Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 CrAccepted-AOC | ₹5.0 Cr | L1 | Accepted-AOC Lowest |
| 2 | L2₹5.5 Cr+₹50.3 L (10.1%)Rejected-Finance | ₹5.5 Cr+₹50.3 L (10.1%) | L2 | Rejected-Finance Other than lowest |
| 3 | L3₹5.9 Cr+₹92.8 L (18.6%)Rejected-Finance | ₹5.9 Cr+₹92.8 L (18.6%) | L3 | Rejected-Finance Other than lowest |
| 4 | L4₹6.6 Cr+₹1.6 Cr (32.6%)Rejected-Finance | ₹6.6 Cr+₹1.6 Cr (32.6%) | L4 | Rejected-Finance Other than lowest |
Tender Value
₹4.5 Cr
EMD Value
₹5.2 L
Closing Date
4 Nov 2024, 6:00 pmClosed
Chief Engineer Udhampur Zone
HQ Chief Engineer Udhampur Zone, PIN-900386, C/O 56 APO
PROVN OF OTM ACCN AT TANDA UNDER GE (N) AKHNOOR
2024_MES_669977_1
87938-A/E8
Open Tender
Civil Works
Lump-sum
485 days
Akhnoor
As per NIT
8 documents required · 8 mandatory
₹2,000
GE (N) Akhnoor
₹5.2 L
Yes
11 Jan 2025
2 Sept 2024
11 Nov 2024
2 Sept 2024
4 Nov 2024
22 Oct 2024
Amount
Sch 'A' Part - I (Building Work):-This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Construction of block of OR Institute, unit shop, tradesmen shop, family welfare centre & education building, complete all as shown on drawings and as specified.
Construction of block of mechanical laundry, drying and ironing building, complete all as shown on drawings and as specified.
Construction of block of religious institute building, complete all as shown on drawings and as specified.
Construction of block of bird watcher hut, complete all as shown on drawings and as specified.
Construction of block of mission planning building, complete all as shown on drawings and as specified.
Total Amount of Sch 'A' Part - II (Site Clearance)
Total Amount of Sch 'A' Part - III (Internal Water Supply)
Total Amount of Sch 'A' Part - IV (Internal Electric Supply)
Total Amount of Sch 'A' Part - V (Plumbing Work)
Total Amount of Sch 'A' -VI (Area Drainage Work)
Total Amount of Sch 'A' -VII ( Sewage Disposal Work)
Total Amount of Sch 'A' Part -VIII (Road, Path and Culvert)
Total Amount of Sch 'A' Part -IX (External Water Supply)
Total Amount of Sch 'A' Part -X (External Electric Supply)
Total Amount of Sch 'A' Part -XI (Rain Water Harvesting)
Total Amount of Sch 'A' Part -XII (Incinerators & Refuse bin Work)
Total Amount of Sch 'A' Part -XIII (Play Ground Works (Football Ground, Basket Ball Ground, Volley Ball Ground, Hockey Ground, Badminton Court and Tennis Court)
Sch 'A' Part - XIV (Misc Items of work) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Construction of septic tank for 100 users (Brick construction) complete all as shown on drawing and as specified.
Construction of soakage well (Brick construction) 1.80m dia and 3m deep, below inlet pipe level (depth from inlet pipe to ground level 45cm) complete all as shown on drawing and as specified.
LLDPE septic tank designed to carry sewage and sludge water, comprising earth work , excavation, returning filling, disposal of surplus spoils to a distance not exceeding 50 mtr from starting point in any type of soil, PCC 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) in foundation, 200mm thick, vent shaft, connections etc. For 20 users including all fittings, fixtures, testing on completion complete all as specified.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level connected with galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15 type B1 in pit with angle iron (25x25x3)mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle, test point etc. in and including light grade GI protection pipe 40mm bore up to 5m length for drawing in earth lead wire, all as shown in electric plate No. 3 of SSR Part-I complete with necessary earth work in any type of soil, removal to a distance not exceeding 50m, testing on completion complete all as specified and directed.
Supply, installation, testing and commissioning split type air conditioning unit, 5 star, eco friendly refrigerant complete with drive motor, air cooled copper condenser with all accessories varied speed and dual rotary compressor, including fixing the out door units as per manufacture recommendation and fixing of room unit on wall , providing and making interconnection , including refrigerant piping with nitrile rubber insulation and control cable from indoor to out door, first charging of refrigerant gas including cordless remote, capacity 1.5 TR all as specified and as directed . Make: Blue star / Samsung / Whirlpool/ LG/ Voltas.
Mounting bracket for Split AC Heavy Duty Air Conditioner Outdoor Unit suitable for 1.5 Ton AC, made Up of heavy duty GI steel, wall mounted type, Powder coated including nuts & bolt etc. all as specified and directed.
AC outlet PVC drain water pipe, 5 mtr length, connecting to nearest drain lines complete all as specified and directed.
3 Core wire 2.5 Sqmm round Copper Cable (ISI Mark), heavy duty for AC, 3 mtr length complete all as directed.
Voltage stabilizer 3KVA capacity, wall mounted for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5%, complete all as specified and directed.
Sheet metal enclosures (double door) vertical double door TPN fitted with bus bar neutral link, blanking plates of 4 way (4+12) suitable for incoming MCB TPN having isolated neutral bar, mechanical impact strength IK09, door earthing complete all as specified and as directed.
MCB, TPN 40 Amps, 415 V, 10KA complete all as specified and directed.
MCB SP 6 to 32 amp rating 240V, 10KA 'C' curve, complete all as specified and directed.
Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps, complete all as specified and directed.
Sub main wiring with two run of FRLSH PVC insulated unsheathed flexible copper conductor (Multistrands), single core of size 4 Sqmm, 1100 Volts grade and one run of 4 Sqmm FRLSH PVC insulated unsheathed as earth (In green Colour), flexible copper conductor (Multistrands) for continuous earthing conforming to IS 694 with latest amendments and drawing in PVC rigid conduit 25mm dia, connecting incoming / outgoing electric connections by using required size copper lugs / thimbles and making good the disturbed surface to match with existing complete in all respect all as specified and directed. Note :- Two run of single core cable with one run of continuous earth wire of copper conductor wire Flexible (Multistrand) of FRLSH PVC insulated and 25 mm PVC conduit shall be measured and paid as one unit length.
Sub main wiring with four run of FRLSH PVC insulated unsheathed flexible copper conductor (Multistrands), single core of size 6 Sqmm, 1100 Volts grade and two run of 6 Sqmm FRLSH PVC insulated unsheathed as earth (In green Colour), flexible copper conductor (Multistrands) for continuous earthing conforming to IS 694 with latest amendments and drawing in PVC rigid conduit 25mm dia, connecting incoming / outgoing electric connections by using required size copper lugs / thimbles and making good the disturbed surface to match with existing complete in all respect all as specified and directed. Note :- Four run of single core cable with two run of continuous earth wire of copper conductor wire Flexible (Multistrand) of FRLSH PVC insulated and 25 mm PVC conduit shall be measured and paid as one unit length.
Water cooler electric driven (single phase), having approx. storage capacity of 80 litre and nominal cooling capacity of 40 Litres per hour, complete all as directed.
Water cooler electric driven (single phase), having approx. storage capacity of 120 litre and nominal cooling capacity of 60 Litres per hour, complete all as directed.
Voltage stabilizer of capacity 1KVA for automatic operation, single phase, naturally air cooled, indoor type and designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of + 2.5%, complete all as directed.
Point wiring with 2.5 sq mm single core PVC insulated and unsheathed FRLSH cable, 1100 volts grade IS -694 marked with multistandard copper conductors and earth continuity wire with similar 2.5 sqmm cable (including connecting to earth dolly) drawn through and including rigid PVC conduit suitable size and conduit accessories concealed in wall by cutting grooves except on ceiling and panel in suitable way with clamps screw etc. with and including concealed/surface modular box suitable for logic modular switches, sockets, etc. and including logic modular white frame with cover plates of suitable size as required at site for complete all as specified and directed
Front loading washing machine with loading Capacity of 30 Kg. dry weight per charge, electrically heated, heavy duty, inner basket & outer drum stainless steel, dully painted all M.S fabricated area ,latest safety feature (machine stops automatically while opening the door through limit switch, micro controller base cyclic timer for auto-reserve, auto-timed & auto digital temperature control, water-inlet valve, drain valve, complete with control panel, & electric motor for wash 1.5 KW and wash speed 35-40 Rpm, driven through pulleys & V belts and control panel, operates on 3Ph, 415V, 50Hz. A.C. supply, operation cycle 30 to 40 minutes and door S.S sheet fitted with toughened glass, complete all as directed.
Hydro extractor machine direct-drive, self-balancing, with automatic electromagnetic DC injection brake system having capacity of 30Kg. Per charge with auto-timed, top loading, vibration less, inner basket and outer drum stainless steel complete with specially designed electric motor 3.75KW and control panel operates on 415 V, 3 phase, 50 Hz AC supply, operation cycle 5 to 10 minutes, dully painted all M.S fabricated area, latest safety feature (machine stops automatically while opening the door through limit switch, complete all as directed.
Drying tumbler machine front loading, open pocket, electrically heated with loading capacity of 30 Kg. per charge, complete with micro controller base cyclic timer for auto timed & auto-reserve, auto digital temperature control, fitted with control panel, one motor each for drive and blower 0.75 KW. double walled glass wool insulated outer body front, back & side with M .S Sheet with inner basket stainless steel, self lint screen, ‘V’ belt drive, waste air exhaust etc.; operates on 415 V, 3 phase, 50 Hz AC supply. operation cycle 40 to 60 minutes, door S.S Sheet fitted with toughened glass, dully painted all M.S fabricated area, latest safety feature (machine stops automatically while opening the door through limit switch, complete all as specified and as directed.
Vacuum finishing table with steam iron table size- 1200mm x 750mm and suitable automatic steam generator, (2 No. Table + 2 No. steam press + steam generator 1 No.) with feature like large flattop padded with silicon padding, strong welded construction therostatically controlled stainless steel table heater, extended exhaust duct with lightening device, adjustable garment hanger stand with rack, power suction through centrifugal blower activated by spring full length foot pedal working in conjunction with sturdy micro switch and Silicon iron stand protects ironing and teflon soles with stand upto 150 degree temperature, complete all as specified and as directed.
Supply, Install, Testing and commissioning LT distribution board (Outdoor Type) suitable size, CPRI Approved factory made, Single door, Cubical type, Compartmentalized design, back door, openable, fabricated out of 3.15 mm thick CRCA steel sheet, weather / dust / vermin proof, suitable spaced totally enclosed in chamber, earthing arrangement, locking arrangement with one no lock with duplicate key duly painted with powder coated paint having danger notice boards and earthing terminals on both sides and including providing the following items including connection of all incoming and outgoing cables using suitable size lugs and glands, Spreader terminal set, control wiring, panel to be mounted on cable trench if required with base channels as required and suitable foundation of panel with PCC 1:2:4 complete in all respect all as specified & directed by Engineer-in-charge including comprising of following items :- ( Mechanical Laundry)
PVC insulated & FRLSH three core cable, copper conductor 1.5 sqmm, for connection from junction box to LED flood light complete all as specified and as directed.
20mm dia steel conduit (heavy duty) for protection of copper cable with suitable clamp complete all as specified and as directed.
Supply, Install, Testing and commissioning LT distribution board (Outdoor Type) suitable size, CPRI Approved factory made, Single door, Cubical type, Compartmentalized design, back door, openable, fabricated out of 3 mm thick CRCA steel sheet, weather / dust / vermin proof, suitable spaced totally enclosed in chamber, earthing arrangement, locking arrangement with one no lock with duplicate key duly painted with powder coated paint having danger notice boards and earthing terminals on both sides and including providing the following items including connection of all incoming and outgoing cables using suitable size lugs and glands, Spreader terminal set, control wiring, panel to be mounted on cable trench if required with base channels as required and suitable foundation of panel with PCC 1:2:4 complete in all respect all as specified & directed by Engineer-in-charge including comprising of following:- (for OR Institute, Drying and Ironing Room, Mechanical Laundry, Education Bldg.)
Supply, Install, Testing and commissioning LT distribution board (Outdoor Type) suitable size, CPRI Approved factory made, Single door, Cubical type, Compartmentalized design, back door, openable, fabricated out of 3mm thick CRCA steel sheet, weather / dust / vermin proof, suitable spaced totally enclosed in chamber, earthing arrangement, locking arrangement with one no lock with duplicate key duly painted with powder coated paint having danger notice boards and earthing terminals on both sides and including providing the following items including connection of all incoming and outgoing cables using suitable size lugs and glands, Spreader terminal set, control wiring, panel to be mounted on cable trench if required with base channels as required and suitable foundation of panel with PCC 1:2:4 complete in all respect all as specified & directed by Engineer-in-charge including comprising of following items :- (for Unit Shop, Tradesman Shop, Family Welfare Centre, Basket Ball Ground 1 & 2)
Junction box water proof outdoor type made out of SMC of external dimensions (295x255x120)mm, single door type, hinged with locking arrangement front operated with one number MCB 16 Amps capacity for housing single phase and neutral including connecting the incoming/outgoing cables including cable glands SMC coated clamps bolts etc. and making cable connection with cable termination lungs (thimble) all as directed and fixed to the existing poles with mild steel flat of size 25mmx4mm complete all as directed. Make: Sintex Cat GSJB 2520 or equivalent make as approved by GE.
Supply, installation, testing and commissioning of 100 KVA 0.8 PF of corresponding 80 KW diesel engine driven Generating set with alternator out put Voltage 415 Volts +/- 1% at set value of 415 V at a frequency 50HZ +/- 0.5% with suitable standard control panel, all mounted in acoustic enclosure with AMF panel as per manufacturers design and specification as per latest approved CPCB-04 + norms confirming to the detailed specifications appended below:- Make of OEM: Cummins GENSET model No Model QSM15-G1 or equivalent in Kirloskar / Stamford /Sudhir / Jackson.
ENGINE (a) General: Suitable four stroke compressed ignition, radiator water cooled, Turbocharged aspiration, continuous duty with 10% overload capacity for any one hour in 12 hours running, 50°C intake air temperature, CPCB-04 approved Engine developing minimum power to generate 80 KW operation at alternator at 1500 RPM coupled to alternator mounted on Channel Iron base frame with in built removable fuel tank of capacity not less than 12 Hrs consumption capacity at 75% load or more as per manufactures recommendation. The prime mover provided should be as per IS specifications having engine overload protection. (b) Air intake system : Should comprise of dry type intake air filter mounted on engine, one in number vacuum indicator mounted on intake piping.
(c) Exhaust System: Should comprise of one exhaust manifold, dry type, mounted on engine, one exhaust silencer which should be positioned in such a way that the exhaust gas is not sucked by the fan on the radiator, thereby affecting the cooling system. The silencer should cater to the noise level tolerance prescribed in the relevant BS/IS. The silencer should be provided with flaps it will open only when the generator is running. The complete exhaust system shall be properly supported so that entire load of the exhaust system shall not fall on the DG Set. (d) Fuel System: Should comprise of disposal type element fuel filter, pressure type fuel pump mounted on engine, non return check valve in fuel supply and drain lines, wire braided hose between filter and pump, fuel system with suitable capacity full authority electronic engine electronic governor and engine mounted actuator. The fuel tank must have proper locking arrangement with level indicator and to be integrated with base frame.
(e) Cooling System: Should comprise of radiator designed and tested for 50o C ambient temperature with 7 PSI pressure cap mounted on base rail. The thermostat installed in the engine coolant outlet, fresh water pump mounted on engine, fan and fan hub mounted on engine. A reservoir of 50% of radiator capacity to replenish coolant by gravity (as and when required) is also to be provided. (f) Lubricating System: Should comprise of lubricating oil sump mounted on engine, gear driven lub oil pump mounted on engine, lubricating oil cooler-fresh water cooled integral with engine cool out circuit mounted on engine, oil filter lubricating with cap and lubricating oil dip stick for oil level check mounted on engine. The system should be capable of feeding lube oil to the main end & large end bearings, cam shaft, valve rocker gear and all moving parts.
(g) Starting System: Should comprise of suitable voltage DC electrical self starter mounted on engine, with suitable maintenance free batteries -2 Nos 2 Nos. 25 Plate, 180 Amps, 12 Volts Battery with one set of connecting leads of 75 sq mm Size Copper Cable to be mounted in trays (having rubber insulation) on the main frame or the capacity as per specification of manufacturer. It should have the provision to charge the battery from external sources during static condition and while running of the generator. (h) AC Generator : The generator shall be horizontal and foot mounted, minimum 100 KVA, 415 Volts, 3 phase, 4 wire, 0.8 PF, 50 HZ, separately excited, self regulated, brushless AC generator, suitable for an ambient temperature of 50° C with IP-23 enclosure class H insulation and temperature rise limited to class H as per following technical details (i) Type : Brush less AC Generators (ii) Output rating minimum : 100KVA at 0.8 PF lagging
(iii) Output Voltage: 415 ± 1% under all loading conditions. (iv) Output frequency : 50Hz ±0.5% up to 0.8 lagging. (v) No of Phases: 3 phase with 01 Neutral (4 wire) (vi) Mounting : Horizontal foot mounted. (vii) Enclosure : Minimum IP-23 / Drip proof and screen protected. (viii) Automatic voltage regulator. (ix) Class of insulation-'H' (x) AREP excitation system Make: Cummins / KIRLOSKAR GREEN / Stamford / Leroy-Somer or as recommended by OEM. (j) BASE FRAME: MS Chanel fabricated frame of suitable size rigedly welded as recommended by the manufacturer should be suitable to mount the engine, alternator, radiator and anti-vibration pads.
(k) CONTROL PANEL: (i) Control panel shall be indoor type manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish consisting of microprocessor power command controller, Aluminium bus bars with suitable capacity with incoming/outgoing terminals, indicating lamps for 'Load ON' and 'Set Running', instrument fuses duly wired and ferruled, MCCB of suitable rating with overload and short circuit protections etc. complete all as specified and directed.
(ii) Standard Auto Mains Failure panel suitable to activate the DG set automatically on power failure shall be provided with necessary accessories like switchgears, meters and other accessories. The panel shall be designed for manual operation if required. The control panel shall consist of all the controls of the alternator as required and recommended by standard codes of practice and shall be originally manufactured along with the alternator, floor mounted, cubical type with LT switch board and complete with internal wiring. Suitable arrangement shall be made for joining incoming cable and for connecting the bus duct on the outgoing side. This shall be dust/ vermin proof.
(o) Internal Lighting: Tube lights with protective mesh around it to be fitted inside the container for proper illumination. (p) Doors : The enclosure will be provided with suitable doors on the side and rear to enter the enclosure during operation and maintenance. All doors will be provided with lock and handles for opening/ closing the doors, retainers for holding the panel door. (q) Painting Scheme Superlative fade resistant paint can last longer in through whether conditions (r) Lifting/ Transportation arrangements:- Container with suitable corners will be provided to lift the DG set along with container. This is suitable for road/ rail/ sea transportation. (s) Trials:- Trials on site should be given as per load tests prescribed and all functional trials should be shown. (t) PCC Foundation for DG set size as per manufacture instruction and as directed by the GE.
ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 200 Amps (For ADM Bldg.) with the following: (i) Adapted to environments subject to chemical, dust, contamination and atmospheric corrosion risks. (ii) CRCA sheet (Door 1.2mm, Body 1.6mm). (iii) Wall mounted with 4 bolts. (iv) 2 external earthing point on each side. (v) Door locking system allows opening of door only in off position. (vi) Incoming & outgoing easily interchangeable at site. (vii) Removable plate top & bottom. (viii) Coating of expoy polyester powder 70 micron.
Brick masonry valve pit of size 60cmx60cmx60cm (internal dimensions) including excavation and earthwork in any type of soil, plastering all wall surfaces internally and flush pointing to brickwork externally as the work proceeds complete including angle iron 50x50x6mm frame, MS sheet cover 3.15mm thick with 12mm dia handle, locking arrangement and painting with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer, complete, all as shown on drawing as specified.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level connected with galvanized iron earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 15mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15 type B1 in pit with angle iron (25x25x3)mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle, test point etc. in and including light grade GI protection pipe 15mm bore up to 5m length for drawing in earth lead wire, all as shown in electric plate No. 3 of SSR Part-I complete with necessary earth work in any type of soil, removal to a distance not exc. 50m, testing on completion complete all as specified & directed.
DWC HDPE pipe 50mm inner dia (double wall corrugated) confirming to IS: 14930 (part-II) alongwith necessary snap fit coupler for interconnection suitable for HT/LT cable complete all as specified and directed.
LED flood light, 120 watt, 230 V, AC, outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver, lamp and fitting and fixture complete all as specified and directed.
LED lamp retrofit type 12 watt B22 base holder with polycarbonate body and heat sink type, complete all as specified and as directed.
Light fitting 10 Watt, 220 Volts, bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
LED light fitting mirror type with high out put diffuser 2 feet, 10 watt, 220 V, general purpose surface and wall mounted LED batten with aluminium housing intergrated electric driver including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and as directed.
LED light fitting 20 Watt, 220 Volts, 50 Hz (4 feet length) general purpose surface and wall mounted LED batten with aluminium housing integrated electronic driver complete connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, complete all as specified and as directed.
Exhaust fan, steel body AC single phase, 230V of size 450mm sweep heavy duty, with blades and frame and louvers, complete all as specified and as directed.
Exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200 copper winding of sweep 250mm, complete all as specified and as directed.
Ceiling fans complete with blades, down rods, modular type electronic regulator 2 module, 120 Watt, suitable for BLDC fan and accessories, 230V, 1200mm sweep. Min air delivery 210 CFM with service value 6.00 BEE, five star rated with brushless direct current motor (BLDC) complete all as specified and as directed
Trial bore of 300mm dia upto 200m depth below ground level in any kind of soil strata including hard stone/boulder including electric logging, MS cap, MS flat iron clamps, reducing socket etc., complete all as specified and directed.
Concealed sub main wiring with two runs of 6 Sqmm (2x6 sqmm) 1100 volts grade single core FRLSH PVC insulated unsheathed multistranded copper conductor confirming to IS-694 drawn through and including non-metalic PVC rigid conduit 20mm dia ISI marked with all conduit accessories mounting on surface of walls /roofs / ceiling including cutting chasing and with one run of 6 Sqmm (1x6)sqmm single core FRLSH PVC insulated unsheathed copper conductor cable as earth wire, complete all as specified and directed. Note: Two run of 6 Sqmm single core copper conductor cable and one run of 6 Sqmm single core copper conductor cable as earth continuity and one run of PVC conduit shall be measured as one unit.
Point wiring complete with 1.5 sqmm PVC insulated, FRLSH type, unsheathed, multistranded, flexible copper conductor cable 1.5 Sqmm 1100 volts grade, drawn through and including concealed PVC conduit, medium grade of size 20mm or above as required at site with all accessories such as tee, corner, overlapping connector etc.; on surface walls, roots and ceiling etc.; including modular steel terminal boxes of required size alongwith modular white cover plate with frame for mounting modular switches, socket, fan regulators etc.; and including 1.5 Sqmm PVC insulated, multistranded, unsheathed (greed colour), FRLSH type single core, copper conductor cable as earth continuity conductor and connecting to common earth dolly for the followings:
One light point/fan point/exhaust fan point/bell point controlled by one switch.
One 3 pin, 5 Amps socket point controlled by one 6 Amps switch on independent board.
One 3 pin, 5 Amps socket point controlled by one 6 Amps switch on same board.
One light point controlled by two way switch
Supply, installation, commissioning and testing polycarbonate CPRI approved OEM made meter panel. The panel shall be made of modular polycarbonate thermoplastic enclosures which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4 meter panel type wall mounted type on mounted structure RAL 7016. The meter panel should be anti-acid, anticorrosive & fully transparent door for meter vision. Degree of protection against mechanical load should be IK 08 (5 Joule) in accordance with IEC 62262. The manufacture of panel shall submit a copy of his CPRI Test report in polycarbonate only also share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. Degree of ingress protection IP 65 in accordance with IEC 60529. The gasket should be internally embedded made of polyurethane and enclosures The manufacturer of panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1.
The CRPI report shall have mention of following tests performed and passed out satisfactorily temperature rise dielectric properties, short circuit withstand current-rated peak, short time withstand current and rated conditional short circuit current, effectiveness of protective circuits and submit the copy of type test reports for polycarbonate thermoplastic board only. Test report submitted of other material of construction like MS, SS will not be applicable. Each board shall have individual routine test report of the manufacture. The panel should passed glow wire test 960 degree centigrade in accordance with 60695-2-11 (flame retardant and self-extinguishing) one main incomer MCCB 125A TP 25 KA thermal/magnetic release with spreader link MCCB/MCB Nos operated by flip cover. Indicator provided on each phase 8 No, single phase sub-meters. Output supply by MCB DP 32AMP 8 No. Meter enclosures & enclosures accessories as per RAL 7035. 10 No. terminal blocks provided for output supply, complete all as specified and directed. Make: Hensel/Clipsal or other equivalent make as approved by the GE.
Coaxial cable for TV and telephone socket outlet complete all as specified and directed.
Telephone socket outlet complete all as specified and directed
TV socket outlet complete all as specified and directed
PVC conduit 25mm dia for TV and telephone socket outlet complete all as specified and directed.
mohan lal gupta sons (BID ID -3152110)
R R CONSTRUCTION (BID ID -3153686)
M/S KAPIL KUMAR KHATTAR (BID ID -3157299)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tenderdocument.pdf
Tender Documents • 4.64 MB
Tenderdocument_2.pdf
Tender Documents • 2.02 MB
Tenderdocument_3.pdf
Tender Documents • 0.19 MB
Tenderdocument_4.pdf
Tender Documents • 3.47 MB
Tenderdocument_5.pdf
Tender Documents • 1.77 MB
BOQ.xls
BOQ • 0.57 MB
Tenderdocument_6.pdf
Tender Documents • 3.85 MB
Tenderdocument_7.pdf
Tender Documents • 9.19 MB
Tenderdocument_8.pdf
Tender Documents • 2.72 MB
Tenderdocument_9.pdf
Tender Documents • 2.72 MB
Tenderdocument_10.pdf
Tender Documents • 36.39 MB
Tenderdocument_11.pdf
Tender Documents • 1.13 MB
Tenderdocument_12.pdf
Tender Documents • 35.69 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .