Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹82.2 LAccepted-AOC ERODE 638 002 | ERODE | TAMIL NADU | 638002 | ₹82.2 L Quoted ₹83.6 L | L1 | Accepted-AOC WORK AWARDED |
| 2 | L2₹84.7 LRejected-AOC | ₹84.7 L | L2 | Rejected-AOC SECOND LOWEST |
| 3 | L3₹86.3 LRejected-AOC NO 1 2 BIG STREET SAKKARAMALLUR VILLAGE POST ARCOT TALUK RANIPET DISTRICT 632 511 | TIRUVANNAMALAI | TAMIL NADU | 632511 | ₹86.3 L | L3 | Rejected-AOC THIRD LOWEST |
| Sl No | Description | Qty | Unit | SURESHBABU L3 | R BALAMURUGAN L2 | R SURESHMANI L1 |
|---|---|---|---|---|---|---|
| 1.00 | RMG Unit : Supply, Erection, testing and commissioning of 11KV 25 KA 630Amps 3 Panel HT OUTDOOR RING MAIN GEAR Switch board suitable for indoor installation comprising two incomer panels with Air Break/ load Breaks switches and one outgoing panel with Vacuum Circuit Breaker complete as per specification with Mechanical inter lock between incomers. 1. Supply and Erection of draw out type 11KV 25 KA 630 Amps Horizontal draw out./Horizontal Isolation VACCUM CIRCUIT BREAKER fitted with motor ( 230 V AC) operated spring charged Mechanism, with ON and Off indicator Anti pumping Device, 110V DC shunt trip and closing coils ( DC source of supply to be derived from a power pack suitable for three Tripping and two closing operations incorporated on Incoming panel only) Mechanical Operation counter, 4 No + NC spare Aux contact with contact multiplication contractor for customer use. Automatic safety shitter, Mechanical close/Trip Knob, Mechanical ON/OFF Indication, operating Handle, 230V AC to 110V DC power pack operating handle, 2. Supply and Erection of 11KV 630 Amps 25 KA HT Air Break/Load Break switch with mechanically inter locked each switch, front operated spring assisted manual closing mechanism 2NO + 2NC Aux. contact 3. 11 KV /Root 3/110V Root3-Three phase 3 Limb 50 VA class 0.2 Resin cast Draw out type potential Transformer complete with HT and LT HRC fuses with sealing arrangement – 3Nos, 4. Current Transformer of suitable Ratio/5-5A Dual core ( Core1-5VA clas 0.2 for metering & crore 2-15 VA 5 P 20 for protection – 3Nos, 5. Meters: Analog Ammeter with 5 position selector switch-1no Analog Voltmeter with selector switch-1No cut out provision to receive digital Tri Vector Meter L & T or secure to be provided. | 1 | No | 8,10,230 ₹8.1 L | 7,94,790 ₹7.9 L | 7,73,570 ₹7.7 L |
| 1.016. Protection: IDMT two over current and one earth fault Relay with high set Inst. Elements 1.3 seconds-1No Master Trip relay Megawin MVAJH 13 equivalent – 1No, 7. Breaker ON/OFF indication LED type-2Nos Auto Trip/Healthy Trip and spring charged indication LED type – 3Nos phase indicating Lamps, 8. TNC Breaker control switch-1No Local Remote selector switch -1No push button for trip Healthy -1No, 9. Panel Mounting Surge Arrester-9KV, 10KA, 10. 630Amps copper Bus bar PVC sleeved & required panel earthing, 11. Common for switch gear, MCB’s for AC/DC control Heater ON/OFF switch with space Heater and thermostat, single phases switch socket, cubicle illumination TL Lamp,Door switch fully covered Test Terminal block of IMP Make ( wherever applicable) 12. MS sheet steel enclosure for outdoor Installation powder coated with Siemens Gray finish, 13.Provision through bottom entry to receive Incoming or Outgoing cable Termination kit (Make : Mega win/System Control | ||||||
| 2.00 | Indoor Singel Panel Consumer VCB: Supply, erection, testing, commissioning and of 11KV 25KA HT Single panel Vacuum Circuit Breaker Switch, Indoor type for installation, board comprising one Incomer VCB and 2 Nos Outgoing 630A 500MVA VCB.1.Draw out type 11KV 500MVA 630A Horizontal Draw out/ Horizontal Isolation VCB operated with spring charged mechanism.Anti Pumping device ,110V DC Shunt Trip and closing Coils (DC source of supply to be derived from a Power pack suitable for 3 Tripping and Two closing operation counter, 4NO + 4NC spare Aux. Contact for customer use, Automatic safety shutter, Mechanical Close/ Trip knob, Mechanical ON/OFF indication, Operating Handle, 110V AC-110V DC Power Pack etc. Core(Core 1-15VA class 1 for metering and core 2-15VA 5P 10 for Protection) Incoming 1 No, Current Transformers of 30/5-5 Amps Dual Core (Core 1-15VA Class 1 for Metering and Core 2-15VA 5P 10 for Protection)(Outgoing-1) 4.Meters: 2. 11KV/Root 3/ 110V/ Root3- Three Phase, 3 Limb 200VA Class 1 Resin Cast Draw out type Potential transformers complete with HT and LT HRC fuses. Digital Voltmeter with selector switch (Incoming 1 No) Digital Trivector of L&T/Secure make (Incom-1No) Digital Power Factor Meter (Incom-1 No) Digital Frquency Meter (Incom-1 No) 5. Protection: TP ND IDMT 2OC + 1EF Relay with Highest inst.Elements similar like Megawin type MCDG 61 (Incom-1No) | 2 | Nos | 5,36,620 ₹10.7 L | 5,26,400 ₹10.5 L | 5,25,000 ₹10.5 L |
| 2.016. TP ND IDMT 2OC + 1 EF Relay similar like Megawin type MCDG 31 Master trip Relay Megawin MVAJH 13 (Incom-1No & Out-1 No) 7. Breaker ON/OFF/Auto Trip/Healthy/Spring Charged Indication Lamp LED Type, 8. Phase Indication Lamps R,Y,B(Incomings 3Nos), 9. Control Wiring, 10. 630Amps Copper Bus bar PVC Sleeved and required panel copper earthing, 11. Control switch TNC, 12.Trip Circuit healthy Push Button(Incoming-1 No, Outgoing -1No), 13. Common for Switch gear, MCB's for AC DC Control, Heater ON/OFF Switch with space Heater and thermostat Single phase switch socket, cubicle illumination lamp, Disconnecting type terminal Block.etc., 14. MS Sheet enclosure for Indoor Installations Powder. | ||||||
| 3.00 | Type OLTC Transformer: Supply, erection, testing and Commissioning of 630 KVA 22KV/ 433V,copper wound ON (OLTC) load tap changing copper wound Indoor type distribution transformer OLTC type of cooling conforming to relevant IS 1180- Level 2 and fitted with the following and standard accessories. (A) HV cable end box suitable for connecting 3 core 300 sq.mm11KVXLPE HT cable., (B) LT Cable end box suitable for connection 4 runs of 3 ½ x 300 sq.mm LTUG cables., (C) Tapping on primary winding for voltage variation +5%to -5% steps 2.5%., (D)Neutral on L.V. side, (E) The transformer should be supplied with first filling of oil All removable covers shall be provided with weather proof, hot oil resistant, resistance gasket to prevent leakage of water into core and oil from the tank (Make: Voltech/ CREL or equivalent). | 1 | No | 23,82,950 ₹23.8 L | 23,37,560 ₹23.4 L | 23,25,000 ₹23.3 L |
| 4.00 | Design, Supply, erection, testing and commissioning of 1250A MV panel board suitable for operation on 415 V 3 phase, 50 Hz A.C supply, dust and vermin proof and accommodating the following ACB as Incomer unit with the following items of work complete to satisfy the latest IE rules and CEIG guidelines with Bus bar chambers, Main switches chambers and cable entry chambers.
Bus bar chamber: Supply and fixing of suitable bus bar chamber made up of 16SWG MS sheet steel(1.8mm) with 3” X 1/2” tinned copper bus bar for 3 phases and neutral (75mm x 12mm) and 2 Nos. of earth bus of size 1” X 1/4 tinned copper bus(25mm x 6mm) on suitable bus bar insulator(Epoxy insulator) with maximum creepage distance and supported on MS Base channel frame work of size 18*3*2–1Set
Main Switches Chamber: Incoming (1)Supply and fixing of 1 No. 1250A 4pole Draw out ACB of Microprocessor board EDO Type ( Cat. no:SL96074) basic rating 4 pole 433V LT ACB confirming to IS13947–2 IEC 60947–2 with suitable capacity and breaking capacity of drawout 65 KA breaking capacity with all accessories for standard horizontal manual draw out type ACB equipped with auxiliary contacts and all accessories for closing and opening operation with Microprocessor Based SR 18 G relay, over current trip device adjustable to LTD, STD and release for over current protection UV release with time delay, EF release short circuit protection, Mains CTs for 3 phases lockout, features, separate mold base for each pole for easy maintenance all relevant protection safety accessories as per CEIG, IE rules in force with inter connection and terminations as required in specification, | 1 | Set | 10,75,200 ₹10.8 L | 10,54,720 ₹10.5 L | 10,50,000 ₹10.5 L |
| 4.01Outgoing : (1) Supply and fixing of 630A MCCB —2 Nos, (3) Supply and fixing of 400A TPN Double break switch with HRC Fuse—4 Nos, 4) Supply and fixing of 250A TPN Double break switch with HRC Fuse—4 Nos, Inter connecting the all LT ACB’s and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve color coding of phases and neutral indication. Double Earth connection of the switches and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/4”.Supply and fixing of RYB LED lamp arrangements with toggle switches to control each phases and with rigid connection in suitable separate compartments within the cubicle as per CEIG rules with 1set, supply and fixing Electronic Trivector meter EC,300N class 0.5 flush mounting L&T or equivalent make–ModelER300N. Supply and fixing of danger board with Siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting ,testing and commissioning (L&T,C&S,SIEMENS,ABB) | ||||||
| 5.00 | Design, Supply, erection, testing and commissioning of 630A 4 pole MCCB of Microprocessor board EDO Type panel board suitable for operation on 415 V 3 phase, 50 Hz A.C supply, dust and vermin proof and accommodating the following ACB as Incomer unit with the following items of work complete to satisfy the latest IE rules and CEIG guidelines with Bus bar chambers, Main switches chambers and cable entry chambers.
Bus bar chamber: Supply and fixing of suitable bus bar chamber made up of 16SWG MS sheet steel(1.8mm) with 2” X 1/2” tinned copper bus bar for 3 phases and neutral (50mm x 12mm) and 2 Nos. of earth bus of size 1” X 1/4 tinned copper bus(25mm x 6mm) on suitable bus bar insulator(Epoxy insulator) with maximum creepage distance and supported on MS Base channel frame work of size 10*3*2–1Set.
Main Switches Chamber: Incoming : (1)Supply and fixing of 1 No. 630A 4pole MCCB of Microprocessor board, basic rating 4 pole 433V LT MCCB confirming to IS13947–2 IEC 60947–2 with suitable capacity and breaking capacity of drawout 65 KA breaking capacity with all accessories for standard horizontal manual draw out type ACB equipped with auxiliary contacts and all accessories for closing and opening operation with Microprocessor Based SR 18 G relay, over current trip device adjustable to LTD, STD and release for over current protection UV release with time delay, EF release short circuit protection, Mains CTs for 3 phases lockout, features, separate mold base for each pole for easy maintenance all relevant protection safety accessories as per CEIG, IE rules in force with inter connection and terminations as required in specification | 1 | Set | 4,65,570 ₹4.7 L | 4,56,710 ₹4.6 L | 4,44,510 ₹4.4 L |
| 5.01Outgoing (1) Supply and fixing of 400A TPN Double break switch with HRC Fuse- 3 Nos, (2) Supply and fixing of 250A TPN Double break switch with HRC Fuse—3 Nos, Inter connecting the all LT MCCB and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve color coding of phases and neutral indication. Double Earth connection of the switches and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/4”. Supply and fixing of RYB LED lamp arrangements with toggle switches to control each phases and with rigid connection in suitable separate compartments within the cubicle as per CEIG rules with 1set, supply and fixing Electronic Trivector meter EC,300N class 0.5 flush mounting L&T or equivalent make–ModelER300N. Supply and fixing of danger board with Siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting ,testing and commissioning (L&T,C&S,SIEMENS,ABB) ( Essential Panel ) | ||||||
| 6.00 | Supply and Clamping of 3C x 240 Sq.mm. 11 KV HT XLPE cable in a suitable 6" duro pipe to be excavated at a depth of 0.75 metre and covering the cable completely and refiling the earth to make good.(Make Gloster/Havells/ Polycab). (From 2 Pole Str. to VCB Panel) | 10 | Mtrs | 2,770 ₹27,700 | 2,720 ₹27,200 | 2,640 ₹26,400 |
Tender Value
₹82.2 L
EMD Value
₹52,000
Closing Date
17 Sept 2025, 3:00 pmClosed
SUPERINTENDING ENGINEER
O/o. The SE, PWD Buildings C and M Circle, Vellore
Providing High Tension Lines, Transofrmers, RMG Panel arrangements to the 50 Bedded Critical Care block in Government Hospital at Anaicut in Vellore District
2025_PWD_603169_1
16/VLR-CLE/25-26-5/26.08.2025
Open Tender
Electrical Works
90 days
ANAICUT IN VELLORE DISTRICT
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹52,000
5 Mar 2026
12 Sept 2025
17 Sept 2025
12 Sept 2025
17 Sept 2025
12 Sept 2025
Amount
6. TP ND IDMT 2OC + 1 EF Relay similar like Megawin type MCDG 31 Master trip Relay Megawin MVAJH 13 (Incom-1No & Out-1 No) 7. Breaker ON/OFF/Auto Trip/Healthy/Spring Charged Indication Lamp LED Type, 8. Phase Indication Lamps R,Y,B(Incomings 3Nos), 9. Control Wiring, 10. 630Amps Copper Bus bar PVC Sleeved and required panel copper earthing, 11. Control switch TNC, 12.Trip Circuit healthy Push Button(Incoming-1 No, Outgoing -1No), 13. Common for Switch gear, MCB's for AC DC Control, Heater ON/OFF Switch with space Heater and thermostat Single phase switch socket, cubicle illumination lamp, Disconnecting type terminal Block.etc., 14. MS Sheet enclosure for Indoor Installations Powder.
Type OLTC Transformer: Supply, erection, testing and Commissioning of 630 KVA 22KV/ 433V,copper wound ON (OLTC) load tap changing copper wound Indoor type distribution transformer OLTC type of cooling conforming to relevant IS 1180- Level 2 and fitted with the following and standard accessories. (A) HV cable end box suitable for connecting 3 core 300 sq.mm11KVXLPE HT cable., (B) LT Cable end box suitable for connection 4 runs of 3 ½ x 300 sq.mm LTUG cables., (C) Tapping on primary winding for voltage variation +5%to -5% steps 2.5%., (D)Neutral on L.V. side, (E) The transformer should be supplied with first filling of oil All removable covers shall be provided with weather proof, hot oil resistant, resistance gasket to prevent leakage of water into core and oil from the tank (Make: Voltech/ CREL or equivalent).
Design, Supply, erection, testing and commissioning of 1250A MV panel board suitable for operation on 415 V 3 phase, 50 Hz A.C supply, dust and vermin proof and accommodating the following ACB as Incomer unit with the following items of work complete to satisfy the latest IE rules and CEIG guidelines with Bus bar chambers, Main switches chambers and cable entry chambers. Bus bar chamber: Supply and fixing of suitable bus bar chamber made up of 16SWG MS sheet steel(1.8mm) with 3” X 1/2” tinned copper bus bar for 3 phases and neutral (75mm x 12mm) and 2 Nos. of earth bus of size 1” X 1/4 tinned copper bus(25mm x 6mm) on suitable bus bar insulator(Epoxy insulator) with maximum creepage distance and supported on MS Base channel frame work of size 18*3*2–1Set Main Switches Chamber: Incoming (1)Supply and fixing of 1 No. 1250A 4pole Draw out ACB of Microprocessor board EDO Type ( Cat. no:SL96074) basic rating 4 pole 433V LT ACB confirming to IS13947–2 IEC 60947–2 with suitable capacity and breaking capacity of drawout 65 KA breaking capacity with all accessories for standard horizontal manual draw out type ACB equipped with auxiliary contacts and all accessories for closing and opening operation with Microprocessor Based SR 18 G relay, over current trip device adjustable to LTD, STD and release for over current protection UV release with time delay, EF release short circuit protection, Mains CTs for 3 phases lockout, features, separate mold base for each pole for easy maintenance all relevant protection safety accessories as per CEIG, IE rules in force with inter connection and terminations as required in specification,
Outgoing : (1) Supply and fixing of 630A MCCB —2 Nos, (3) Supply and fixing of 400A TPN Double break switch with HRC Fuse—4 Nos, 4) Supply and fixing of 250A TPN Double break switch with HRC Fuse—4 Nos, Inter connecting the all LT ACB’s and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve color coding of phases and neutral indication. Double Earth connection of the switches and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/4”.Supply and fixing of RYB LED lamp arrangements with toggle switches to control each phases and with rigid connection in suitable separate compartments within the cubicle as per CEIG rules with 1set, supply and fixing Electronic Trivector meter EC,300N class 0.5 flush mounting L&T or equivalent make–ModelER300N. Supply and fixing of danger board with Siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting ,testing and commissioning (L&T,C&S,SIEMENS,ABB)
Design, Supply, erection, testing and commissioning of 630A 4 pole MCCB of Microprocessor board EDO Type panel board suitable for operation on 415 V 3 phase, 50 Hz A.C supply, dust and vermin proof and accommodating the following ACB as Incomer unit with the following items of work complete to satisfy the latest IE rules and CEIG guidelines with Bus bar chambers, Main switches chambers and cable entry chambers. Bus bar chamber: Supply and fixing of suitable bus bar chamber made up of 16SWG MS sheet steel(1.8mm) with 2” X 1/2” tinned copper bus bar for 3 phases and neutral (50mm x 12mm) and 2 Nos. of earth bus of size 1” X 1/4 tinned copper bus(25mm x 6mm) on suitable bus bar insulator(Epoxy insulator) with maximum creepage distance and supported on MS Base channel frame work of size 10*3*2–1Set. Main Switches Chamber: Incoming : (1)Supply and fixing of 1 No. 630A 4pole MCCB of Microprocessor board, basic rating 4 pole 433V LT MCCB confirming to IS13947–2 IEC 60947–2 with suitable capacity and breaking capacity of drawout 65 KA breaking capacity with all accessories for standard horizontal manual draw out type ACB equipped with auxiliary contacts and all accessories for closing and opening operation with Microprocessor Based SR 18 G relay, over current trip device adjustable to LTD, STD and release for over current protection UV release with time delay, EF release short circuit protection, Mains CTs for 3 phases lockout, features, separate mold base for each pole for easy maintenance all relevant protection safety accessories as per CEIG, IE rules in force with inter connection and terminations as required in specification
Outgoing (1) Supply and fixing of 400A TPN Double break switch with HRC Fuse- 3 Nos, (2) Supply and fixing of 250A TPN Double break switch with HRC Fuse—3 Nos, Inter connecting the all LT MCCB and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve color coding of phases and neutral indication. Double Earth connection of the switches and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/4”. Supply and fixing of RYB LED lamp arrangements with toggle switches to control each phases and with rigid connection in suitable separate compartments within the cubicle as per CEIG rules with 1set, supply and fixing Electronic Trivector meter EC,300N class 0.5 flush mounting L&T or equivalent make–ModelER300N. Supply and fixing of danger board with Siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting ,testing and commissioning (L&T,C&S,SIEMENS,ABB) ( Essential Panel )
Supply and Clamping of 3C x 240 Sq.mm. 11 KV HT XLPE cable in a suitable 6" duro pipe to be excavated at a depth of 0.75 metre and covering the cable completely and refiling the earth to make good.(Make Gloster/Havells/ Polycab). (From 2 Pole Str. to VCB Panel)
Supply and Laying of 3C x 240 Sq.mm. 11 KV HT XLPE PVC cable with aluminium conductors on wall with MS clamp with necessary supports or in a existing trench including removing and relaying the cement slab. (From VCB To Tr. 1) (Make Gloster/Havells/ Polycab)
Supply and Providing cable end termination for 11KV 3 core 240 Sqmm XLPE HTUG cable with necessary Indoor type heat shrinkable joint kit and accessories (Make: Raychem or Equivalent)
Supply and Providing cable end termination for 11KV 3 core 240 Sqmm XLPE HTUG cable with necessary Outdoor type heat shrinkable joint kit and accessories (Make: Raychem or Equivalent)
Supply and laying of 4 runs of 31/2 x 300 sqmm size of PVC armoured LTUG cable in a trench tobe excavated at a depth of 0.75 Mtr. And puttin 0.15 mtr. layer of sand and covering the cable completely with concrete trough and sand and refilling the earth to make good. (From transformer to MV panel)
Supply and clamping of 4 runs of 31/2 x 300 sqmm of PVC armoured LTUG cable on post on wall with MS clamp.
Supply and Fixing brass cable gland for 31/2 x 120 Sq.mm PVC armoured LTUG cable with earth connection
Supply and providing cable end termination of 3 1/2 x 240 sqmm PVC LTUG Aluminum armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection
Supply and run of 1" x 1/8" (25mmx3mm) tinned copper flat with necessary clamps/supports on all / floor/ ground for earth connection.
Supply and run of 1" x 1/4" (25mmx6mm)copper flat for earth connection.
Supply and run of 1 of No. 8 SWG hard drawn copper conductor for earth connection.
Supply and insallation maintenance free GI Earthing System comprising of 50mm dia and 2 mtr. long earth electrode of low carbon steel rod with 100 micron bonding and 25 kgs. of carbon based environment friendly backfill compound and suitable clamp.
Supply and erection of 175 KVAR 415/440Volts 50Hz 3 Ph automatic power factor correction panel, 8 stage, (at 0.95 lag), made up of powder coated, 14/16 SWG CRCA sheet steel enclosure with 1 1/2" x 1 1 1/2" x 1/2" AI Frame work with RCC concreting foundation and bolted to masonry pedestal with 400A triple pole MCCB as incoming (L&T/Siemens/C&S) with Delta Connected capacitors (BCH/EPCOS) MOO Type operating in multiple stage with 3 current and Voltage Transducers (CVT) at the phases simultaneously to activate the desired power factor switching time between steps 120 seconds, switching off time in case of fault 3 seconds with a LCD display to show the following Parameters. (A)Vr – R phase Line Voltage, (B)Vy – Y phase Line Voltage, (C)Vb – B phase Line Voltage, (D)Ir – R phase Line current, (E)Iy – Y phase line current, (F)Ib – B phase Line Current, (G)KW – Present Kilo Watts, (H)RKVA – Present KVAR Demand, (I)KVA – Present KVA,. (j)PF – Present Power Factor, (K)Number of Capacitor bank ON/OFF, (L)Provision to indicate the imbalanced load, Provision to indicate the change in phase Sequence The APFC Panel Should also with built in protection For high Voltage/Low Voltage cut off, single phase Preventer in current line surge line surges, Current Limiters, Current Sensor, etc., with connection complete and as per the relevant IE Rules. Eight Stages of Automatic Power Factor control panel is necessary connection.
Provision towards preparation of site plan, physical layout, electrical line schematic diagram HT side ,5 sets getting drawing approval from C E I G authority (Measures safety to electricity) regulation, preparation of completion report ,Rectification report, preparation of one set approved drawing and copy of safety certificate in a neat frame work and payment of CEIG 's inspection fees including supporting staff for availing service connection.
R BALAMURUGAN (BID ID -1461052)
SURESHBABU (BID ID -1461168)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid