial taper plug, bolts, nuts & washers as per IS 2713 (Part-II) 1980 made out of mild steel tubing, type 410 SP-55 (11 metre long) including painting of poles with one coat of red oxide primer and two coat of aluminum paint (one coat before fixing and one coat of aluminum paint after fixing) over exposed surface and two coats of bituminous paint over embedded portion & the portion above coping shall be painted in alternative bands of black and yellow colour starting with white colour (each band of 30cm wide) by two coats of super enameled paint upto 1.5m height including taking out old unserviceable HT PCC Pole complete all as specified and directed. Note :- Excavation, earthwork, PCC in foundation & coping shall be measured and paid for separately.
M&L for PCC (1:3:6) type C-2 using 40mm graded crushed stone aggregate as in foundation for stays & filling, mass concrete and similar works including necessary form work as required and fair finishing complete all as specified and directed. Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment.
M&L for cement concrete 1:2:4 type B1 using 20mm graded crushed stone aggregate as in copings, pedestal of poles and the like including use and waste of form work (straight or curved), all exposed surface of concrete finished even & smooth without using extra cement, complete all as specified & as directed. Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment.
M&L for sand cushioning using clean local unwashed river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of under ground electric cable complete all as specified and as directed. Notes:-(i) Approved local river sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured.
Supplying and laying factory made, un-reinforced precast concrete cable cover, ISI marked, Class HV, Type 1, flat, size 300mm x 180mm x 40mm, laid as cable protection cover in trenches, complete all as specified & as directed.
Supply, laying, jointing and testing HT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium stranded conductor 11000 Volt (Earthed) grade of cross sectional area 95 Sqmm, 3 Core (ISI marked) laid in trenches/ducts, through pipe, under floors or roads/ along poles etc, including dismantling & taking out old unserviceable HT cable, complete all as specified & as directed. Notes :- (i) Sand cushioning, cable protection, GI protection pipe, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
All as per serial item No 10.00 here-in-before but of size 120 Sqmm 3 Core complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for Galvanized iron tubing, 100mm bore, light grade, ISI marked, including all fittings and laid in trenches/under road/drains/foors, fixed to poles/walls with required size of flat iron (25mmx3mm) clamps, bolts, nuts and washers for protection of HT electric cable including taking down old unserviceable cable protection pipe with clamps complete all as specified & as directed. Note :- Excavation & earthwork shall be measured & paid for separately.
M&L for Boring of holes under road, pavement, hard standing, etc by manually without disturbing the top surface suitable for passing the GI protection pipe for cables complete all as specified and as directed.
S&F Aluminium Conductor Steel Reinforced (ACSR) of any size as directed, stringing for overhead line on 11 KV HT poles including jointing with and including aluminium binding wire 2 mm dia, jumpers, line tapes, conducting jelly, stretching properly and connecting with suitable PG clamps, etc including dismantling and taking down old existing unserviceable aluminium conductor steel reinforced (ACSR) of any size/type/capacity, complete all as specified and as directed. Notes : (i) The ACSR conductors shall conforming to IS-398 (Part-II) and as specified in SSR Part-I. (ii) The unit rate quoted shall also deemed to include for supply and fixing of binding wire, aluminium tapes, etc which shall not be included in the weight of conductors for payment. (iii) Weight of conductors shall be determined by measuring the horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra shall be added for sag, jointing, jumpers etc. (iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS code.
S&F cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections conforming to Grade E-165 (Fe 290) including nuts, bolts, washers, welding, bending cold or hot, drilled holes for bolts, in any shape or size as directed with & including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces after preparation of surfaces including taking down old cross arms, bracing, supports, clamps and back plates etc complete all as specified and as directed. Note: - (i) Sizes, sections & types of members and shape of the cross arms etc shall be as required at site and all as directed. (ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only. Cost of the same is included in unit rate of the item and nothing extra shall be paid on this account. (iii) Weight of paint shall not be considered for payment purpose and quoted rate shall deemed to be included this aspect.
S&F in replacement of Switch air break, gang operated outdoor, Vertical operated type, HT 11 KV, Triple pole, 200 Amps, 3 insulator per phase, rotating vertical type, with fixed contacts of phosphorous bronze and moving contacts of copper, manually operated from ground level with operating mechanism including GI tubing medium grade 25mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with Mink conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for vertical mounting, fixed complete all as specified and as directed.
S&F in replacement of Switch air break, gang operated outdoor, Horizontal operated type, HT 11 KV, Triple pole, 400 Amps, 3 insulator per phase, tilting/rocking horizontal type, with fixed contacts of phosphorous bronze and moving contacts of copper, manually operated from ground level with operating mechanism including GI tubing medium grade 25mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with Mink conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for horizontal mounting, fixed in repairs, complete all as specified and as directed.
S&F in replacement of Lightning arresters HT 11 KV, 65 kilo Amp Non linear expulsion type complete with all fittings distribution class discharge with standard fittings confirming to IS-3070 (Part-I) 1993, fixed complete all as specified & as directed.
S&F Pin type insulator, porcelain, vitreous, white, brown or green for working pressure 11000 Volts, 150mm height and 150mm dia including galvanized mild steel spindle, two Nos GI washers, one No GI nut, including dismantling & taking down old unserviceable insulator, complete all as specified & as directed.
S&F Disc type insulator, porcelain, vitreous, 145mm high and 255mm dia ball and socket type, white, brown or green, single disc assembly for tension with tension clamps for conductors, working pressure 11000 Volts, including dismantling & taking down old unserviceable insulator, complete all as specified & as directed.
S&F Post type insulator with GI post for holding fixed/moving contact assembly including fixing arrangement suitable for air break gang operated switch 400 to 800 Amp, Single Pole, white, brown or green, working pressure 11000 Volts, including dismantling & taking down old unserviceable insulator, complete all as specified & as directed.
S&F in replacement of Earthing continuity conductor or main earthing lead fixed to wall or batten or recess or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6 mm galvanized iron strip complete all as specified and directed.
S&F Danger notice plate of 25x20cm size, 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour for HT 11000 Volts and fixed with suitable MS clamps made out of flat iron 25x3mm, bolts and nuts of approved size, fixed in repairs, complete all as specified & as directed.
S&F Danger notice plate of 20x15cm size, 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour for LT 1100 Volts and fixed with suitable MS clamps made out of flat iron 20x3mm, bolts and nuts of approved size, fixed in repairs, complete all as specified & as directed.
Dehydration & filtration of transformer oil with portable filtration cum dehydration machine to improve the dielectric strength, not less than 40 to 60 KV within 1 minute with 4 mm Gap at site of any installation in Cantt area of any capacity/make of transformer installed on pole mounted, indoor/outdoor type plinth mounted complete all as specified and as directed. Notes: (i) All necessary T&P / testing equipment shall be provided by the contractor at his own cost. No extra payment shall be made to the contractor. (ii) Contractor shall ensure that there shall be no wastage of transformer oil. (iii) Contractor shall ensure that conservator tank is full to its level before starting the dehydration. (iv) New Transformer Oil required for topping up shall be measured and paid for separately under relevant item of this Schedule. (v) Testing of dielectric strength of dehydrated transformer oil of each transformer shall be carried out in the presence of Engineer-in-Charge and cost thereof shall be borne by the contractor.
Supply and filling in replacement or new mineral grade transformer oil EHV type conforming to IS-335 of 1993 for topping up in transformer duly filtered with filtration plant to obtain high dielectric strength not less than 60 KV (gap 2.5mm) complete all as specified and as directed. Note : Transformer oil shall be supplied in sealed barrels with test certificate. Cost of barrel shall be deemed to be included in the unit rate quoted by the contractor and empty barrel will be property of the Department and same shall be deposited to the AGE E/M Store Yard. Nothing extra shall be paid on this account.
M&L for disconnecting of defective transformer (indoor/outdoor type) 11 KV/433 Volts copper wound from power mains and dismantling the same from 2/4 Pole structure/ platform mounted, uploading and transporting by using crane and vehicles the same to authorised workshop and opening the transformer cover, draining out of tranformer oil and keep safely for reuse after filtration, assembling, removing of the burnt parts i.e tape, paper insulating strings etc gently and carefully, washing of the dust, rust and dirt from all parts including taking out HT/LT leg coil core tank and cooling tubes, painting the inner side tank by zinc chromate paint, spray painting outside by enemelled smoke gray colour paint and preparing the same for re-assembling after opening of core with coil and carrying out required repair and Transporting and re-installation on existing 2/4 Pole structure/ platform with neccessary fixing arrangment including connecting up electrical connections, commissioning and testing complete all as directed by Engineer-in-Charge and specified in particular specification of the following capacity complete (HT/LT limb case shall be measured and paid seperately)
Transformer (indoor/outdoor type) capacity 50 KVA to 200 KVA
Transformer (indoor/outdoor type) capacity 250 KVA to 500 KVA
Supply only LT limb coils with triple papper coated and insulation varnishing complete all as specified and as directed.
Supply only HT limb coils with triple papper coated and insulation varnishing complete all as specified and as directed.
Supply only HT bushing complete with brass/tinned copper rod with nuts, washers, gasket set for transformer of capacity 50 KVA to 250 KVA complete all as specified and as directed.
Supply only HT bushing complete with brass/tinned copper rod with nuts, washers, gasket set for transformer of capacity 315 KVA to 500 KVA complete all as specified and as directed.
Supply only LT bushing complete with brass/tinned copper rod with nuts, washers, gasket set for transformer of capacity 50 KVA to 250 KVA complete all as specified and as directed.
Supply only LT bushing complete with brass/tinned copper rod with nuts, washers, gasket set for transformer of capacity 315 KVA to 500 KVA complete all as specified and as directed.
Supply only tap changer switch 11 KV complete with rod and gasket for transformer capacity 50 KVA to 250 KVA complete all as specified and as directed.
Supply only tap changer switch 11 KV complete with rod and gasket for transformer capacity 315 KVA to 500 KVA complete all as specified and as directed.
Opening of transformer cover at site for carrying out repairs such as replacment of bushing rods, gasket, insulators and minor spare parts etc and re-assembling after carrying out required at site repair in the transformer complete all as specified and as directed. Note :- Bushing rods shall be measured and paid separately.
Taking out silica gel from unserviceable breather assembly of transformer of any capacity and supply & filling new Silica Gel blue in crystal complete all as specified and as directed.
Supply and fixing in replacement indicator lamp in different colour code LED/Neon type suitable RYB including making connection with copper conductor cable of suitable size complete all as specified and as directed.
M&L for uprooting upto 30cm depth grass/weeds/plant by scrapping soil in order to made free ground from all sort of vegetation including supply & spray chemical (glycel 41% Sl or equivalent) for prevention of growth of weed and grass in electrical sub station with spray gun as per the manufacturer's instructioned complete all as specified and as directed.
Supply and spread and leveling Graded coarse aggregate in loose filling over the surface of stone aggregate 20mm nominal size in the installation yard complete all as specified and as directed by Engr-in-Charge.
Supply and spread and leveling Graded coarse aggregate in loose filling over the surface of stone aggregate 40mm nominal size in the installation yard complete all as specified and as directed by Engr-in-Charge.
Material and labour in replacement of earthing complete with copper earthing with copper earth plate electrode 60cm x 60cm x 3.15mm buried directly in ground (earth pit not less than 4.0 mtr deep below normal ground level) with top edge of the plate not less than 2.95 mtrs deep below normal ground level, connecting to and including copper earth strip 20x3mm as earthing strip by means of bolts, nuts, check nuts and washers, including watering arrangement with 25mm GI pipe medium grade upto top of plate and 50mm bore light grade GI pipe for earth strip protected with and necessary excavation and earth work with mixing magnesium sulphate (100 Kg) ), charcoal (250 Kg) and common salt (200 Kg) filling and vegitable soil all around the plate upto 350mm above from top edge of plate and balance portion filling with excavated soil in layers not exc 25cm thick, including PCC (1:3:6) C-1 for chamber of internal size 30cmx30cmx12cm thick wall and 70cm x 70cm x 15cm thick bed concrete and RCC (1:2:4), type B-1 for precast chamber cover 50mm thick reinforced with welded steel wire fabric or XRM jali (weight not less than 4 Kg/Sqmm),GI funnel with wire mesh test point, testing and commissioning compele all as specified and directed. Note:- (i) On testing, after completion, if the earth resistance below 1 Ohms is not obtained, earthing will rejuvenated at no extra cost till the desired earth resistance is obtined. (ii) Quoted rate shall be deemed to included for earth strip with protection pipe upto 7.5metre length.
Material and labour for replacement of unserviciable existing earthing with bore well earthing with the help of mechanical boring machine 150mm bore, 30 metre depth supply and fixing 160mm dia (OD), UPVC pipe 6 Kg/sqcm rating, 06 metre long with the help of suitable size clamp with nut bolt and washer - 01 No including charcoal dust, salt fill in bore well for earth conductivity M&L for covering of bore well with PCC (1:2:4) type B-1 using 20mm graded stone aggregate / Brick masonry pit of size 45x45x45cm complete and give the minimum earth test result below 1 ohm complete all as specified and directed by Engineer-in-charge. Note :- (i) The earth pit shall be refilled by boulders free from vegetable soil. (ii) Earthing shall be tested by contractor in presence of Engr-in-charge.Record shall be maintained.Payment shall be admissible only after satisfactory test results.
Supply & fixing in replacement of Galvanised iron tubing 50mm bore medium grade including necessary all fittings for lowering in bore well of depth upto 30 metre complete all as specified & directed by Engr-in-charge.
M&L for Repir/Maintenance of drawout type / trolly mounted HT VCB/RMUs 11 KV by cleaning the VCB/RMU by using air blower, tightening of connections/ controls, checking of all fuses, spray painting outside by enemelled smoke gray colour paint/sealing of VCB/RMU at bottom, repairing of mechanical parts, oiling/greesing of all moving parts and carrying out following checks for smooth functioning complete all as specified & directed. (a) Visual Inspection. (b) Checking of functional locks, interlocks, signalling devices and auxillery devices. (c) Checking of suitability and correct operations of protections, control instruments and electrical connection of the circuit breaker operating mechnasim. (d) Checking of Tripping Mechanism Operation. (e) Spring Charging Limit Switch Operation. (f) Checking with stand voltage on the auxillary circumstances. (g) Checking of with stand voltage at power frequency. (h) Checking of Breaker ON/OFF Operation manually & electrically. (i) Testing of vacuum Bottle Integrity. (j) Relay Testing. (k) Checking of the resistance of the main circumstances. (l) Verification of wiring. Note : (i) Work shall be executed by the authorised service center of manufacturer. (ii) Spare part if found defective will be measured & paid seperately as supply & fixing in repair under respective item of this BOQ.
Supply and fixing in replacement of battery 12 Volt, 17 AH, fixed to Metering module of RMU for auto charging of spring with compatible existing system complete all as specified & directed. Make : C&S/Crompton/CG
Supply and fixing in replacement of 110 Volt, 17 AH DC power pack for operation of relay of VCB complete all as specified & directed.
Supply and fixing in replacement of closing coil operating voltage 24 Volt, DC suitable for 11 KV VCB/SF-6 Gas breaker complete all as specified & directed. Make : AREVA/CG/Schneider
Supply and fixing in replacement of TNC switch suitable for 11 KV VCB complete all as specified & directed. Make : C&S/Crompton/CG/AREVA/SCHNEIDER
Supply and fixing in replacement of Resin based insulator suitable for existing 11 KV Breaker complete all as specified & directed.
Supply only ratchet wheel assembly with ratchet pin suitable for 11 KV VCB complete all as specified & directed.
Supply only trip catch assy suitable for 11 KV VCB complete all as specified & directed.
Supply and fixing in replacement of Trivector meter for VCB/RMU including disconnecting the existing and connecting the new one with necessary wiring complete with compatible existing system complete all as specified & directed by Engg in Charge.
Supply and fixing in replacement of MCCB 200 Amps capacity, 4 Pole, 415 Volt, rupturing capacity 36 KA, Adjustable thermal & fixed magnetic setting Ics=100% of Icu complete all as specified & directed.
Supply and fixing in replacement of MCCB 250 Amps capacity, 4 Pole, 415 Volt, rupturing capacity 36 KA, Adjustable thermal & fixed magnetic setting Ics=100% of Icu complete all as specified & directed.
Supply and fixing in replacement of MCCB 630 Amps capacity, 4 Pole, 415 Volt, rupturing capacity 50 KA, Adjustable thermal & fixed magnetic setting Ics=100% of Icu complete all as specified & directed.
Supply and fixing in replacement of VAF + PF meter in panel high accuracy input voltage measurement range 50-520 VAC (P-P), Aux supply 80-300 VAC/DC, CT secondary side 1A/5A, Flush mounting 96x96, CT/PT programmable, Para meters VLL, VLN, A, F, PF, on Hours, Hz Apeak etc complete all as specified & directed.
Supply and fixing stay wire complete length 7/4mm dia grade 2 as directed complete all as specified & as directed.
S&F Stay assembly complete with 20mm dia, 1800mm long GI stay rod, with threaded ends and GI nuts, two number thimbles, MS galvanized clamps made out of 40mmx6mm flat iron including MS galvanized nuts, bolts and washers, 200mm x 200mm x 6mm MS galvanized stay plate, stay bow, galvanized stay strand 7/4 mm including loop type insulator and stay clamp, with & including painting of exposed MS work with two coats of aluminium paint over a coat of red oxide zinc chromate primer, all as shown in electrical plate No 1 of MES Schedule Part-I, complete all as specified and as directed. Note : Excavation & earthwork and PCC shall be measured & paid for separately under respective items of this Schedule.
S&F in replacement of Anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered complete all as specified & directed. Note : Clamps shall be measured & paid for separately.
Supply and fixing in replacement of complete intenal wiring for ABB REJ601 relay with copper conductor, PVC insulate cable for SF6 type VCB of any capacity as per manufacturer instruction with compatible existing system complete all as specified & directed by Engr in Charge.
Supply and fixing in replacement of locking device kit for door assembly of outdoor type Ring Main Unit with compatible existing system complete all as specified & directed by Engr in Charge.
Supply and fixing in replacement of complete GASKET rubber tube type of outdoor type Ring Main Unit any type with compatible existing system complete all as specified & directed by Engr in Charge. Make : C&S/Crompton/CG
Supply and fixing in replacement of Current Transformer for metering module of Ring Main Unit with compatible existing system complete all as specified & directed by Engr in Charge. Make : C&S/Crompton/CG/Schnider/Siemens
Supply and fixing in replacement of Potential Transformer for metering module of Ring Main Unit with compatible existing system complete all as specified & directed by Engr in Charge. Make : C&S/Crompton/CG/Schnider/Siemens
Supply, installation, testing and setting of Digital Protection relay with Instant trip for phase and earth fault, relay to be fixed in existing 11 KV VCB drawout type, including taking down old unserviceable relay complete all as specified & directed.
Tracing out the Fault in existing underground HT cables network under any depth below or above the existing earth surface by earth work, fault locator machine, expertise staff and repair the same by required spares materials in existing position whenever informed by Engr-in-charge or JE E/M in the AOR at Bharatpur including testing on completion complete all as specified & directed. Note : (i) The all T&P and earth work shall be included in quoted rates and no extra cost shall be claim by the contractor. (ii) The neccessary materials any type required to repair the fault shall be measured and paid separately under relevent item of BOQ under Sch 'A'.
M&L for HT cable route indicator made out of PCC (1:2:4) type B-0 (using 12.5mm graded stone aggregate of size 1000mm (H) x 120mm (W) x 80mm (thick), painted with orange colour lettering synthetic enamel paint and embedded in PCC block (1:3:6) type C-2 (using 40mm grade stone aggregate) of size 150mm x 150mm x 200mm including necessary excavation for PCC block, placed at interval of 30 metre complete all as specified and directed by Engr-in-Charge.
Supplying and laying synthetic Rubber insulated mats 2.5mm thick for voltage upto 11 KV for electrical purpose as suitable for electrical shock safety of size 2mx1m complete all as specified and directed by Engr-in-Charge.
M&L for replacement of broken earth chamber cover by providing RCC Cover (1:2:4), Type B-1, using 20mm graded stone aggregate of size 550x550x40mm thick, reinforced with 8mm dia MS TMT bars @ 100mm C/C both ways with MS handle 12mm dia complete all as specified and as directed.
M&L for factory made chequered cement concrete tiles, 20cm x 20cm x 25mm thick, set, jointed and pointed in neat cement slurry in floors with grey cement & pigment, over & including 15mm thick screed bed in cement & sand mortar 1:6, including dismantling existing tiles completed all as specified and directed.
M&L for painting of transformer of any capacity and size by using sand papers and applying one coat suitable primer and applying of synthetic enamel paint through spray gun by arranging compressor at site with adequate power generating set complete all as specified and directed by Engineer-in-Charge.
M&L for painting steel tubular poles 11 metre height with two coats of synthetic enamel paint alternatively with black and yellow colour, after coping and remaining portion with aluminium paint but including brckets, clamp & cross arms (i.e single poles, 2/3/4/6 Pole structure) etc complete all as specified and directed.
M&L for calibration of IDMT microprocessor based nemuric relay fixed in 11 KV HT panel by primary and secondary injection method and setting the relay tripping timing in advance to match the outgoing load on the incoming and outgoing feeders complete all as specified and directed. Note : (i) individual Breaker VCB/RMU shall be considered as one unit and above Job is to be carried out unit wise. Above Job will be carried out by licenced technician as approved by GE. (ii) Any accident/mishappening occurred during the execution of work shall be responsibility of Contractor. (iii) All necessary tools & plants required to carry out above job will be provided by contractor and the cost of the same deemed to be included in quoted reate.
Supply and fixing in replacement breather assembly with fresh silica gel for transformer of capacity 63 KVA to 500 KVA complete all as specified and as directed.
Demolition of brickwork or stone/boulder masonry, built in cement mortar or cement lime mortar including all quoins, arches, pillars, etc but excluding ashlar facings, dressed stonework and precast concrete articles complete all as specified and as directed.
M&L for brick work with old size burnt clay sub-class ‘B’ bricks, straight or curved on plan exc 6.00 metre mean radius, built in cement mortar 1:4 for platform with steps for transformer complete all as specified and as directed.
M&L for rendering 15mm thick in cement mortar 1:4 on fair faces of brick masonry or concrete surfaces of walls, finished even & smooth without using extra cement including two coats of white wash complete all as specified and directed.
DEMROT ELECTRICAL WORKS (BID ID -3477390)
Vijay Electricals (BID ID -3470387)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.43 MB
Tender.pdf
Tender Documents • 1.26 MB
BOQ_824318.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .