Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.9 LAccepted-Finance 150 VILLARASAMPATTI NAAL ROAD NASIYANUR ROAD ERODE 638 107 | ERODE | ERODE | TAMIL NADU | 638107 | L1 | Accepted-Finance L1 bidder | |
| 2 | Rejected-Technical SALEM | SALEM | - | Rejected-Technical BQR Not satisfied |
Tender Value
Refer Docs
EMD Value
₹17,700
Closing Date
3 Jan 2025, 2:00 pmClosed
SEES NCTPS-II
OFFICE OF SEES NCTPSII
Sp.77 NCTPS II ES circle EM II Division Sub division I Overhauling VPI of 11KV 4000W 239A 1494 RPM Primary Air Fan Motor 48266A421 81 01 including machining of NDE side rotor shaft and fabrication of labyrinth seal to match with rotor shaft new
2024_EB_511936_1
CE NCTPS II SE ES EM II SPEC NO 77 24 to25
Open Tender
Electrical and Maintenance Works
Works
60 days
NCTPS-II
AS PER TENDER SPECIFICATION
2 documents required · 2 mandatory
₹0
₹17,700
Yes
15 Jul 2025
19 Dec 2024
4 Jan 2025
19 Dec 2024
3 Jan 2025
19 Dec 2024
Amount
Unloading of Motor and Dismantling 4000KW PA fan Motor by removing the silencer, fan cover, fan and Bearing pedestals, threading out the rotor
Preliminary inspection on Stator, rotor and other spares in presence of TANGEDCO Engineers. STATOR: Conducting the Electrical tests to find out the healthiness of stator winding (IR value, WR value and Surge comparison test), Visual inspection on the winding to find out any looseness of coils, top wedges PD symptoms, Checking condition of take-off leads, Checking Condition of terminal insulators and spares, Checking RTD, BTD and Heater terminals, Checking condition of RTD, Checking condition of Space heaters, Condition of machine foot. ROTOR: Shaft trueness checking, Shaft bearing seating area fitness checking, Visual inspection on the winding to find out any looseness of bars and crack in the end rings, DPT test on the bracing joints, Checking the other mechanical parts of the motor, Dynamic balancing the rotor to grade G 2.5
Checking the bearings and its clearance, inspecting the bearings.
Dismantling the worn out DE sleeve bearing from plumber block and re-fixing the New DE Bearing(Supplied by TANGEDCO). – If Necessary
Dismantling the worn out NDE sleeve bearing from plumber block and re-fixing the New NDE Bearing (Supplied by TANGEDCO). – If Necessary
Machining, grinding and polishing the NDE side rotor shaft bearing journal and labyrinth area and fabrication of labyrinth seal to match with rotor shaft new dimension.
COverhauling of Stator (VPI treated winding): Through cleaning of stator spares by using pressure water, Drying out in the oven, Applying resin on the winding, Baking in the oven, Conducting electrical tests on the stator including Tan delta and capacitance measurement, Applying anti tracking varnish on the overhang portion of winding,
Threading in the rotor, Assembling of motor and Conducting necessary test for trail run and painting
To and fro transport & transit insurance charges
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .