Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹5.5 LAccepted-AOC | ₹5.5 L | L-1 | Accepted-AOC Accepted by competent authority |
Tender Value
₹5.8 L
EMD Value
₹11,600
Closing Date
20 Feb 2024, 6:00 pmClosed
EE(E), ED-I, Jaipur
Room No. 301, IIIrd Floor, TAX Bldg, M.I. Road, Jaipur
Rate Contract for Providing Call Basis Maintenance of Diesel Engine Alternator Sets in Various TE / BTS Sites under BA Jaipur
2024_BSNL_184729_1
53 /23-24/BSNL/ED-I/JP/09
Open Tender
Electrical Works
Item Rate
180 days
Jaipur BA
Please refer Tender documents.
4 documents required · 4 mandatory
₹590
AO (Cash), O/o PGMTD, BSNL, JAIPUR
₹11,600
27 Mar 2024
6 Feb 2024
22 Feb 2024
6 Feb 2024
20 Feb 2024
6 Feb 2024
Amount
Visit charges to attend fault of DEA Set on call basis / complaint basis on behalf of written Job order from SDE(E) concerned for different TE / BTS sites under jurisidication including attending the minor faults involving no material and submit detailed report for major fault to the Engineering -In-charge i/c fare charges to visit the site from HQ etc complete as reqd.
Note:- (1). Visit Charges are not payabie, if cost of work executed at particular site is beyond Rs 5000/-. (2). The Charges shall be paid only subject to submission of detailed site visit report in Job Order along with bill for sites where servicing / major repairing work not carried out by agency. (3). Charges shall be paid proportinately to attend the complaints e.g. 3 Sites for visit up to 30 KM's on a route, 2 Sites for visit more than 30 KM & Up to 60 KM on a route and 1 Site for visit beyond 60 KM from HQ .
Pdg & Making of General Servicing of the following capacity E/A sets of different make and model installed at TE/BTS Sites comprising of following jobs i/c Fare and labour charge i/c complete checking of E/A Set after servicing and replacement of consumables for proper working as per manufacturer recommendations etc. complete as reqd.
i). Cleaning the bowl inside as well as out side of fuel filter and oil filter , replacement of sealing ring.
ii). Cleaning the fuel strainer with clean diesel i/c pressure testing of fuel injector and it should be as per manufacturer recommendation.
iii). Cleaning the cooling system (Raditor)
iv). Replacement of Air cleaner element if reqd.
v). Checking all belt Drives and retensioning the same etc as reqd.
vi). Remove the tapet cover and checking the valve clearance gap between rocker arm toe and valve stem end in cold condition as per manufacturer recommendation i/c replacement of tappet cover gasket if reqd. etc. as reqd..
vii). Cleaning the entire E/A Set (inclusive of fins, blower and block). i.e. oil & grease etc.
viii). Cleaning of diesel tank if reqd.
ix).Checking of charging alternaror, starter self and engine control panel connection, gauges and indicators and its fuction.
x). Checking and setting of fuel supply and time as per manufacturer recommendations.
NOTE: 1. After servicing the set, a trial test also be carried out by the firm for 30 minutes and check its performance & submitt the readings of out put voltage, current (for each phase) and frequency, LOP, RPM, Hr Meter Reading with working condition status report etc. in Service Report. 2. This item shall be paid only after submission of desired report along with Job Order duly verified by concerned telecom authorities & SDE(E) Concerned.
Up to 20 KVA DEA sets
More Than 20 KVA & Upto 32.5 KVA DEA Sets
More Than 32.5 KVA & up to 55 KVA DEA Sets
Replacement of the following Parts / Items in existing Different capacity and make of Engines I/c dismentling of faulty parts, fixing the new in place of faulty parts , testing etc as reqd. ( Note- Make and Model as per manufacturer recommendation )
(a) Diesel Filter Element Set ( 1 Ltr )
(b) Oil Filter Element ( 1/2 Ltr )
(c) Oil Filter Element ( 1 Ltr )
(d) Diesel Filter Element Set ( 1/2 Ltr )
(e) Oil Filter Set suitable for E/A Set of 50/55 KVA
(f) Lubricating Oil Multi Grade ( 20W40)
(g) Steel Wire Braided Fuel Pipe Line
(h) Stop Solenoid 12 Volt
(i) Starting Key with Switch
(j) Mechanical Type RPM Cum Hr Meter
(k) Mechanical Type RPM Cum HR Meter Chain
(l) Battery Leads Red & Black Standard Length & Size i/c terminals
(m) Coolant for Radiator of superior quality or as recommended by manufacturer
(n) V-belt
(o) Hose pipe set
(p) Techo Drive Unit
(q) Fuel Feed Pump assembly.
Replacement of the following Parts / Items in existing Different capacity and make E/A Set AMF / Manual Control Panels I/c dismentling of faulty parts, fixing the new in place of faulty parts , testing etc as reqd. ( Note- Make and Model as per manufacturer recommendation )
(a) Solid state SMPS or SCR based battery chargers suitable up to 12v, 180 AH Battery ( Make - VNT or Similar Superior make)
(b) Push Button Switch for Start/ Stop/Reset
(c) 12 V DC / 220 V AC HR Meter Counter Type
Supplying & fixing of 12 Volt Battery Operated Self Starter suitable for Starting of Engine i/c fixing the same on the DG set making connections testing etc. complete as reqd. ( Make- Autolek or Similar Superior Make)
Supplying & fixing of 12 Volt Battery Charging Alternator on the existing DG set i/c making connections testing etc. complete as reqd. ( Make -Autolek or Similar Superior Make)
Replacement of following faulty items in the existing Alteranator up to 55 KVA Capacity at TE / BTS Sites i/c dismentling the faulty, replacement by new one i/c fixing, testing, commissioning etc. complete as reqd.
(a) AVR ( M/s National or Similar Superior Make)
(b) Power Diode for Rotating Rectifier Assembly
Pdg General Servicing and Repairing of Battery Charging Alternator / Dynamo that’s I/c dismentalling of equipment , greasing and oiling of bearings and other parts , repairing of rectifier assembly , replacement of carbon brush etc. and complete checking of battery operated alternator and fixing with proper alignment etc complete as reqd.
Repairing & General Servicing of the existing faulty radiator up to 100 KVA Diesel Engine alternator set by repairing of leakage and cleaning of copper tubes with help of cleaning agents, dismentling of radiator assembly including transportation, brazing and testing for leakage and re-installation after repairing the same etc. reqd.
Pdg General servicing and Repairing of 12 Volts Engine Starting Self that I/c dismentalling of equipments, greasing and oiling of bearing and other parts , cleaning of self with petrol , replacement of Carbon Brush , Housing etc. complete checking of self and testing and fixing with proper alignment with gears etc complete as reqd.
Providing of following Core and Size PVC insulated and PVC sheathed grade Aluminium conductor armoured cable of 1.1 KV grade confirming to relevent IS-Specification complete as reqd. ( Note - Cable shall be provided at Site / Handed over to SSA Authority as per direction of Engg. in Charge )
(a) 2 Core 10 Sqmm
(b) 4 Core 16 Sqmm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Upto 35 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size fo PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 kV grade as required.
2 X 10 sq. mm ( 19 mm)
4 X 16 sq. mm ( 28 mm)
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required.
S/I/T/C of 32 amps four pole ON Load Side Handle operated change over switch in steel enclosure capable of working 415/500 V i/c drilling hole on the board, making connection, earthing the body etc. as reqd.
S/I/T/C of 63 amps 2 Pole ON Load Side Handle operated change over switch in steel enclosure capable of working 240 V i/c drilling hole on the board, making connection, earthing the body etc. as reqd.
S/I/T/C of 63 amps four pole ON Load Side Handle operated change over switch in steel enclosure capable of working 415/500 V i/c drilling hole on the board, making connection, earthing the body etc. as reqd.
Providing and fixing 63 A TPN disconnector fuse switch unit in sheet steel enclosure a/w HRC fuses capable of working 415/500 V i/c drilling hole on the board, making connection, earthing the body etc. as reqd.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .