Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹2,000
Closing Date
8 Oct 2026, 5:00 pm
Executive Engineer, PWD, Electrical Division, MDU
O/o the Executive Engineer, PWD., Electrical Division, Tallakulam, Madurai - 625 002
Special Repairs to Electrical Installations, Improvements by Providing 5KVA UPS for Additional Circuit House at Theni in Theni District
2026_PWD_707408_1
14/DB/JDO-1/C-26/2026-2/Dt 22.09.2026
Open Tender
Electrical Works
Lump-sum
30 days
Additional Circuit House at Theni in Theni Distric
No
3 documents required · 3 mandatory
₹0
₹2,000
24 Sept 2026
24 Sept 2026
9 Oct 2026
24 Sept 2026
8 Oct 2026
24 Sept 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and fixing of 5kVA Three Phase In & Single Phase out Online UPS of Microcontroller based High frequency and Double Conversion Online Technology with inbuilt isolation transformer system, LCD/ LED Display with suitable SMF battery to provide minimum 1hour backup along with Powder coated MS Rack and interlink cables with following specifications: | 1 | No | 1,37,610 | ₹1,37,610 |
| 2 | a. Capacity 5000VA Pure sinewave
b. Input Voltage range 170V to 270V AC Single phase
c. Output Voltage 230V AC Single Phase
d. Backtime 1 Hour
e. Digital Indication Showing Mains ON, Inverter ON, Low Battery, Battery Voltage, Connected load in watts
f. Fuse Protection, in built resettable circuit breaker Protection | - | - | - | - |
| 3 | g. Voltage THD (Linear Load) : ≤2%
h. Voltage THD (Non-Linear Load) : ≤4%
i. Current THD : < 10%
j. Overload : >110%, 30s turn to Bypass mode; >150% instant turn to Bypass mode
k. Short Circuit protection : 5 cycles turn off inverter, no transfer to Bypass, provide Alarm (AC mode) ; 5cycles turn off inverter, provide Alarm (Battery mode), Input fuse blown or breaker action | - | - | - | - |
| 4 | l. Waveform : Pure sinewave
m. Transfer time : (AC mode to Battery mode - Zero) (Inverter to bypass - <4ms)
n. Efficiency : 85% to 92%
o. Noise Level : less than 50dBA @ 1meter (with fan speed control)
p. Warranty : Two years on Electronics & one year on battery.
(Microtek / Numeric make / Eq), (Battery make : Exide) | - | - | - | - |
| 5 | Supply and run of 2 of 2.5 Sqmm PVC insulated SC unsheated FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection of 2.5Sqmm copper wire with painting of suitable colour. | 148 | Mtrs | 203 | ₹30,044 |
| 6 | GST@ 18%(mailto:GST@%2018%25塹ᴻ䡿ⲯ嶂藄挧ꮥ) | 0.18 | times | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.37 MB
tno144.pdf
Tender Documents • 0.95 MB
BOQ_850152.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .